title: "CoolMax SRX 300 Series Modbus and CAN Communications Protocol · Communications Protocol"
revision: "1.0"
publisher: AERL (Australian Energy Research Laboratories)
url: https://www.aerl.com.au/docs/coolmax-srx-300-modbus-can-protocol
pdf: https://www.aerl.com.au/documents/obsolete/AERL_CoolMax_SRX_300_Modbus_CAN_Protocol_REV_1.0.pdf
description: "Modbus RTU memory map and CAN messages for the discontinued CoolMax SRX HV 300 and SRX MV 300 charge controllers."
---

# CoolMax SRX 300 Series Modbus and CAN Communications Protocol · Communications Protocol

*Rev 1.0. Markdown copy of the AERL document at https://www.aerl.com.au/docs/coolmax-srx-300-modbus-can-protocol; the PDF (https://www.aerl.com.au/documents/obsolete/AERL_CoolMax_SRX_300_Modbus_CAN_Protocol_REV_1.0.pdf) is the controlled version.*

Communications Protocol

# CoolMax SRX 300 Series Modbus and CAN Communications Protocol

SRX HV 300/30 · SRX HV 300/40 · SRX MV 300/50 · SRX MV 300/60 · Legacy Product

SRX HV 300 · SRX MV 300

## Chapter 01 1. Overview

The CoolMax SRX 300 series (SRX HV 300 and SRX MV 300) supports Modbus RTU over RS485 and CAN for remote monitoring and control. This document gives the Modbus memory map and the CAN messages. The CoolMax SRX 300 is no longer manufactured; this protocol is published for systems already installed. For anything not covered here, contact AERL support.

### 1.1 Physical Connection

Both interfaces are on the controller's RJ45 comms sockets (SRX HV 300: Comms 1 and Comms 2; SRX MV 300: one socket), at the bottom of the controller.

| Pin | Signal |
|---|---|
| 1 | +12 V (CAN) |
| 2 | +12 V (Modbus) |
| 3 | CAN-L |
| 4 | RS485-A |
| 5 | CAN-H |
| 6 | RS485-B |
| 7 | Not connected |
| 8 | Isolated GND |

### 1.2 Network Topology

Modbus and CAN are both linear buses, with short stubs branching from T connectors on the main backbone to each device. Terminate each end of the backbone with a 120 Ω resistor: between RS485-A and RS485-B for Modbus, and between CAN-H and CAN-L for CAN. Several CoolMax SRX controllers can share one bus, and the bus can be connected to other networks with a Modbus-to-Ethernet or CAN-to-Ethernet bridge.

## Chapter 02 2. Modbus RTU

### 2.1 Communication Parameters

| Parameter | Value |
|---|---|
| Interface | RS485, Modbus RTU |
| Bit rate | 9600 bps |
| Modbus address | 1–128 |
| Measurement data | IEEE 754 single-precision (32-bit) float, most significant byte first |
| Data types | 16-bit values in one register; 32-bit integers and floats over two registers; 64-bit values over four registers |

Register addresses below are given in the conventional Modbus form: discrete input 10001 is offset 0 (read with function 02), and input register 30001 is offset 0 (read with function 04). In each multi-register value the first register holds bytes 1 and 2, the second bytes 3 and 4, and so on, high byte first in each register.

### 2.2 Discrete Inputs (Single Bit, Read-Only)

A read returns a byte holding 8 consecutive inputs, with the addressed input as the least significant bit. If the quantity read is not a multiple of 8, the last byte is padded with zeros.

#### Active events (1 = event triggered, 0 = event cleared)

| Address | Offset | Event |
|---|---|---|
| 10001 | 0 | System power |
| 10002 | 1 | Low output voltage warning |
| 10003 | 2 | Low output voltage fault |
| 10004 | 3 | Low output voltage, genset |
| 10005 | 4 | High output voltage fault |
| 10006 | 5 | High output current fault |
| 10007 | 6 | High discharge current fault |
| 10008 | 7 | High battery temperature fault |
| 10009 | 8 | Input breaker open |
| 10010 | 9 | Output breaker open |
| 10011 | 10 | Temperature sensor fault |
| 10012 | 11 | Negative PV current shutdown |
| 10013 | 12 | High PV current shutdown |
| 10014 | 13 | High PV voltage shutdown |
| 10015 | 14 | High output current shutdown |
| 10016 | 15 | High output voltage shutdown |
| 10017 | 16 | Heatsink temperature too high |
| 10018 | 17 | Fan fault |
| 10019 | 18 | Log file full |

| Address | Offset | Event |
|---|---|---|
| 10020 | 19 | Solar panel missing |
| 10021 | 20 | Configuration value out of range |
| 10022–10032 | 21–31 | Reserved |

#### Status

| Address | Offset | Status | Value |
|---|---|---|---|
| 10033 | 32 | Factory configuration CRC | 1 = valid, 0 = invalid |
| 10034 | 33 | Factory configuration check | 1 = passed, 0 = failed |
| 10035 | 34 | User configuration CRC | 1 = valid, 0 = invalid |
| 10036 | 35 | User configuration check | 1 = passed, 0 = failed |
| 10037 | 36 | Event configuration CRC | 1 = valid, 0 = invalid |
| 10038 | 37 | Event configuration check | 1 = passed, 0 = failed |
| 10039 | 38 | Telemetry configuration CRC | 1 = valid, 0 = invalid |
| 10040 | 39 | Telemetry configuration check | 1 = passed, 0 = failed |
| 10041–10080 | 40–79 | Reserved (statistics, flags, telemetry, communications, flash) | — |
| 10081 | 80 | Master / slave | 0 = master, 1 = slave |
| 10082 | 81 | Active set point | 0 = float set point, 1 = bulk set point |
| 10083–10084 | 82–83 | Control mode (2-bit field) | 0 = MPPT, 1 = output voltage, 2 = input voltage, 3 = not used |
| 10085–10088 | 84–87 | Reserved | — |
| 10089 | 88 | Safety shutdown state | 0 = shut down, 1 = operating |
| 10090–10096 | 89–95 | Reserved | — |

### 2.3 Input Registers (16-Bit, Read-Only)

Each register returns two bytes (0–65535).

