title: "CoolMax SRX – CAN Integration Guide"
revision: "1.0.3"
publisher: AERL (Australian Energy Research Laboratories)
url: https://www.aerl.com.au/docs/coolmax-srx-can-integration-guide
pdf: https://www.aerl.com.au/documents/guides/AERL_CoolMax_SRX_CAN_Integration_Guide_REV_103.pdf
description: "How an energy management system should respond to each CoolMax SRX and SRX-R fault and status flag reported over CAN bus, with the minimum firmware for each."
---

# CoolMax SRX – CAN Integration Guide

*Rev 1.0.3. Markdown copy of the AERL document at https://www.aerl.com.au/docs/coolmax-srx-can-integration-guide; the PDF (https://www.aerl.com.au/documents/guides/AERL_CoolMax_SRX_CAN_Integration_Guide_REV_103.pdf) is the controlled version.*

CAN Master & Site Controller Integration

# CoolMax SRX

CAN Bus Integration Guide

**Doc · SRX-CAN-GUIDE**

Active Flags msg 5 · bytes 4–7

Inhibit Reason msg 5 · byte 3

Output off Status 4 or 6

Power Target period 1 to 5 s

Fastest target rate every 250 ms

Target timeout about 32 s

Self-clear hold-off 10 s to 30 min

Halt charging, bit 27

| | |
|---|---|
| Document | SRX-CAN-GUIDE |
| Revision | 1.0.3 |
| Effective | 11 / 2026 |
| Product | CoolMax SRX / SRX-R |
| Audience | Integrators |
| Firmware | 2.0.1 and later |
| Format | A4 · 6 pages |

> Halt all system charging
>
> On **bit 27** (PWM Regulation Failure), stop every charge source on site, not just the SRX, until the fault is resolved or the affected unit is physically isolated. Bit 27 is Critical: latch an alarm on the first occurrence. See chapter 03.
>
> **Firmware before 2.19.5 logs −390 but raises no flag bit: rely on the current cross-check (rule 7).**

> Firmware
>
> Applies to CoolMax SRX and SRX-R firmware 2.0.1 and later. Min FW (chapter 03) is the first firmware with each flag. Firmware 2.6.6 to 2.8.4 has been withdrawn; update units on it to 2.17.9.

## Chapter 01 Reading the SRX

| What | Where | Notes |
|---|---|---|
| Active Flags | msg 5, bytes 4 to 7 (big-endian) | Bit 0 is the least significant bit of byte 7. More than one bit can be set. |
| Inhibit Reason | msg 5, byte 3 | From 2.19.5. Ignore bytes 0 to 2 always, and byte 3 on earlier firmware (bytes 0 to 3 are undefined there). |
| Device Status | msg 0, bytes 4 to 7 | Status 4 or 6 means the output is off. |
| Event code | AERL Link | Not broadcast on CAN. Use it to confirm the exact cause on site. |

> Important
>
> **Use the flags to detect faults, not the status.** Some stops leave the flags at 0 (chapter 04).

## Chapter 02 General Rules

1. **Most faults will clear themselves.** The SRX will restart once the condition has cleared, after a hold-off of 10 s to 30 min. The EMS should keep sending Power Targets throughout.
2. **Commands reach every unit on the bus.** Enable, Reset, Shutdown, Power Target and Remote Temperature must be sent to every SRX unit. **Reset restarts every SRX on the bus**; do not use this command to try to reset an individual unit. Reset needs 2.4.2 or later: update units on 2.0.1 to 2.0.3.
3. **The system controller shall latch all safety alarms.** An SRX flag can clear before the fault has been fixed, so ensure all safety alarms are captured and actioned by the controller.
4. **Repeated faults on a single unit.** A unit that records multiple faults should be investigated on site, even if the faults have cleared.
5. **Send Power Targets every 1 to 5 s** (never faster than every 250 ms). After about 32 s without a Power Target, the SRX will stop following the target and return to default behaviour.
6. **To slow or stop charging, lower the current limit.** Keep the voltage target at or above the battery voltage.
7. **Cross-check the total charge current. This is mandatory.** The master controls every charge source on site (SRX units, AC-coupled inverters, genset chargers), so it knows the total charge current it has requested. Alarm if the battery current measured by the BMS or shunt stays above the request, beyond your measurement tolerance, for more than a few seconds: requesting 100 A but seeing 140 A means a source isn’t following its target or something is charging unregulated. Compare the summed SRX output current with the current requested from the SRX units to find the source. If current flows while the units report output off, or above the request, treat it as bit 27 and halt charging. **Firmware before 2.19.5 logs −390 but raises no flag bit: there, this cross-check is the only detection.**

