CoolMax SRX 300 Series Modbus and CAN Communications Protocol

SRX HV 300/30 · SRX HV 300/40 · SRX MV 300/50 · SRX MV 300/60 · Legacy Product
SRX HV 300 · SRX MV 300
Chapter 01

1. Overview

The CoolMax SRX 300 series (SRX HV 300 and SRX MV 300) supports Modbus RTU over RS485 and CAN for remote monitoring and control. This document gives the Modbus memory map and the CAN messages. The CoolMax SRX 300 is no longer manufactured; this protocol is published for systems already installed. For anything not covered here, contact AERL support.

1.1 Physical Connection

Both interfaces are on the controller's RJ45 comms sockets (SRX HV 300: Comms 1 and Comms 2; SRX MV 300: one socket), at the bottom of the controller.

PinSignal
1+12 V (CAN)
2+12 V (Modbus)
3CAN-L
4RS485-A
5CAN-H
6RS485-B
7Not connected
8Isolated GND

1.2 Network Topology

Modbus and CAN are both linear buses, with short stubs branching from T connectors on the main backbone to each device. Terminate each end of the backbone with a 120 Ω resistor: between RS485-A and RS485-B for Modbus, and between CAN-H and CAN-L for CAN. Several CoolMax SRX controllers can share one bus, and the bus can be connected to other networks with a Modbus-to-Ethernet or CAN-to-Ethernet bridge.

CoolMax SRX 300 · Modbus and CAN Protocol · Rev 1.0Page 1 / 6© 2026 AERL Pty Ltd
CoolMax SRX 300 · Modbus and CAN Protocol
Rev 1.016 Nov 2026
Chapter 02

2. Modbus RTU

2.1 Communication Parameters

ParameterValue
InterfaceRS485, Modbus RTU
Bit rate9600 bps
Modbus address1–128
Measurement dataIEEE 754 single-precision (32-bit) float, most significant byte first
Data types16-bit values in one register; 32-bit integers and floats over two registers; 64-bit values over four registers

Register addresses below are given in the conventional Modbus form: discrete input 10001 is offset 0 (read with function 02), and input register 30001 is offset 0 (read with function 04). In each multi-register value the first register holds bytes 1 and 2, the second bytes 3 and 4, and so on, high byte first in each register.

2.2 Discrete Inputs (Single Bit, Read-Only)

A read returns a byte holding 8 consecutive inputs, with the addressed input as the least significant bit. If the quantity read is not a multiple of 8, the last byte is padded with zeros.

Active events (1 = event triggered, 0 = event cleared)

AddressOffsetEvent
100010System power
100021Low output voltage warning
100032Low output voltage fault
100043Low output voltage, genset
100054High output voltage fault
100065High output current fault
100076High discharge current fault
100087High battery temperature fault
100098Input breaker open
100109Output breaker open
1001110Temperature sensor fault
1001211Negative PV current shutdown
1001312High PV current shutdown
1001413High PV voltage shutdown
1001514High output current shutdown
1001615High output voltage shutdown
1001716Heatsink temperature too high
1001817Fan fault
1001918Log file full
CoolMax SRX 300 · Modbus and CAN Protocol · Rev 1.0Page 2 / 6© 2026 AERL Pty Ltd
CoolMax SRX 300 · Modbus and CAN Protocol
Rev 1.016 Nov 2026
AddressOffsetEvent
1002019Solar panel missing
1002120Configuration value out of range
10022–1003221–31Reserved

Status

AddressOffsetStatusValue
1003332Factory configuration CRC1 = valid, 0 = invalid
1003433Factory configuration check1 = passed, 0 = failed
1003534User configuration CRC1 = valid, 0 = invalid
1003635User configuration check1 = passed, 0 = failed
1003736Event configuration CRC1 = valid, 0 = invalid
1003837Event configuration check1 = passed, 0 = failed
1003938Telemetry configuration CRC1 = valid, 0 = invalid
1004039Telemetry configuration check1 = passed, 0 = failed
10041–1008040–79Reserved (statistics, flags, telemetry, communications, flash)—
1008180Master / slave0 = master, 1 = slave
1008281Active set point0 = float set point, 1 = bulk set point
10083–1008482–83Control mode (2-bit field)0 = MPPT, 1 = output voltage, 2 = input voltage, 3 = not used
10085–1008884–87Reserved—
1008988Safety shutdown state0 = shut down, 1 = operating
10090–1009689–95Reserved—

2.3 Input Registers (16-Bit, Read-Only)

Each register returns two bytes (0–65535).