#### Live telemetry

| Address | Offset | Value | Type |
|---|---|---|---|
| 30001–30004 | 0–3 | Product ID (8 characters) | ASCII |
| 30005–30008 | 4–7 | Serial number (8 characters) | ASCII |
| 30009–30010 | 8–9 | PV voltage (V) | Float |
| 30011–30012 | 10–11 | PV current (A) | Float |
| 30013–30014 | 12–13 | Output voltage (V) | Float |
| 30015–30016 | 14–15 | Output current (A) | Float |
| 30017–30018 | 16–17 | PV open-circuit voltage (V) | Float |
| 30019–30020 | 18–19 | Daily output charge (Ah) | Float |
| 30021–30022 | 20–21 | PV power (W) | Float |
| 30023–30024 | 22–23 | Case temperature (°C) | Float |
| 30025–30026 | 24–25 | Active events | UInt32 |
| 30027–30030 | 26–29 | Status flags | UInt64 |
| 30031–30034 | 30–33 | Unix time | UInt64 |
| 30035–30040 | 34–39 | Reserved | — |

The discrete inputs (section 2.2) give each event and status bit individually.

#### System information

| Address | Offset | Value | Type |
|---|---|---|---|
| 30041–30044 | 40–43 | Hardware version (8 characters) | ASCII |
| 30045–30048 | 44–47 | Firmware version (8 characters) | ASCII |
| 30049–30050 | 48–49 | Model type (4 characters) | ASCII |
| 30051–30054 | 50–53 | Product ID (8 characters) | ASCII |
| 30055–30058 | 54–57 | Serial number (8 characters) | ASCII |
| 30059–30064 | 58–63 | Reserved | — |

## Chapter 03 3. CAN

### 3.1 Communication Parameters

| Parameter | Value |
|---|---|
| Hardware | CAN 2.0B compatible; 11-bit standard identifiers |
| Bit rates | 1 Mbps, 500 kbps (default), 250 kbps, 125 kbps, 100 kbps, 50 kbps |
| Frames | Data frames for most communication; remote frames enabled |
| Data field | Always 8 bytes |
| Measurement data | IEEE 754 single-precision (32-bit) float |

### 3.2 Identifier

The 11-bit identifier is split in two: bits 10–5 hold the **device identifier** and bits 4–0 the **message identifier**. A controller's base address is its device identifier in bits 10–5 with bits 4–0 at zero; each message below is sent at the base address plus its message number.

| Bits 10–5 | Bits 4–0 |
|---|---|
| Device identifier | Message identifier |

### 3.3 Data Field

The 8-byte data field holds two 32-bit values: the high value in bits 63–32 and the low value in bits 31–0. It is sent and expected least significant byte first, so on a little-endian processor the field overlays a `float[2]` (or `char[8]`) array directly.

### 3.4 Broadcast Messages

The CoolMax SRX broadcasts these data frames periodically.

| ID (base +) | Message | Bits | Type | Value |
|---|---|---|---|---|
| 0 | Identification | 63–32 | UInt32 | Serial number, allocated at manufacture |
|  |  | 31–0 | UInt32 | Product ID, "A001" as a string |
| 1 | PV measurement | 63–32 | Float | PV current (A) |
|  |  | 31–0 | Float | PV voltage (V) |
| 2 | Output measurement | 63–32 | Float | Output current (A) |
|  |  | 31–0 | Float | Output voltage (V) |
| 3 | PV open-circuit voltage and charge | 63–32 | Float | Output charge |
|  |  | 31–0 | Float | PV open-circuit voltage (V) |
| 4 | PV power and battery temperature | 63–32 | Float | Battery temperature (°C) |
|  |  | 31–0 | Float | PV power (W) |
| 5 | Active flags | 63–0 | Bits | See section 3.5 |
| 7 | Time | 63–0 | UInt64 | System Unix time |

### 3.5 Active Flags (Base + 5)

| Bit | Flag | Meaning |
|---|---|---|
| 0 | Vout low warning | Low output voltage warning |
| 1 | Vout low fault | Low output voltage fault |
| 2 | — | Not used |
| 3 | Vout high fault | High output voltage fault |
| 4 | Iout fault | High output current fault |
| 5 | Bat current | High battery discharge current fault |
| 6 | Hi bat temp | High battery temperature fault |
| 7–8 | — | Not used |
| 9 | Bat temp sensor fault | Battery temperature sensor fault |
| 10 | Maximizer fault | Regulation or power stage fault |
| 11 | Log file full | Log file full |
| 12 | Panel missing | Input voltage indicates the panel is missing |
| 13–63 | — | Not used |