AERL technical documentation

CoolMax SRX-R 48 V — User Manual Rev 2.0.4

30 pages

Download PDF Print
Download PDF· Rev 2.0.4 CoolMax User Manual

SRX-R

MPPT Solar Charge Controller

AERL CoolMax SRX-R charge controller module
SRX-R 600/60-48 Installation & OperationAER09 Rev 2.0.4, 9 Nov 2026
aerl.com.au SRX-R 600/60-48 · Indoor Type 1 / IP20

Contents

Document

DocumentAER09
Revision2.0.4
Effective11 / 2026
Firmwarev2.17.9+
ModelSRX-R 600/60-48
FormatA4 · 30 pages
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
01

About AERLCompany, contact, copyright

Australian Energy Research Laboratories (AERL) was founded in 1985 by Stuart Watkinson to commercialise the Power Optimizer, which he developed while studying at the University of Queensland. It became the AERL MAXIMIZER™, a universal maximum power point tracker (MPPT).

Today AERL designs, integrates and supports power conversion, lithium energy storage, monitoring and earth-fault detection products for commercial, industrial and off-grid energy systems, including oil and gas, mining and telecommunications sites.

Contact Information

Address

Australian Energy Research Laboratories

1/75 Bluestone Circuit
Seventeen Mile Rocks QLD 4073
Australia

Phone & web

Phone: 1800 950 865

Email: [email protected]

Web: aerl.com.au

Disclaimer

Unless specifically agreed to in writing, AERL Pty Ltd:

(a) Makes no warranty as to the accuracy, sufficiency or suitability of any technical or other information provided in its manuals or other documentation.

(b) Assumes no responsibility or liability for loss or damage, whether direct, indirect, consequential, or incidental, which might arise out of the use of such information.

The use of any such information will be entirely at the user’s risk.

Trademark & Copyright

AERL and the AERL logo are trademarks owned by AERL Holdings Pty Ltd and used by AERL Pty Ltd under licence. These trademarks may be registered in Australia and other countries.

CoolMax SRX-R Charge Controller User Manual © 2026 AERL Pty Ltd. All rights reserved. Effective November 2026.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
02

Safety & WarrantySymbols, manual scope, warranty terms

This installation manual contains important safety information and installation instructions for the AERL CoolMax SRX-R MPPT Solar Charge Controller. The following symbols indicate ideal installation methods, potentially dangerous conditions, and important operational information.

Important

Information that must be followed to ensure proper installation or operation of the CoolMax SRX-R.

Caution

Indicates a critical procedure for the safe installation or operation of the CoolMax SRX-R.

About This Manual

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Warranty

WarrantyDuration
Standard warranty2 years
Registered within 60 days of installation at aerl.com.au/warranty-registration (or connected to AERL Cloud within 60 days)5 years
Plus 5, bought from AERL within 60 days of installation10 years
SRX-R rack shelf2 years

The warranty starts 30 days after AERL dispatches the controller, whether to you, your installer or the business you bought it from. If the controller connects to AERL Cloud before then, the warranty starts on the day it first connects instead.

Our goods come with guarantees that cannot be excluded under the Australian Consumer Law.

Full terms: AERL warranty statement for CoolMax SRX-R, aerl.com.au.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
03

SpecificationsGeneral, characteristics, standards

General
Weight6.2 kg
Dimensions (W × H × D)192 × 78 × 432 mm
Enclosure typeIndoor Type 1 / IP20
Mounting method2U Rack
Power connectorsBackplane Connector
CommunicationsRS485 / CAN Bus / USB
Cooling methodActive (user serviceable)
Cabinet air exchange (40 °C intake)25 m³/hour
Environment
Ambient operating temperature*−20 to 50 °C
Storage temperature−30 to 70 °C
Relative humidity4–95% non-condensing
Max altitude rating2000 m
Pollution degree (Int & Ext)II
Self-consumption @ idle3.5 W
Max conversion efficiency96%
Compliance
Overvoltage category / protectionDC II / DC Type II
Safety protection classI
Electrical (SRX-R 600/60-48)
Nominal battery voltage / range24 V / 18–30
48 V / 40–60
Max charge current60 A
Nominal charge power1728 W @ 24 V
3456 W @ 48 V
Max PV input powerNominal × 2.0
Max PV input voltage (Voc)600 V
Nominal device voltage336 V
MPP voltage range (Vmp)170–540 V
Min PV voltage (MPPT)100 V
Max PV input current (Imp)18 A
Max PV short circuit current (Isc)25 A
Device startup voltage60 V (and ≥ Vbat + 10 V)
Total backfeed current (Ibf)0 A
Protection
Overload behaviourPower limitation
PV reverse polarity protectionYes
Reverse current protectionYes
Over-temperature protection / deratingYes
Over-voltage / over-current protectionYes
Pre-charge protectionYes
Earth leakage current detectionYes

