AERL technical documentation

AERL — Compatibility Guide Rev 1.0.0

14 pages

Download PDF Print
Download PDF· Rev 1.0.0 Compatibility Guide

AERL Systems

Batteries, Inverters, Chargers and Monitoring

LiFe² · Kakadu 120 · CoolMax SRX · All-In-One · Nexus Compatibility GuideRev 1.0.0, 8 Nov 2026
aerl.com.au © 2026 AERL Pty Ltd

Contents

Document

Revision1.0.0
Effective11 / 2026
AudienceSystem designers, installers and integrators
CoversLiFe² 5120S · Kakadu 120 · CoolMax SRX and SRX-R · All-In-One · Solinteg M2HT · Nexus · EarthGuard
FormatA4 · 14 pages
AERL Compatibility GuideRev 1.0.0

About This Guide

This guide lists which AERL products work together, and with which third-party inverters, batteries and monitoring equipment. Each row names the AERL document that gives the connection details and settings. Use this guide to choose the equipment; use the named document to install it.

Every combination listed here is covered by a published AERL or manufacturer document. A combination that is not listed may still work, but AERL has not documented it: contact AERL before you design it in.

Settings and firmware requirements can change with third-party firmware. They are correct at the date of publication. Use the latest firmware the manufacturer offers.

Deye, Victron Energy, Selectronic, SP PRO, SP LINK, Solis, SMA, Sunny Island, Noark, Morningstar, Pylontech, Solinteg and other third-party names are trademarks of their respective owners. They are used here only to identify compatible equipment.

How to Read the Tables

TermMeaning
ManagedThe battery's BMS talks to the inverter over CAN bus and sends its charge and discharge limits and state of charge (SOC).
Self-ManagedNo communication. The charge settings are programmed into the inverter or charger by hand.
DC-coupledA CoolMax SRX or SRX-R charges the battery directly from PV; the inverter is a separate device on the same battery.
Minimum modulesThe smallest number of LiFe² 5120S modules that supports the full output of that inverter or charger.
Contact AERLNot covered by a published document. AERL can advise on the combination.
AERL Compatibility GuideRev 1.0.0
01

At a GlanceBatteries with inverters and chargers, products with AERL Cloud

1.1Batteries With Inverters and Chargers

BatteryVictron EnergyDeyeSelectronic SP PROSolisSMA Sunny IslandCoolMax SRX / SRX-R
LiFe² 5120S (51.2 V)ManagedManagedManaged or Self-ManagedManaged or Self-ManagedSelf-Managed48 V models
Kakadu 120 (140.8 V)Contact AERLContact AERLSPLC1200, SPLC1202, with the Nexus EMSContact AERLContact AERL120 V models, at least one per cabinet
All-In-One battery cabinets——————

The All-In-One battery cabinets are supplied with their Solinteg M2HT inverter, as one system (section 2.4).

1.2Products With AERL Cloud

ProductThrough the Nexus GatewayNotes
CoolMax SRX, SRX-RYes (CAN)Also read-only Modbus RTU for third-party monitoring
LiFe² 5120SYes (CAN)Nexus inline on the battery–inverter CAN bus
Kakadu 120Yes (CAN): the Nexus is requiredThe Nexus is also the system EMS
Selectronic SP PRO 2iYes (RS485 Modbus)SP PRO ACC Port 1
Battery SenseYes (CAN)On the SRX's CAN bus
CoolPro CP30Yes (RS485 Modbus)Through the CoolPro Meter Board
EarthGuard EG-600, EG-600-SCContact AERLAlarm relays to any monitoring input
All-In-One, Solinteg M2HTContact AERLSolinteg's own monitoring app and cloud
AERL Compatibility GuideRev 1.0.0
02

Batteries and InvertersLiFe² 5120S: Managed (CAN bus)

2.1LiFe² 5120S: Managed (CAN Bus)

The LiFe² 5120S starts in Managed mode by default. The master battery's COMM port carries CAN on pins 4 and 5. Default depth of discharge for every managed inverter: 80% (20% SOC low cut-off).

