AERL technical documentation

AERL All-In-One — Datasheet Rev 1.2.1

4 pages

Download PDF Print
Download PDF· Rev 1.2.1 Datasheet

All-In-One

Commercial Energy Storage System

AERL All-In-One energy storage cabinet
25–50kWPower range
64.3–
112.5kWh
Storage capacity
<10msOff‑grid switching
IP55Cabinet, outdoor
aerl.com.au AIO-25K – AIO-50K Datasheet · Rev 1.2.1 · 2026

All-In-One

Commercial Energy Storage System

Hybrid inverter, battery modules, BMS, fire suppression and thermal management in one outdoor cabinet.

Product highlights

High energy performance

  • 20 A inputs with 4 MPPTs for optimised PV yield
  • 150 A charge/discharge for high-power cycling
  • 100% three-phase unbalance for diverse loads
  • 150% backup overload for surge protection

Flexible power architecture

  • Half-wave load support for industrial applications
  • Off-grid paralleling, up to 10 units
  • Diesel generator compatibility for weak-grid sites
  • Smart control for EV chargers and heat pumps

Robust safety & durability

  • Four-level fire protection with multi-sensor detection
  • IP66 inverter and IP55 cabinet for outdoor resilience
  • C4/C5 anti-corrosion for challenging environments
  • Integrated distribution with breakers, SPD, and UPS power

Intelligent control & O&M

  • Built-in EMS with multi-mode ToU scheduling
  • Dynamic pricing for automated energy optimisation
  • < 10 ms seamless off-grid switching
  • Remote monitoring and firmware updates
System ModelAIO-25KAIO-29.9KAIO-30KAIO-40KAIO-50K
Rated AC Output Power[kW]25.029.930.040.050.0
Dimensions, inverter fitted[W × H × D mm]1376 × 2262 × 1140
Battery Expansion[kWh]64.3 / 80.3 / 96.4 / 112.5
Operating Temperature Range[°C]−20 to 50
Relative Humidity[%]5–95 (non-condensing)
Max. Operation Altitude[m]3000
CoolingAir-conditioner with 2 kW cooling and 2 kW heating
Noise Level[dB]< 65
DisplayLED & OLED
CommunicationCAN, RS485
Hybrid Inverter ModelM2HT-25-150M2HT-29.9-150M2HT-30-150M2HT-40-150M2HT-50-150
PV Input
Max. PV Array Power[kWp]5060608080
Max. PV Input Voltage *[V]1000*
Rated PV Input Voltage[V]620
Start-up Voltage[V]135
MPPT Operating Voltage Range *[V]200–950*
No. of MPP Trackers44444
No. of Strings per MPPT2/2/2/22/2/2/22/2/2/22/2/2/22/2/2/2
Max. Input Current per MPPT[A]40/40/40/4040/40/40/4040/40/40/4040/40/40/4040/40/40/40
Max. Short-circuit Current per MPPT[A]50/50/50/5050/50/50/5050/50/50/5050/50/50/5050/50/50/50
All-In-One · Datasheet · Rev 1.2.1 Page 2 / 4
Hybrid Inverter ModelM2HT-25-150M2HT-29.9-150M2HT-30-150M2HT-40-150M2HT-50-150
Grid Side (On-Grid)
Rated Output Power[kW]25.029.930.040.050.0
Max. Output Apparent Power[kVA]25.029.930.040.050.0
Rated AC Voltage[V]3L/N/PE; 220/380 V; 230/400 V; 240/415 V
Rated AC Frequency[Hz]50/60
Rated Output Current[A]37.9/36.2/34.745.3/43.3/41.545.5/43.5/41.760.6/58/55.675.8/72.5/69.4
Power Factor0.8 leading … 0.8 lagging
THDi (@Rated Power)< 3%
Back-up Side (Off-Grid)
Rated Output Power[kW]25.029.930.040.050.0
Peak Output Apparent Power[kVA]37.5 @ 10 s45 @ 10 s45 @ 10 s60 @ 10 s75 @ 10 s
Rated Output Voltage[V]3L/N/PE; 220/380 V; 230/400 V; 240/415 V
Rated Output Frequency[Hz]50/60
Rated Output Current[A]37.9/36.2/34.745.3/43.3/41.545.5/43.5/41.760.6/58/55.675.8/72.5/69.4
On/Off-grid Switching Time< 10 ms
THDv (@Linear Load)< 3%
Generator Side
Max. Input Apparent Power[kVA]30.036.036.048.060.0
Rated Input Voltage[V]3L/N/PE; 220/380 V; 230/400 V
Rated Input Frequency[Hz]50/60
Max. Input Current[A]45.554.554.572.790.9
Efficiency
MPPT Efficiency99.90%
Max. Efficiency97.80%
European Efficiency97.40%
General Data
Dimensions[W × H × D mm]919 × 739 × 305
Weight[kg]89
Ingress ProtectionIP66
Standby Self-consumption[W]< 40
Battery ModelS64S80S96S112
Battery TypeLiFePO₄ / 314 Ah
Battery Module Quantity4 Packs5 Packs6 Packs7 Packs
Rated Energy[kWh]64.380.396.4112.5
Depth of Discharge90%
Rated Voltage[V]204.8256307.2358.4
Operating Voltage Range[V]166.4–233.6208–292249.6–350.4291.2–408.8
Max. Charge/Discharge Current[A]150/150
Dimensions[W × H × D mm]1050 × 2262 × 1140
Weight[kg]1101121413271440
Ingress ProtectionIP55
* Max. operating PV input voltage is 950 V. Between 950 V and 1000 V the inverter waits (does not operate); above 1000 V it is damaged.
All-In-One · Datasheet · Rev 1.2.1 Page 3 / 4
Manufactured by Solinteg
Supplied and supported in Australia by AERL

Australian Energy Research Laboratories

Address

1/75 Bluestone Circuit
Seventeen Mile Rocks QLD 4073
Australia

Contact

[email protected]
[email protected]

aerl.com.au Phone1800 950 865