Designed to meet: IEC 62109-1:2010 (safety) · EN 61000-6-3 & EN 61000-6-4 (EMC). *Charge current derates up to 10% per °C above 80% of the upper ambient limit.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
04

IntroductionFeatures, firmware coverage

Thank you for purchasing an Australian engineered CoolMax SRX-R Series Charge Controller.

CoolMax Charge Controllers deliver an efficient, reliable charging process that maintains battery life while maximising generation from your PV array.

AERL CoolMax SRX-R charge controller module, front three-quarter view
CoolMax SRX-R — front three-quarter view

Features

CoolMax Charge Controllers use advanced Maximum Power Point Tracking (MPPT) to extract the maximum power available from your PV array.

AERL’s MPPT algorithm does not lock onto local power peaks, and its tracking losses stay under 0.5% across the array’s full operating temperature range.

Firmware

This user manual covers CoolMax SRX-R Control Firmware Revisions v2.17.9 and later.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
05

Safe Handling & TransportHandling, transport, storage, pre-install

Handling Precautions

Transport Guidelines

Storage Requirements

Pre-installation Inspection

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
06

InstallationStandards, mounting, wiring, backplane

Standards & Requirements

All installations must comply with national and local electrical standards and codes; AERL recommends professional installation. No ongoing maintenance is required.

Local standards & certified installation

Installation must comply with the electrical standards, codes, and wiring rules at the site; only an installer accredited or licensed in your jurisdiction should perform the work. Install in a clean, dry location away from direct sunlight. Standards cited elsewhere reflect design intent at publication; refer to current local standards.

Hazard (solar isolator)

Ensure the SOLAR ISOLATOR / BREAKER is in the OFF position before connecting or disconnecting the controller. Do not connect CoolMax controllers in parallel with third-party charge controllers.

Grounding

CoolMax controllers are designed for floating systems but include provisions for positive functional earthing for telecom applications if required. The chassis ground is marked with the standard earth symbol.

Do not functionally earth the array

If a negative earth is used for the batteries, load, or DC system, do not functionally earth the array. If damaged, the controller should only be repaired by a qualified service centre; incorrect reassembly risks electric shock or fire.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Mounting the Shelf

The SRX-R shelf must be mounted horizontally in a suitably ventilated lockable IP5X cabinet, ensuring the backplane area is restricted to licensed electricians and qualified technicians. A representative rack-cabinet installation populated with multiple SRX-R shelves is shown in Figure 1A.

SRX-R rack cabinet populated with multiple 2U SRX-R shelves
Figure 1A · SRX-R rack cabinet installation
Front elevation of the 2U shelf showing two SRX-R modules installed side-by-side in their bays
Figure 1B · SRX-R modules in shelf

Wire and Disconnect Sizing

Wiring requirements

Wire sizes must comply with local and national standards. Input conductors and circuit breakers must be rated at 1.56 × the short-circuit current of the PV array. Copper wiring must be rated at 75 °C or higher.

Use a minimum of 1/0 AWG (50 mm²) multistrand cable for the output between the backplane and the battery bus bar or termination. Confirm the conductor’s current-carrying capacity is appropriate for the chosen load circuit breaker, and use an appropriately sized insulated crimp ferrule when terminating both input and output connections.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
Earthing conductor sizing

Size the protective earth conductor between the SRX-R shelf and the installation’s main earthing system per AS/NZS 5033 Figure 4.13 (earthing-conductor sizing decision tree) or the equivalent installation standard in your jurisdiction. #12 AWG (4 mm²) is the minimum cross-section acceptable at the SRX-R earth stud — it is not a default. Many installations require larger: for example, arrays exposed to lightning-protection requirements (LPS) or installations without DC overcurrent protection typically require 16 mm², or the earth conductor sized to the array cable, whichever is greater. The installer is responsible for the final selection.