InverterModelsBattery settingDocument
Victron EnergyAll 48 V Multis, MultiPlus, Quattros and RS models, through a GX device (BMS-Can port)CAN-bus profile CAN-bus BMS LV (500 kbit/s); the battery shows as PylontechLiFe² Managed Battery Integration Guide, ch. 03
DeyeLow-voltage hybrids on Deye's approved battery list: single phase SUN-(3.6–8)K-SG05LP1-EU and -AU, SUN-(3–6)K-SG03LP1-EU, SUN-(3–6)K-SG04LP1-EU and -AU, SUN-(7.6–8)K-SG01LP1-EU, SUN-(12–16)K-SG01LP1-EU, SUN-(5–8)K-SG01LP1-US; three phase SUN-(5–12)K-SG04LP3-EU and -AUBatt Mode Lithium, Lithium Mode 00LiFe² Managed Battery Integration Guide, ch. 04
Selectronic SP PROSeries 2i SPMC480, SPMC481, SPMC482; Series II with Selectronic's Managed Battery Upgrade Kit (005295). Not Series ISP LINK battery type AERL LiFe2-5120SLiFe² Managed Battery Integration Guide, ch. 05
SolisS6-EH1P(3–8)K-L-PRO, S6-EH1P(3–6)K-L, S6-EO1P(4–5)K-48, S5-EH1P(3–6)K-LBattery Model Lithium Battery LV (not the RS485 variant)LiFe² Managed Battery Integration Guide, ch. 06
CoolMax SRX / SRX-R (48 V)SRX 600/70-48, SRX-R 600/60-48Charge profile in AERL Link, within the battery's charge settings; on the battery's CAN bus the SRX stops charging on a battery alarmCoolMax SRX DC-Coupling Design Guide
NoarkEx9N-DH-3KS-AU to Ex9N-DH-12KT-AUContact AERLLiFe² PCE Integration Guide, §1.4 (minimum modules)
AERL Compatibility GuideRev 1.0.0

2.2LiFe² 5120S: Self-Managed (No Comms)

Use Self-Managed mode with inverters and chargers that have no communication link to the battery. Program the charge settings by hand: charge voltage 56 V, maximum charge current 70 A and maximum discharge current 100 A per module, 90% maximum depth of discharge (recommended setting).

Inverter or chargerModelsDocument
Selectronic SP PROSPMC480, SPMC481, SPMC482LiFe² PCE Integration Guide, ch. 3
SolisRHI-(3–6)K-48ES-5G, RAI-3K-48ES-5G, S5-EH1P(3–6)K-L, S5-EO1P(4–5)K-48(-P), S6-EO1P(4–5)K-48, S6-EH1P(3–6)K-L-EU, S6-EH1P(3–8)K-L-PROLiFe² PCE Integration Guide, ch. 4
SMA Sunny IslandSI 4.4M, SI 6.0H, SI 8.0H (with an external shunt for SOC)LiFe² PCE Integration Guide, ch. 5
CoolMax SRX / SRX-R (48 V)SRX 600/70-48, SRX-R 600/60-48CoolMax SRX DC-Coupling Design Guide
Other inverters and chargersAny that allow the charge settings to be set to the battery's requirementsContact AERL for the settings

The minimum number of modules for each inverter is in the LiFe² System Sizing Guide.

2.3Kakadu 120

The Kakadu 120 (140.8 V nominal) needs an AERL Nexus Gateway on its CAN bus, and is designed for DC coupling with the CoolMax SRX 120 V.

EquipmentCombinationDocument
Selectronic SP PRO SPLC1200, SPLC1202One SP PRO per Kakadu 120 cabinet. The SP PRO runs the Kakadu as a managed battery: SP LINK battery type BMS – SelectCell River GumKakadu Commissioning Guide (SPLC1202 and CoolMax SRX); Kakadu 120 SPLC12xx Sizing Guide
CoolMax SRX 600/30-120At least one per Kakadu cabinet, on the Kakadu CAN bus; charges to target points set by the NexusKakadu Commissioning Guide
AERL Nexus GatewayOne per system: the EMS. AERL installs the EMS firmware on the Nexus and every SRX during commissioningKakadu Commissioning Guide
Other invertersContact AERL—
AERL Compatibility GuideRev 1.0.0

2.4All-In-One and Solinteg M2HT Batteries

The All-In-One is supplied with its own Solinteg battery cabinet and needs no other battery:

SystemInverterBattery
All-In-One 25–50 kWSolinteg M2HT-25-150 to M2HT-50-150Solinteg E2BR-S64K-C, -S80K-C, -S96K-C or -S112K-C
All-In-One Max 125/257 (off-grid; grid connection pending CEC listing)Solinteg M2HT-125K-300Solinteg E2BR-S257K-C

For a Solinteg M2HT 75–125 kW sold on its own (grid connection pending CEC listing), contact AERL. A Solinteg M2HT 25–50 kW inverter sold on its own works only with high-voltage LFP batteries with a BMS on Solinteg's compatibility list, connected over CAN, within its 150–840 V battery range. These are the batteries Solinteg lists for the M2HT 25–50 kW (Solinteg compatibility list Ver. 2.03, 22 July 2025):