## Chapter 03 What to Do for Each Flag

| Class | Meaning |
|---|---|
| Info | Normal operation. Log only. |
| Auto | Clears by itself. Alarm only if it repeats frequently. |
| Config | Usually caused by your settings or targets. Fix these first. |
| Service | Repeats point to a unit or wiring fault. Raise a service alarm after about 3 in an hour. |
| Critical | Latch an alarm on the first occurrence. The system should be inspected before re-initialisation. |

**Halt Charging:** **Yes** means stop all system charging (every charge source, not just the SRX) until the fault is resolved or the affected unit is physically isolated. **Min FW:** the first firmware with the flag (cover, Firmware).

| Bit | Flag | Class | Halt charging | Min FW | Typical cause | What to do | Event codes |
|---|---|---|---|---|---|---|---|
| 0 | Hardware Fault | Service | No | 2.0.1 | Internal AERL hardware fault, or a battery BMS alarm. | Contact AERL. For a BMS alarm, clear it at the battery. | −1 to −99, −150, −1305 |
| 1 | No Config Data | Config | No | 2.0.1 | Unit not commissioned. | Commission with AERL Link. | −26 |
| 2 | Config Data Out of Range | Config | No | 2.0.1 | Charge profile doesn’t suit the battery, or (from 2.19.5) your targets are outside the battery’s limits. | Check the SRX profile against the battery spec, and your targets against the BMS limits. Other units may also turn off: send Enable once it’s fixed. | −1160, −1306 (2.19.5) |
| 3 | Battery Sense Lost | Service | No | 2.0.1 | Battery Sense wiring or feed lost. | Check the battery sense connection. | – |
| 4 | CAN Master Lost | Config | No | 2.0.1 | No valid Power Target for about 32 s. | Check your controller and the CAN bus. Don’t rely on this flag; detect loss of your own targets. | −1301 |
| 5 | Internal Over Temp | Auto | No | 2.0.1 | Unit too hot. | As bit 11. | – |
| 6 | Vin Low | Info | No | 2.0.1 | Not enough PV: dawn, dusk, heavy cloud. | None. If it repeats and latches during full sun, it may be a symptom requiring service: contact AERL. | −1153, −1158 |
| 7 | Vout Low | Service | No | 2.0.1 | No battery: breaker or contactor open. | Check the battery breaker and BMS contactor. | −1159 |
| 8 | Vout High | Config | No | 2.0.1 | Battery above the voltage target, usually because the target was set below the battery voltage, or another charger pushed it up. | **Don’t lower the voltage target.** Raise it to at least the battery voltage and throttle with the current limit. If no target change explains it, check the controller calibration. | −1154, −1155 |

| Bit | Flag | Class | Halt charging | Min FW | Typical cause | What to do | Event codes |
|---|---|---|---|---|---|---|---|
| 9 | Vin High | Service | No | 2.0.1 | PV voltage above the rating, often on cold mornings. | Check the string open-circuit voltage design. | −1152 |
| 10 | High PV Current | Service | No | 2.0.1 | PV current too high. | As bit 17. | – |
| 11 | Over Temp | Auto | No | 2.0.1 | Heatsink too hot after the unit reduced its output. | Check ventilation, fans and ambient temperature. | −1100 |
| 12 | Low Battery Temp | Auto | No | 2.0.1 | Battery cold. | Reduce charge current per the battery spec. Adhere to the BMS CCL/CVL limits. | – |
| 13 | Earth Fault Positive | Service | No | 2.0.1 | Low insulation on the positive side. | As bit 20. | −1401 |
| 14 | Earth Fault Negative | Service | No | 2.0.1 | Low insulation on the negative side. | As bit 20. | −1403 |
| 15 | Active Cooling Fault | Service | No | 2.0.1 | Fan fault. | Check and clear the fans. Watch heatsink temperature (msg 4). | −1050 to −1054 |
| 16 | Iout High | Auto | No | 2.0.1 | Output current spike, typically sun bursting through cloud on a large array. From 2.19.5 it reports on bit 24. | None for occasional trips. If it trips in steady sun, ensure the array is within specifications. | −1157 |
| 17 | Iin High | Service | No | 2.0.1 | PV current above the rating. | Ensure the array is within specifications. | −1156 |
| 18 | Cross Check Fault | Service | No | 2.0.1 | Internal self-check failed; the unit restarts. | Contact AERL if it repeats. | −400 |
| 19 | Temp Sensor Timeout | Service | No | 2.0.1 | Temperature sensor or temperature feed lost. | Check the sensor. If you send Remote Temperature (msg 31), make sure it is still being sent. | −350, −1055, −1161 |
| 20 | Earth Fault | Service | No | 2.0.1 | Low insulation resistance between the PV/battery circuit and earth. | Latch a critical alarm. Notify per AS/NZS 5033, isolate the affected array, and test insulation before recommissioning. The SRX may keep charging. From 2.6.6 the flag clears after about 30 min, possibly before the fault is fixed; from 2.19.6 it holds until the unit resets. | −1400 to −1403 |
| 21 | No Output | Service | No | 2.0.1 | Converting but no current reaching the battery: breaker, contactor or wiring open. | Check the output breaker and BMS contactor. If unresolved, contact AERL service. | −360 |
| 22 | Low Bat Temp Cut-off | Auto | No | 2.0.1 | Battery below the configured charge cut-off temperature. | If you supply battery temperature, keep sending msg 31. Heater if fitted. | −1103 |
| 23 | High Bat Temp Cut-off | Auto | No | 2.0.1 | Battery above the charge cut-off temperature. | Check battery cooling. Keep sending msg 31. | −1102 |
| 24 | Current Flow Disrupted | Auto | No | 2.0.1 | Sudden current change: breaker or contactor opened under load, or a burst of sun through cloud. | None for occasional trips. Treat as Service only if it trips very often, day after day. Don’t open the contactor while charging. | −1157, −1162, −1163 (2.19.5) |

