The CoolMax SRX 300 series (SRX HV 300 and SRX MV 300) supports Modbus RTU over RS485 and CAN for remote monitoring and control. This document gives the Modbus memory map and the CAN messages. The CoolMax SRX 300 is no longer manufactured; this protocol is published for systems already installed. For anything not covered here, contact AERL support.
1.1 Physical Connection
Both interfaces are on the controller's RJ45 comms sockets (SRX HV 300: Comms 1 and Comms 2; SRX MV 300: one socket), at the bottom of the controller.
Pin
Signal
1
+12 V (CAN)
2
+12 V (Modbus)
3
CAN-L
4
RS485-A
5
CAN-H
6
RS485-B
7
Not connected
8
Isolated GND
1.2 Network Topology
Modbus and CAN are both linear buses, with short stubs branching from T connectors on the main backbone to each device. Terminate each end of the backbone with a 120 Ω resistor: between RS485-A and RS485-B for Modbus, and between CAN-H and CAN-L for CAN. Several CoolMax SRX controllers can share one bus, and the bus can be connected to other networks with a Modbus-to-Ethernet or CAN-to-Ethernet bridge.
CoolMax SRX 300 · Modbus and CAN Protocol
Rev 1.016 Nov 2026
Chapter 02
2. Modbus RTU
2.1 Communication Parameters
Parameter
Value
Interface
RS485, Modbus RTU
Bit rate
9600 bps
Modbus address
1–128
Measurement data
IEEE 754 single-precision (32-bit) float, most significant byte first
Data types
16-bit values in one register; 32-bit integers and floats over two registers; 64-bit values over four registers
Register addresses below are given in the conventional Modbus form: discrete input 10001 is offset 0 (read with function 02), and input register 30001 is offset 0 (read with function 04). In each multi-register value the first register holds bytes 1 and 2, the second bytes 3 and 4, and so on, high byte first in each register.
2.2 Discrete Inputs (Single Bit, Read-Only)
A read returns a byte holding 8 consecutive inputs, with the addressed input as the least significant bit. If the quantity read is not a multiple of 8, the last byte is padded with zeros.
Active events (1 = event triggered, 0 = event cleared)
Data frames for most communication; remote frames enabled
Data field
Always 8 bytes
Measurement data
IEEE 754 single-precision (32-bit) float
CoolMax SRX 300 · Modbus and CAN Protocol
Rev 1.016 Nov 2026
3.2 Identifier
The 11-bit identifier is split in two: bits 10–5 hold the device identifier and bits 4–0 the message identifier. A controller's base address is its device identifier in bits 10–5 with bits 4–0 at zero; each message below is sent at the base address plus its message number.
Bits 10–5
Bits 4–0
Device identifier
Message identifier
3.3 Data Field
The 8-byte data field holds two 32-bit values: the high value in bits 63–32 and the low value in bits 31–0. It is sent and expected least significant byte first, so on a little-endian processor the field overlays a float[2] (or char[8]) array directly.
3.4 Broadcast Messages
The CoolMax SRX broadcasts these data frames periodically.