Backplane terminations on the shelf use studded connections. Apply the torque values below, using the provided nut and spring washer for each terminal:

TerminalStudCurrent ratingTorque
Battery (+ / −)M10350 A17 Nm
PV+, PV−, EarthM5180 A2.2 Nm

Example setup — two MPPTs in a single 2U shelf

For the example scenario of two SRX-R MPPT modules installed in a single 2U shelf as the only charge controllers on the battery bus, the breaker and configuration below are the recommended setup for that scenario. For other scenarios (multi-shelf installations, mixed-controller systems, etc.) contact AERL for guidance on multi-shelf or mixed-controller systems.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Backplane Terminations

Hazard (polarity)

Reversing the polarity of either the input or output may damage the CoolMax SRX-R and void product warranty. Confirm polarity with a multimeter prior to closing the input and output circuit breakers.

Hazard (cable entry)

All SRX-R wiring must enter through the designated backplane entry points. Under no circumstances should holes be drilled into the chassis to make other cable entry points; metal swarf can enter the internal electronics and damage the unit once powered up.

Annotated SRX-R backplane showing earth stud, Battery Terminal, PV Terminal (1) and (2), LINK and CANBUS RJ45 sockets, USB-B Port, USB Change-Over switch, and MODBUS connector
Figure 2 · SRX-R backplane

The backplane exposes the following user controls:

Shared switches

The CAN and Modbus buses are shared internally between both module slots, so each switch above is a single shared control that applies to both modules in the shelf. The USB Change-Over switch is the only per-module selector.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
07

Operation & StatusStart-up, programming, LED states

Start-Up & Shutdown Procedure

The CoolMax SRX-R starts up once the PV input is above 60 Vdc and at least 10 Vdc higher than the connected battery voltage; the device will not power up from the battery terminal. To start: connect the battery first, then turn the PV isolator / breaker on; the LED flashes blue for about 60 seconds, then begins to charge. To shut down: turn the PV isolator off, wait for the LED to turn off, and disconnect the battery breaker.

Equipment damage (shutdown order)

Do not disconnect the battery fuse / breaker under load. Turn off the PV isolator first per the procedure above.

Do not hot-swap modules

Do not remove an SRX-R MPPT module from the backplane while charging — turn off the PV isolator first to prevent equipment damage.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Programming the Device

When the CoolMax SRX-R is first powered on, the device runs a self-test and the LED indication strip flashes orange to indicate that no charge profile has been configured.

The CoolMax SRX-R is programmed via the USB-B port on the backplane board (Figure 3). Set the USB Change-Over Switch to the module you intend to program (MPPT 1 / MPPT 2) — only one module communicates over USB at a time. The AERL Link software for Windows 10/11 can be downloaded from aerl.com.au/professionals.

Close-up of the SRX-R backplane board highlighting the USB-B socket and the adjacent MPPT 1 / MPPT 2 toggle selector switch
Figure 3 · USB-B programming port & toggle switch

Device Status Indicator

Flashing
Solid
Meaning (flash)
Meaning (solid)
Green
Remotely controlled & OK
OK
Blue
Starting up
Sleeping
Orange
N/A
Setup required / FW update in progress
—
Red
System fault
Hardware fault
Figure 4 · LED indication states
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
08

Battery Charge ProfileThree-stage profile, AERL Link, presets, safeguards

The CoolMax SRX-R uses an advanced three-stage charging process with pre-set voltage profiles for each supported nominal battery voltage. The controller does not charge until a charge profile is configured for the connected battery.

Default profile

The CoolMax SRX-R default charge profile is intended for a generic LiFePO4 battery solution. AERL supports most other chemistries that do not require external BMS communications; always refer to the battery manufacturer’s specifications.

Three-stage battery charge profile: bulk, absorb, float with re-bulk transition
Figure 5 · Battery charge profile illustrated

The programmable profile exposes Battery Charge Rate, Tail Current (end-of-absorption threshold), and the Absorb, Float, Re-Bulk, and Equalisation voltage points. Refer to your battery manufacturer’s specifications for the optimal profile; configuration with AERL Link is covered on the next page.

