| 9 | Vin High | Service | No | 2.0.1 | PV voltage above the rating, often on cold mornings. | Check the string open-circuit voltage design. | −1152 |
| 10 | High PV Current | Service | No | 2.0.1 | PV current too high. | As bit 17. | – |
| 11 | Over Temp | Auto | No | 2.0.1 | Heatsink too hot after the unit reduced its output. | Check ventilation, fans and ambient temperature. | −1100 |
| 12 | Low Battery Temp | Auto | No | 2.0.1 | Battery cold. | Reduce charge current per the battery spec. Adhere to the BMS CCL/CVL limits. | – |
| 13 | Earth Fault Positive | Service | No | 2.0.1 | Low insulation on the positive side. | As bit 20. | −1401 |
| 14 | Earth Fault Negative | Service | No | 2.0.1 | Low insulation on the negative side. | As bit 20. | −1403 |
| 15 | Active Cooling Fault | Service | No | 2.0.1 | Fan fault. | Check and clear the fans. Watch heatsink temperature (msg 4). | −1050 to −1054 |
| 16 | Iout High | Auto | No | 2.0.1 | Output current spike, typically sun bursting through cloud on a large array. From 2.19.5 it reports on bit 24. | None for occasional trips. If it trips in steady sun, ensure the array is within specifications. | −1157 |
| 17 | Iin High | Service | No | 2.0.1 | PV current above the rating. | Ensure the array is within specifications. | −1156 |
| 18 | Cross Check Fault | Service | No | 2.0.1 | Internal self-check failed; the unit restarts. | Contact AERL if it repeats. | −400 |
| 19 | Temp Sensor Timeout | Service | No | 2.0.1 | Temperature sensor or temperature feed lost. | Check the sensor. If you send Remote Temperature (msg 31), make sure it is still being sent. | −350, −1055, −1161 |
| 20 | Earth Fault | Service | No | 2.0.1 | Low insulation resistance between the PV/battery circuit and earth. | Latch a critical alarm. Notify per AS/NZS 5033, isolate the affected array, and test insulation before recommissioning. The SRX may keep charging. From 2.6.6 the flag clears after about 30 min, possibly before the fault is fixed; from 2.19.6 it holds until the unit resets. | −1400 to −1403 |
| 21 | No Output | Service | No | 2.0.1 | Converting but no current reaching the battery: breaker, contactor or wiring open. | Check the output breaker and BMS contactor. If unresolved, contact AERL service. | −360 |
| 22 | Low Bat Temp Cut-off | Auto | No | 2.0.1 | Battery below the configured charge cut-off temperature. | If you supply battery temperature, keep sending msg 31. Heater if fitted. | −1103 |
| 23 | High Bat Temp Cut-off | Auto | No | 2.0.1 | Battery above the charge cut-off temperature. | Check battery cooling. Keep sending msg 31. | −1102 |
| 24 | Current Flow Disrupted | Auto | No | 2.0.1 | Sudden current change: breaker or contactor opened under load, or a burst of sun through cloud. | None for occasional trips. Treat as Service only if it trips very often, day after day. Don’t open the contactor while charging. | −1157, −1162, −1163 (2.19.5) |