| Bit | Flag | Class | Halt charging | Min FW | Typical cause | What to do | Event codes |
|---|---|---|---|---|---|---|---|
| 25 | Pre-charge Failure | Service | No | 2.0.1 | PV pre-charge didn’t complete during start-up. | None for brief, intermittent trips in low irradiance: this is normal. If it latches on, service is required: contact AERL. | −365 |
| 26 | PV Pre-charge Failure | Service | No | 2.8.4 R 2.9.4 | As bit 25. Min FW is 2.8.4 on the SRX-R, 2.9.4 on the SRX. | As bit 25. | −380 |
| 27 | PWM Regulation Failure | Critical | Yes | 2.19.5 | Current flowing while the output should be off: possible power-stage failure. The unit may lock out for the rest of the day. **Firmware before 2.19.5 logs −390 but raises no flag bit: rely on the current cross-check (rule 7).** | Stop all system charging until service can attend or the controller is physically isolated. Don’t keep resetting. Contact AERL. | −390 |
| 28 | PWM Corruption | Service | No | 2.19.5 | Internal integrity check. | If it recurs, contact AERL with the firmware version (msg 11). | −367, −372 |
| 29 | Stack Overflow | Service | No | 2.19.5 | Internal integrity check. | As bit 28. | −368 |
| 30 | Clock Failure | Service | No | 2.19.5 | Internal integrity check. | As bit 28. | −369 |
| 31 | Brownout | Service | No | 2.19.5 | Unit’s internal supply dipped. | As bit 28. | −371 |

## Chapter 04 Stops with No Flag

If the flags read 0 and the status shows the output is off with no output current, follow these checks:

| Check | Cause | What to do |
|---|---|---|
| 1 | Your Power Targets stopped or arrived late. | Review the EMS for correct function. The units should resume when the next target is received. |
| 2 | A Shutdown was sent, or another unit’s fault turned the bus off. | Send Enable. If units don’t resume, send Reset. |
| 3 | The battery BMS is alarming (where the SRX listens to the BMS; from 2.4.2). | Clear the BMS alarm, then send Reset if units don’t resume. |
| 4 | Inhibit Reason 3: a unit on the bus runs firmware earlier than 2.19.6, so units on 2.19.6 or later hold off. | Put every unit on the bus on the same firmware: contact AERL. |
| 5 | Routine self-restart. | Normal. Ignore a single short dropout. |
| 6 | None of the above. | Contact AERL with the unit’s event log. |

## Chapter 05 Controller Checklist

- Send Power Targets every 1 to 5 s.
- Throttle with the current limit, not the voltage target.
- Alarm when a unit’s broadcasts stop (no msg 0 for more than 5 s).
- Latch earth fault (bits 13, 14, 20) and bit 27 alarms.
- Halt all system charging on bit 27.
- Count repeats per serial for Service flags.
- If you supply battery temperature, send msg 31 regularly.
- **Mandatory:** alarm on output current while the unit reports output off, and treat it as bit 27. Firmware before 2.19.5 never raises bit 27 (it logs −390 only).
- **Mandatory:** alarm when measured battery current exceeds the total current requested from all charge sources (rule 7).
- Use Reset only when restarting every unit on the bus is acceptable.

## Chapter 06 Revision History

| Rev. | Date | Change |
|---|---|---|
| 1.0.0 | 21/10/26 | First release |
| 1.0.1 | 08/11/26 | Target timeout 34 s (as the CAN protocol); inhibit reason from 2.19.2; version-gate stop (check 4); bits 4, 10 and 20 per firmware 2.19.6. |
| 1.0.2 | 09/11/26 | Items that need firmware later than 2.17.9 marked. |
| 1.0.3 | 16/11/26 | Minimum firmware for every flag, from 2.0.1; bit 27 added in 2.19.5 (rely on the current cross-check, now mandatory); event codes from later firmware marked; target timeout about 32 s. |