Equalisation

Equalisation is only required for flooded lead-acid cells with sulfation. It is not recommended for LiFePO4 or other lithium-based solutions and will likely cause damage unless advised by the battery manufacturer.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Live Status with AERL Link

Once the SRX-R is connected over USB, AERL Link opens to the device’s Status tab, the default view for any selected device, providing a live, read-only view of operating values:

AERL Link Status tab layout: power gauge, PV voltage and current, battery voltage and current, device status and firmware version (live values not shown) for the connected SRX-R
Figure 6 · AERL Link: Live Status (layout; live values not shown)

Setting the Profile with AERL Link

Connect over USB with the USB Change-Over Switch set to the module you wish to program. Within a few seconds the controller registers in AERL Link’s LOCAL devices list. Figure 7 shows the device tile that appears; click its tile to open the device page, then select the OUTPUT tab to adjust the charge profile (Figure 8).

AERL Link Devices page showing a connected SRX-R 600/60-48 tile under LOCAL devices
Figure 7 · AERL Link: Devices list
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Click the device tile to open its page. On the OUTPUT tab, change values with the +/− arrows or the keyboard, then Apply to commit them to the controller.

AERL Link Battery settings panel showing Battery voltage, Max charge current, Charger enabled toggle, and Charge voltages with Export / Import / Apply controls
Figure 8 · AERL Link: Battery Settings panel

Battery Profile Presets & Saving

The Battery Preset dropdown on the OUTPUT tab lists pre-tuned profiles for common battery products. Selecting a preset populates the absorption, float, and re-bulk voltages, the absorption time, and the temperature-compensation factor with AERL’s recommended values; presets refresh from AERL HQ on each AERL Link launch with an internet connection. Export saves the current profile to a JSON file and Import applies a saved profile; AERL Link verifies the saved profile’s nominal voltage matches the connected device, and warns before applying a mismatch.

Presets are a starting point

Always cross-check the applied values against your battery manufacturer’s published charge specification before relying on them in a production system.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Blackstart Guard

The CoolMax SRX-R includes a configurable Blackstart Guard that lets the converter begin charging into a battery bank whose voltage is below the controller’s normal “no battery detected” safety threshold (for example, a deeply discharged lithium bank that has been left flat for an extended period and now reads well below its nominal range).

Blackstart Guard is disabled by default. With it disabled, the controller performs its standard start-up safety check: if the output voltage is implausibly low, it refuses to enable and reports a Low Output Voltage / No Battery fault. Enabling Blackstart Guard from the Settings panel in AERL Link bypasses that check, allowing the controller to start charging the depleted bank from a black state.

Disable Blackstart Guard once the bank has recovered

Leaving Blackstart Guard permanently enabled defeats a key safety check; the controller will no longer refuse to operate into a disconnected or faulty battery.

Battery Temperature Compensation

Temperature compensation measures the temperature of the batteries and adjusts the float and absorb voltage set points by a user-specified factor (mV/°C, per bank). The factory default is 50 mV/°C. Compensation needs a battery temperature reading (see below); without one, the controller charges to the uncompensated set points.

Temperature source

Battery temperature compensation needs a battery temperature reading. The current firmware release does not use a temperature reported by the battery’s BMS over CAN; contact AERL support before relying on temperature compensation.

Low-Temperature Charge Cutoff

Many lithium chemistries are damaged by charging below freezing. The SRX-R can be configured to inhibit charging when the remote battery temperature falls below a user-specified threshold. When the Low-Temperature Charge Cutoff is enabled in AERL Link, the controller suspends charging when battery temperature falls below the configured set point and resumes once it rises back above. Both the cutoff temperature and the enable toggle are configured from the Settings panel; the cutoff is disabled by default.

Requires a battery temperature reading

The cutoff only operates when a battery temperature reading is available to the controller; contact AERL support before relying on it. Without a temperature source, the controller cannot enforce the cutoff and charging will proceed regardless of battery temperature.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
09

Firmware UpdatesField updates over USB via AERL Link

The CoolMax SRX-R supports field firmware updates over USB via AERL Link. Updates are signed and encrypted; the bootloader will reject a corrupted or unauthorised image.

Before you begin: install the latest AERL Link from aerl.com.au/professionals, ensure the unit is connected to a battery and powered up, and use a stable PC. Do not disconnect USB, kill power, or open the PV / battery isolators during the update.