CoolMax SRX 300 · Modbus and CAN Protocol · Rev 1.0Page 3 / 6© 2026 AERL Pty Ltd
CoolMax SRX 300 · Modbus and CAN Protocol
Rev 1.016 Nov 2026

Live telemetry

AddressOffsetValueType
30001–300040–3Product ID (8 characters)ASCII
30005–300084–7Serial number (8 characters)ASCII
30009–300108–9PV voltage (V)Float
30011–3001210–11PV current (A)Float
30013–3001412–13Output voltage (V)Float
30015–3001614–15Output current (A)Float
30017–3001816–17PV open-circuit voltage (V)Float
30019–3002018–19Daily output charge (Ah)Float
30021–3002220–21PV power (W)Float
30023–3002422–23Case temperature (°C)Float
30025–3002624–25Active eventsUInt32
30027–3003026–29Status flagsUInt64
30031–3003430–33Unix timeUInt64
30035–3004034–39Reserved—

The discrete inputs (section 2.2) give each event and status bit individually.

System information

AddressOffsetValueType
30041–3004440–43Hardware version (8 characters)ASCII
30045–3004844–47Firmware version (8 characters)ASCII
30049–3005048–49Model type (4 characters)ASCII
30051–3005450–53Product ID (8 characters)ASCII
30055–3005854–57Serial number (8 characters)ASCII
30059–3006458–63Reserved—
Chapter 03

3. CAN

3.1 Communication Parameters

ParameterValue
HardwareCAN 2.0B compatible; 11-bit standard identifiers
Bit rates1 Mbps, 500 kbps (default), 250 kbps, 125 kbps, 100 kbps, 50 kbps
FramesData frames for most communication; remote frames enabled
Data fieldAlways 8 bytes
Measurement dataIEEE 754 single-precision (32-bit) float
CoolMax SRX 300 · Modbus and CAN Protocol · Rev 1.0Page 4 / 6© 2026 AERL Pty Ltd
CoolMax SRX 300 · Modbus and CAN Protocol
Rev 1.016 Nov 2026

3.2 Identifier

The 11-bit identifier is split in two: bits 10–5 hold the device identifier and bits 4–0 the message identifier. A controller's base address is its device identifier in bits 10–5 with bits 4–0 at zero; each message below is sent at the base address plus its message number.

Bits 10–5Bits 4–0
Device identifierMessage identifier

3.3 Data Field

The 8-byte data field holds two 32-bit values: the high value in bits 63–32 and the low value in bits 31–0. It is sent and expected least significant byte first, so on a little-endian processor the field overlays a float[2] (or char[8]) array directly.

3.4 Broadcast Messages

The CoolMax SRX broadcasts these data frames periodically.

ID (base +)MessageBitsTypeValue
0Identification63–32UInt32Serial number, allocated at manufacture
31–0UInt32Product ID, "A001" as a string
1PV measurement63–32FloatPV current (A)
31–0FloatPV voltage (V)
2Output measurement63–32FloatOutput current (A)
31–0FloatOutput voltage (V)
3PV open-circuit voltage and charge63–32FloatOutput charge
31–0FloatPV open-circuit voltage (V)
4PV power and battery temperature63–32FloatBattery temperature (°C)
31–0FloatPV power (W)
5Active flags63–0BitsSee section 3.5
7Time63–0UInt64System Unix time
CoolMax SRX 300 · Modbus and CAN Protocol · Rev 1.0Page 5 / 6© 2026 AERL Pty Ltd
CoolMax SRX 300 · Modbus and CAN Protocol
Rev 1.016 Nov 2026

3.5 Active Flags (Base + 5)

BitFlagMeaning
0Vout low warningLow output voltage warning
1Vout low faultLow output voltage fault
2—Not used
3Vout high faultHigh output voltage fault
4Iout faultHigh output current fault
5Bat currentHigh battery discharge current fault
6Hi bat tempHigh battery temperature fault
7–8—Not used
9Bat temp sensor faultBattery temperature sensor fault
10Maximizer faultRegulation or power stage fault
11Log file fullLog file full
12Panel missingInput voltage indicates the panel is missing
13–63—Not used