SRX‑R

SRX‑R 600/60‑48 · 3456 W Charge Power

AERL CoolMax SRX-R charge module
600VdcMax PV input
60AMax charge current
3456WNominal @ 48 V
96%Peak efficiency
aerl.com.au 2U-Rack MPPT Module · 48 V Datasheet · Rev 2.0.2 · 2026

Specifications

SRX-R 600/60-48

The CoolMax SRX-R is a Maximum Power Point Tracker (MPPT) and battery charger built on over thirty years of AERL MPPT and charging experience. High conversion efficiency, intelligent thermal management and accurate tracking make it a key component of a high-quality DC-coupled power system.

General

Weight
6.2 kg
Dimensions (W × H × D)
192 × 78 × 432 mm
Enclosure
Indoor Type 1 / IP20
Mounting
2U Rack
I/O power connectors
Backplane Connector
Communications
RS485 / CAN / USB
Cooling method
Active (serviceable)
Cabinet air exchange (40 °C)
25 m³/hour
Max conversion efficiency
96%
MPPT tracking loss
< 0.5%
Self-consumption @ idle
3.5 W
Warranty
2 yr · 5 yr registered · 10 yr (Plus 5)

Battery (output)

Nominal battery voltage
24 V / 48 V
Battery voltage range
18–30 Vdc (24 V)
40–60 Vdc (48 V)
Max charge current
60 A
Nominal charge power @ 24 V
1728 W
Nominal charge power @ 48 V
3456 W
Charging method
3-stage CCCV
Temp. compensation
50 mV/°C (default)

PV input

Max PV input power
Nom × 2.0
Max PV input voltage (Voc)
600 V
Nominal device voltage
336 V
MPP voltage range (Vmp)
170–540 V
Min PV voltage (MPPT)
100 V
Max PV input current (Imp)
18 A
Max PV short-circuit (Isc)
25 A
Startup voltage
60 V and ≥ Vbat + 10 V
Total backfeed (Ibf Total)
0 A

Safety & environment

Overload behaviour
Power limitation
PV reverse-polarity protection
Yes
Pre-charge protection
Yes
Earth-leakage detection
Yes
Overvoltage category
DC II
Overvoltage protection
DC Type II
Safety protection class
I
Pollution degree (int. & ext.)
II
Max altitude
2000 m
Operating temperature
−20 to 50 °C
Storage temperature
−30 to 70 °C
Relative humidity
4–95% NC

2U rack format for easier installation & servicing

Scalable for large storage applications

Remote module control & monitoring

Designed for long‑term reliability

PV array oversizing up to 200%

Reverse polarity & current protection

Built-in overload & thermal protection

On-board ground fault detection

Engineered and supplied by

Australian Energy Research Laboratories
1/75 Bluestone Circuit, Seventeen Mile Rocks QLD 4073

Designed to meet

IEC 62109-1 (safety)EN 61000-6-3 (EMC)EN 61000-6-4 (EMC)

Contact

1800 950 865
[email protected]
aerl.com.au