  1. Toggle the MPPT 1 / MPPT 2 selector switch to the module you intend to update — only one module communicates at a time. Connect a USB cable from the PC to the USB-B port on the backplane (Figure 3).
  2. Launch AERL Link. The connected charger appears on the Devices page. Click it to open. AERL Link checks the controller’s hardware revision and serial against its repository; if a newer image is available, an Update prompt appears.
  3. Click Update (standard updates) or wait (critical updates start automatically and cannot be deferred). If calibration is required as part of the update, AERL Link will warn you and recommend that a digital multimeter is on hand. A progress bar shows upload percentage; the transfer typically takes 1–2 minutes.
  4. When upload finishes, the controller reboots. The LED briefly flashes blue, then returns to normal operation.
  5. If both modules in the shelf require an update, flip the toggle switch to the other module and repeat.
AERL Link firmware update dialog showing progress on a connected SRX-R
Figure 9 · AERL Link: Firmware Update
Note & recovery

AERL Link refreshes its firmware repository from AERL HQ each time it starts; allow the PC to reach the internet briefly before connecting if it has been offline for a while. If an update fails partway through (e.g. the cable was disconnected or the toggle switch was flipped mid-transfer), retry. The bootloader retains the previous valid image and the controller will continue operating normally until a complete, signed update is received.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
10

Output Voltage CalibrationField re-calibration with AERL Link

Each CoolMax SRX-R is factory calibrated, but field re-calibration can correct for sensor drift or be requested as part of a firmware update. AERL Link guides you through the procedure step by step.

Before you begin: have a multimeter that reads DC to ≥ 0.1 V resolution, a connected battery with output voltage in the normal operating range, a stable DC bus (isolate other charge sources, inverters, and large loads on the same battery), and the MPPT 1 / MPPT 2 toggle switch set to the module being calibrated.

  1. Connect the controller over USB and open the Device page in AERL Link.
  2. Click Calibrate. AERL Link checks for a connected battery and a sensible output voltage; resolve any prompts first.
  3. On the Start Calibration dialog, click Yes. The controller disables its output and prepares for calibration (a few seconds).
  4. Measure output voltage at the battery terminals with your multimeter and enter the reading. AERL Link only accepts values within ±5% of the device-reported voltage.
  5. Click OK. AERL Link writes the new calibration multiplier; the device resets, re-enables the output, and resumes charging using the corrected voltage scale.
  6. Each module in a shelf is calibrated independently; flip the toggle switch and repeat for the second module.
AERL Link calibration dialog with the measured-voltage entry field
Figure 10 · AERL Link: Output Voltage Calibration
Do not interrupt calibration

Do not disconnect USB, flip the MPPT toggle switch, or interrupt power during calibration. The output is automatically re-enabled at the end of the procedure; allow it to complete cleanly. AERL Link re-prompts for calibration on first connect after install, and after a calibration-required firmware update; you can also re-run it manually at any time.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
11

Ground Fault DetectionChassis earth, modes, sensitivity, AERL Link

The CoolMax SRX-R features onboard PV and battery system ground-fault detection. All connected poles are checked for insulation degradation during start-up. The device chassis must be connected to the same earth as the PV array for ground-fault detection to function; the chassis earth point is the earth stud on the 2U shelf, at the end of the shelf beside the module terminals, marked with the standard earth symbol (Figure 11).

Ground Fault Mode

The system earth-type configuration (Ground Fault Mode) must be adjusted in AERL Link for use with functionally earthed systems; otherwise an earth fault will be detected on the earthed pole. The SRX-R supports four mode configurations:

End view of the SRX-R 2U shelf with a module fitted, showing the earth stud on the shelf with the standard IEC earth symbol indicated alongside
Figure 11 · Chassis earth point
ModeUse case
DisabledGround fault detection is turned off. Not recommended outside of commissioning or test environments.
FloatingDefault for solar-plus-battery systems with no functional earth on the DC side. Both PV and battery poles are monitored against chassis earth.
Positive EarthThe positive PV pole is intentionally bonded to chassis earth, common in some telecommunications applications. Fault detection on the earthed pole is suppressed.
Negative EarthThe negative PV pole is intentionally bonded to chassis earth. Fault detection on the earthed pole is suppressed.

Mis-configuring this setting will either mask a genuine earth fault or trigger a false fault on the intentionally-earthed pole.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Ground Fault Sensitivity

The SRX-R trips a ground fault when the insulation resistance of a monitored pole falls below a fixed 50 kΩ. Check that 50 kΩ meets your local standards. Firmware 2.0.1 (February 2024) and later trips at this fixed threshold. Earlier firmware offered a Low/Mid/High setting; update the firmware with AERL Link to get the fixed threshold. The Ground Fault Mode is set in AERL Link (Figure 12).