Battery brandBattery ID in the inverterBattery models
SolintegSolinteg_HVEBS-B2K5-B, EBA-B5K1; EBR-B5K3-A
PylontechPylon_HVForce H1/H2/H2(-V2)/H3; Powercube X1/X2/H1/H2(-V2); Powercube M1/M2/M3/M5A
DynessDynessTower/Tower Pro; PowerRack (HV1/HV2/HV4/HV4F), PowerStone, Stack100
WattsonicWattli_HV3.84kWh Commercial (6–17/Rack)
SolunaSoluna_HVSoluna 10K HV, Soluna 15K HV; Power Cell-60 Series, Power Cell-150 Series
WecoWeco_HV4K5XP ULTRA; 5K3XP, 14K3XP (High Voltage)
Lithium ValleyDefault HV_1LV-BST-H2.56 / 5.12
SunwodaSunwoda_HVSunESS-H
RaystechDefault HV_1RT5427 HV, RT5427 SHV; RT5000B, RT5427-HV-RACK
ZetaraDefault HV_1Inspiration DC3000; Zbox100
UhomeDefault HV_1LFP 5427 HV, LFP 5427 SHV; LFP 5000 HV, LFP 5000S HV, LFP 5000B
ShotoDefault HV_1HP-SG
CegasaDefault HV_1E/Scal HV
Unlisted batteries

Solinteg states that a battery not on its list voids the inverter warranty, unless Solinteg has issued a compatibility statement for it. Solinteg updates its list from time to time: check with AERL that a battery is still listed before you order it.

AERL Compatibility GuideRev 1.0.0
03

CoolMax SRX and SRX‑R Charge ControllersBatteries, inverters (DC coupling), Communications

3.1Batteries

BatteryControllersHow it works
AERL LiFe² 5120S (48 V)SRX 600/70-48, SRX-R 600/60-48The SRX charges to its own profile, set within the battery's charge settings; on the battery's CAN bus it stops charging when the battery reports an alarm. Minimum 1 module (LiFe² PCE Integration Guide, §1.1).
AERL Kakadu 120 (140.8 V)SRX 600/30-120Through the Nexus EMS (Kakadu Commissioning Guide).
Batteries that publish Pylontech-style CAN framesAllThe SRX listens to the battery's alarm frame (0x359): an alarm stops charging. No configuration; the SRX charges to its own profile (CoolMax SRX DC-Coupling Design Guide, section 2.3).
Other lithium and lead-acid batteriesAll, within the battery voltage range: 18–30 Vdc (24 V) or 40–60 Vdc (48 V); 90–170 Vdc (120 V)Standalone, with a charge profile set in AERL Link to the battery manufacturer's specification. Banks without their own temperature reporting (typically lead-acid) need an AERL Battery Sense, on a CoolMax SRX.

The SRX default charge profile suits a generic LiFePO4 battery. AERL supports most other chemistries that do not need external BMS communication. The SRX-R 600/30-120 and SRX 600/30-120 are for 120 V batteries only.

AERL Compatibility GuideRev 1.0.0

3.2Inverters (DC Coupling)

The SRX does not communicate with third-party inverters. It charges the battery directly, and the inverter shares the battery.

InverterWhat is documentedDocument
Selectronic SP PRO (48 V)A current shunt in the SRX output gives the SP PRO the solar current; the SP PRO's SOC resets to 100% on a voltage offset, as the SRX has no float switch outputSP PRO with CoolMax SRX Integration Guide; Selectronic DC Coupled Example System
Selectronic SP PRO SPLC1200, SPLC1202 (120 V)With the Kakadu 120, through the Nexus EMSKakadu Commissioning Guide
Victron Energy, Deye and other battery invertersStandalone SRX with a charge profile, on a battery the inverter managesCoolMax SRX DC-Coupling Design Guide
Other charge controllers

Do not connect CoolMax controllers in parallel with third-party charge controllers.

3.3Communications

InterfaceUse
CAN busMonitoring and control: enable and disable, Power Targets, firmware updates. Two linked RJ45 sockets labelled CANBUS. 500 kbps default (125 and 250 kbps selectable).
RS485 (Modbus RTU)Read-only monitoring. Two linked RJ45 sockets labelled MODBUS, with their own pin-out.
USBAERL Link (Windows 10/11): charge profile, settings and firmware updates.
AERL Compatibility GuideRev 1.0.0
04

Monitoring and AccessoriesAERL Nexus Gateway, Battery Sense

4.1AERL Nexus Gateway

The Nexus connects equipment to AERL Cloud. It finds supported devices on its CAN bus by itself; a Modbus or SNMP device is set up on the gateway in AERL Cloud (one of each per gateway).