AERL Link settings panel showing the Ground Fault Mode selector
Figure 12 · AERL Link: Ground Fault Mode setting
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
12

Communications ProtocolsRS485 / CAN pinouts, topology, AERL Link settings

The CoolMax SRX-R supports CAN bus and Modbus RTU (RS485) for remote monitoring; device control (enable/disable, setpoints, firmware updates) is available via CAN only. RS485 and CAN use separate RJ45 sockets on the backplane, two labelled MODBUS and two labelled CANBUS (Figure 2); their pin-outs are below (Figure 13). The register maps are in the CoolMax SRX Modbus RTU and CAN bus protocol documents, available from AERL.

PinMODBUS port (RS485)CANBUS port
3RS485-A (non-inv.)—
4—CAN High
5—CAN Low
6RS485-B (inv.)GND
8GND—
RJ45 connector with pins 1 to 8 labelled
Figure 13 · Comms connector pin-outs
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Modbus RS485 network topology

On a Modbus RS485 segment, each SRX-R module sits as a slave on a daisy-chained two-wire bus, with the master at one end. Terminate the bus at both ends with 120 Ω: at the master (many masters have a built-in or switchable terminator) and at the far end, by enabling the 120 Ω termination switch on the last module only.

Modbus RS485 network topology showing a master and multiple SRX-R modules daisy-chained on a two-wire bus, with a 120 Ω termination at the far end
Figure 14 · Modbus RS485 topology
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Configuring CAN and Modbus

Bus ID and speed are configured via AERL Link. With the device connected over USB (USB Change-Over switch set to the module being configured), open the Device page, select the COMMS tab, set the fields below (Figure 15), and click Apply Settings. The controller resets briefly when settings are applied. A changed RS485 or CAN bus speed cuts the controller off from any master still using the old speed: update the master to match before you leave the site.

AERL Link Communications settings panel showing Modbus ID, RS485 Speed, CAN ID, and CAN Bus Speed fields with an Apply Settings control
Figure 15 · AERL Link: Communication settings
FieldRangeDefaultNotes
Modbus ID1–9020Unique slave address on the RS485 segment.
RS485 speed9600 / 19200 / 38400 / 57600 / 115200 baud9600 baudMust match every device on the segment, including the master.
CAN ID10–6010Unique address on the CAN segment. Units on a shared bus take a free ID automatically, skipping 24 and 56 (their frames would alias battery identifiers); 62 means not yet assigned.
CAN bus speed125 / 250 / 500 kbps500 kbpsMust match every device on the CAN segment.

Each module in a shelf is configured independently; flip the USB Change-Over switch and repeat for the second module.

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4
13

TroubleshootingWarning & fault codes

If the CoolMax SRX-R detects an issue, a warning or fault code is triggered; refer to the tables below.

Warning codes

CodeLEDWarningDescriptionRecommended action
−1153 · −1158Solid blueLow input voltage (sleep)PV voltage below minimum or below battery voltage; device cannot charge.Confirm PV string configuration is appropriate. May appear at sunrise / sunset.
−1162Flashing blueCurrent flow interruptedCharge current stopped abruptly, for example a breaker opened or a cable was disconnected. Restarts automatically.Check PV and battery breakers, fuses and terminations. If recurring, contact AERL.
−1400Flashing bluePossible earth faultAn earth-leakage reading at start-up was outside limits; the device re-tests before confirming. Charging continues.If it recurs or becomes −1401 · −1403, inspect the wiring insulation.
−26Flashing orangeDevice not configuredInitial setup not completed; device will not begin charging.Connect and configure the device with AERL Link.
−1160Flashing orangeConfiguration out of rangeSet-point configuration outside limits for the detected nominal battery voltage.Confirm the charge profile is appropriate for the battery. Refer to manufacturer recommendations.
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Warning codes (continued)