Device typeSupported equipmentConnects by
ChargerAERL CoolMax SRX, SRX-RCAN
BatteryAERL LiFe² 5120S, AERL Kakadu 120, Pylontech US5000CAN
InverterSelectronic SP PRO 2i; Deye hybrid inverter (low-voltage, three-phase)RS485 Modbus to SP PRO ACC Port 1 (SP PRO); contact AERL (Deye)
Cathodic protectionAERL CoolPro CP30RS485 Modbus (CoolPro Meter Board)
SensorAERL Battery SenseCAN (on the SRX bus)
Earth-fault monitorAERL EarthGuardContact AERL
UPSABB Upscale UPSSNMP

The authoritative, current list is in the AERL Cloud documentation at docs.aerl.cloud. The Nexus CAN ports run at a fixed 500 kbps: every device on the bus must use 500 kbps. The two CAN sockets are linked inside the Nexus and have no built-in termination: at an end of the bus, fit a 120 Ω plug in the spare socket.

ModelPorts
Nexus Lite (NEXUS-LITE)2 × CAN (RJ45, linked), 1 × RS485, Ethernet, dual-band Wi-Fi; 12–60 Vdc or 5 V USB-C
Nexus 4G (NEXUS-4G)As the Nexus Lite, plus a 4G cellular modem, digital inputs and output relays

4.2Battery Sense

The AERL Battery Sense gives a CoolMax SRX the battery's temperature and voltage, for banks without a BMS that reports them. It plugs into a CANBUS port on the SRX (which powers it at 5 V; turn the SRX's CANBUS 5 V switch on), on cable up to 10 m, and measures 18–200 Vdc.

AERL Compatibility GuideRev 1.0.0

4.3EarthGuard EG-600 and EG-600-SC

The EarthGuard monitors insulation on DC circuits from 40 Vdc to 600 Vdc (two circuits on the EG-600, one on the EG-600-SC), powered from 12–60 Vdc. All AERL products are compatible. Third-party equipment listed in the EarthGuard manuals:

For other equipment, check the device's earth-leakage specification before installation. Some third-party devices can exceed the permissible leakage and trip the EarthGuard. The alarm relays (dry contact, normally open, fail-safe) can signal a monitoring input such as a Victron Cerbo GX relay input.

4.4CoolPro CP30

The CoolPro CP30 Meter Board connects to the Nexus RS485 Modbus port for AERL Cloud monitoring (CoolPro User Manual and CoolPro Modbus RTU Communications Protocol).

AERL Compatibility GuideRev 1.0.0
05

Minimum Firmware and Software

EquipmentMinimum versionNeeded for
Selectronic SP PRO firmware16.11LiFe² 5120S Managed
Selectronic comms card firmware5.31LiFe² 5120S Managed
Selectronic SP LINK16.11 (includes both firmware versions)LiFe² 5120S Managed
Selectronic SP PRO firmwareV14.47Kakadu 120
Selectronic SP PRO ACC firmwareV4.31Kakadu 120
Selectronic SP LINKA version that lists BMS – SelectCell River GumKakadu 120
Victron VE.Bus firmware469LiFe² 5120S Managed
Victron Inverter RS / Multi RS firmware1.16LiFe² 5120S Managed
Victron GX deviceLatestLiFe² 5120S Managed
CoolMax SRX / SRX-R firmware2.15.8The SRX and SRX-R user manuals
CoolMax SRX / SRX-R firmwareAny release from 2.0.1Ground fault trip fixed at 50 kΩ (earlier firmware had a sensitivity setting)
AERL Nexus and SRX EMS firmwareInstalled by AERLKakadu 120 with the Nexus EMS
AERL LinkLatest, from aerl.com.au/professionalsSRX, SRX-R, EarthGuard settings and firmware
Solinteg M2HT firmwareConfirm with AERLParallel and generator systems
AERL Compatibility GuideRev 1.0.0
06

Warranty and SupportUsing unlisted equipment, support, change log

6.1Using Unlisted Equipment

Third-party equipment must be installed and set up as its manufacturer instructs. Damage caused by incompatible equipment or by settings outside a battery's specification is not covered by AERL's warranties: see each product's warranty statement, at aerl.com.au. For Solinteg inverters, an unlisted battery voids the inverter warranty.

6.2Support

Before you contact AERL about a combination, note the equipment models and firmware versions. Contact AERL support on 1800 950 865 or [email protected].

6.3Change Log

RevisionDateChange
1.0.011 / 2026First issue.

Thank You for Choosing AERL

If you have any questions or need support, contact AERL.

Sincerely,

The AERL Team

AERL Pty Ltd · 1/75 Bluestone Circuit, Seventeen Mile Rocks QLD 4073 · 1800 950 865 · [email protected] · aerl.com.au

AERL Compatibility GuideRev 1.0.0

Notes

AERL Compatibility GuideRev 1.0.0

Notes

AERL Compatibility GuideRev 1.0.0

Australian Energy Research Laboratories

Address

1/75 Bluestone Circuit
Seventeen Mile Rocks QLD 4073
Australia

Contact

[email protected]
[email protected]

aerl.com.au Phone1800 950 865