CodeLEDWarningDescriptionRecommended action
−1301Flashing orangeCAN master lostWas communicating with the CAN master but has not received a setpoint update within the allowed time-out.Confirm the RJ45 connection is secure and the master is still active.
−1303Flashing orangeWaiting for CAN masterCAN-controlled mode, no commands from master yet; charger appears disabled until the master connects.Check CAN master is powered and sending commands. If standalone is intended, disable CAN control in AERL Link.
−1306Flashing orangeCharge held: battery voltage limitReported by some pre-release firmware: the charge voltage set point is above the maximum charge voltage the battery’s BMS requests over CAN. Charging stops and retries automatically.Set the absorption and float voltages at or below the battery’s requested charge voltage.
−1307Flashing orangeCharge held: battery current limitReported by some pre-release firmware.Contact AERL support.
110Flashing orangeFirmware update in progressA firmware update is being installed over CAN; charging is paused.Wait for the update to finish. Do not remove power or the communications cable.
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Fault codes

CodeLEDFaultDescriptionRecommended action
−1 to −99Solid redGeneric hardware faultAny code from −1 to −99 other than −26: a hardware fault found at start-up or during operation.Power cycle. If persistent, contact AERL for warranty replacement.
−150Solid redMeasurement faultThe internal measurement circuit stopped providing fresh readings; the converter is stopped.Power cycle. If persistent, contact AERL.
−350 · −1055 · −1161Solid redTemperature sensor faultInternal or remote temperature sensor missing or unresponsive.Check communications wiring configuration and ensure connected devices are functioning as expected. If persistent, contact AERL.
−365 · −370 · −380 · −390Solid redStartup / precharge faultIssue during startup or precharge prevented safe converter online.Power cycle. Check PV / battery isolators, breakers, wiring. If persistent, contact AERL.
−367 · −368 · −369 · −371 · −372 · −400 · −401Solid redCritical system faultCritical system integrity fault; converter locked out for safety.Power cycle; check comms wiring and power-supply integrity. If persistent, contact AERL.
−1050 · −1051 · −1052 · −1053 · −1054Solid redActive cooling faultAn active cooling fan has failed or is operating outside expected parameters.Check the fan for blockages then power cycle the device. If persistent, contact AERL.
−1100Solid redInternal temperature criticalInternal temperature has reached a critical level; device has shut down to prevent damage.Auto-restart when safe. Ensure adequate clearance and ventilation.
−1163Solid redCurrent sensor faultA current measurement is outside its physical range; the converter is held off.Power cycle. If persistent, contact AERL.
−3601 flash redNo output detectedConverter enabled but no output current is flowing.Power cycle. If recurring, contact AERL.
CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Fault codes (continued)

CodeLEDFaultDescriptionRecommended action
−11592 flashes redLow output / no batteryNo battery detected or output voltage implausibly low.Confirm battery is connected and output breaker is closed.
−11543 flashes redHigh output voltageOutput voltage exceeds the configured maximum.Battery may be getting charged from a secondary source. Confirm charge parameters across the system.
−11553 flashes redHigh battery voltageBattery voltage exceeds maximum permitted for detected nominal voltage.Verify battery nominal voltage matches the configured profile.
−13053 flashes redBattery BMS faultFault / alarm received from the battery’s BMS over CAN (e.g. AERL LiFe² battery).Refer to the battery manufacturer’s manual for BMS troubleshooting.
−11574 flashes redHigh output currentOutput current exceeds the configured maximum.Confirm no short on the output; load within device current limit.
−11525 flashes redHigh PV voltagePV input voltage exceeds rated maximum; device shut down to prevent damage.Confirm string Voc at record-low ambient is within the device’s rating.
−11566 flashes redHigh PV currentPV input current exceeds rated maximum.Confirm string configuration is appropriate for the device.
−11028 flashes redHigh battery temperatureBattery temperature sensor over-temperature; high temperatures reduce battery life.Increase temperature-compensation factor in AERL Link or reduce ambient.
−11039 flashes redLow battery temperatureBattery temperature sensor under-temperature; low temperatures reduce battery life.Consider a temperature-controlled battery environment.
−1401 · −1402 · −140310 flashes redEarth fault detectedEarth fault detected on the input or output.Isolate the controller, confirm the fault with an insulation resistance tester, and repair it before recommissioning.

If your situation is not covered here, contact AERL on 1800 950 865 or [email protected].

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Notes

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Notes

CoolMax SRX-R 600/60-48 User ManualAER09 Rev 2.0.4

Australian Energy Research Laboratories

Address

1/75 Bluestone Circuit
Seventeen Mile Rocks QLD 4073
Australia

Contact

[email protected]
[email protected]

aerl.com.au Phone1800 950 865