title: "CoolMax SRX – Modbus RTU Protocol"
revision: "2.0.5"
publisher: AERL (Australian Energy Research Laboratories)
url: https://www.aerl.com.au/docs/coolmax-srx-rs485-protocol
pdf: https://www.aerl.com.au/documents/protocols/AERL_CoolMax_SRX_RS485_Modbus_Protocol_REV_205.pdf
description: "Modbus RTU communications protocol for the CoolMax SRX and SRX-R over RS485: communication parameters, register map and fault flags, with the minimum firmware for each."
---

# CoolMax SRX – Modbus RTU Protocol

*Rev 2.0.5. Markdown copy of the AERL document at https://www.aerl.com.au/docs/coolmax-srx-rs485-protocol; the PDF (https://www.aerl.com.au/documents/protocols/AERL_CoolMax_SRX_RS485_Modbus_Protocol_REV_205.pdf) is the controlled version.*

RS485 / Modbus Communications

# CoolMax SRX

Modbus RTU Communications Protocol

**Doc · SRX-MODBUS-RTU**

Standard Modbus RTU

Physical RS485 · RJ45

Default baud 9600 bps

Frame 8·N·1

Default address 20

Function codes 0x02 · 0x04 · 0x0B

CRC CRC-16 (LSB first)

| | |
|---|---|
| Document | SRX-MODBUS-RTU |
| Revision | 2.0.5 |
| Effective | 11 / 2026 |
| Product | CoolMax SRX / SRX-R |
| Audience | Integrators |
| Firmware | 2.0.1 and later |
| Format | A4 · 8 pages |

> Firmware
>
> Applies to CoolMax SRX and SRX-R firmware 2.0.1 and later. The **Min FW** column gives the first release with each item.
>
> 2.6.9 and 2.8.4 were SRX-R releases only, so an item first released in 2.8.4 reaches the SRX in 2.9.4. 2.6.6 to 2.8.4 have been withdrawn; update units on them to 2.17.9.

## Chapter 01 Bus, Connection and Settings

The CoolMax SRX and SRX-R (firmware 2.0.1 and later) provide read-only access to real-time measurements, fault flags and device information via the standard **Modbus RTU** protocol over RS485.

### Communication Parameters

| Parameter | Value | Min FW |
|---|---|---|
| Baud rate | 9600, fixed | 2.0.1 |
| Configurable baud rate | 9600 (default) / 19200 / 38400 / 57600 / 115200; set by AERL, as AERL Link cannot change it on 2.17.9 and earlier | 2.8.4 (SRX-R) / 2.9.4 (SRX) |
| Data bits | 8 | 2.0.1 |
| Stop bits | 1 | 2.0.1 |
| Parity | None | 2.0.1 |
| Device address | 20 (default); configurable 1–90 with AERL Link; a setting outside 1–90 is used as 20 | 2.0.1 |
| CRC | Modbus CRC-16 (transmitted LSB first) | 2.0.1 |

The broadcast address 0 is not supported; every request is addressed to one unit. Only the function codes in Chapter 02 are supported.

### Frame Timing

Modbus RTU frames are delimited by idle time on the bus: a frame is treated as complete once the bus has been silent for the inter-frame gap period.

Firmware before 2.19.6 uses an inter-frame gap of about **8 ms** at every baud rate. From 2.19.6 the gap follows the rate: 8 ms at 9600 baud, 4 ms at 19200 and 3 ms at 38400 baud and above. Allow for that gap, a short processing delay, and the transmission time of the response, which at 9600 baud is 126 ms for a full 58-register read.

Set the response timeout to at least **250 ms** at 9600 baud, and wait for the response, or for the timeout to expire, before sending the next request. Requests must not be overlapped: a second request that arrives before the first has been answered is discarded along with it.

### Chapter 01 · continued Physical Connection

RS485 uses the two paralleled RJ45 sockets labelled MODBUS, separate from the two CAN sockets. The pin-out differs: pin 6 is RS485-B here and GND on a CAN socket, so do not plug a CAN cable into a MODBUS socket.

![RJ45 connector viewed from the front, with the eight contacts numbered 1 through 8 from left to right](https://www.aerl.com.au/docs/_assets/assets/images/srx/aerl-srx-rj45-pinout.png)

*RJ45 connector viewed from the front: contacts numbered 1 to 8, left to right.*

| Pin | Signal |
|---|---|
| 3 | RS485-A (non-inverting) |
| 6 | RS485-B (inverting) |
| 8 | GND |

All other pins are unused.

### Network Topology

The Modbus network is a linear bus, with short stubs branching from ‘T’ connectors on the main backbone to each device. Terminate the bus at both ends with a **120 Ω** resistor between the RS485-A and RS485-B signals: at the master (many masters have a built-in or switchable terminator) and at the far end of the backbone.

![Modbus RS485 network topology: a master is daisy-chained to SRX 1, SRX 2 and SRX n on a two-wire bus plus GND, each unit exposing A, B and G terminals, with a 120 ohm termination resistor R2 fitted across A and B at the far end of the backbone](https://www.aerl.com.au/docs/_assets/assets/images/srx/aerl-srx-modbus-topology.png)

*Linear two-wire RS485 bus plus GND: master daisy-chained to SRX units (A / B / G), with 120 Ω termination across A and B at the far end of the backbone.*

Each CoolMax SRX is pre-fitted with a switchable 120 Ω termination, enabled by the slide switch next to the MODBUS sockets. Enable it on the SRX at the far end of the backbone only, and leave it off on every other SRX.

## Chapter 02 Supported Function Codes

0x02 Read Discrete Inputs Min FW 2.0.1

Read one or more fault flags as single bits. On firmware before 2.19.5 the quantity is 1–26 and start address + quantity must not exceed 26: inputs 10027–10032 cannot be read with 0x02, so read bit 26 from the Status Flags register (30027). From 2.19.5 the limit is 32. Inputs are packed eight per byte, first requested input in the LSB; a final partial byte is padded with zeros.

Request [Device ID] [0x02] [Start Address High] [Start Address Low] [Quantity High] [Quantity Low] [CRC Low] [CRC High] Response [Device ID] [0x02] [Byte Count] [Input Bytes…] [CRC Low] [CRC High]

| Frame | Bytes | Notes |
|---|---|---|
| Request | 14 02 00 00 00 1A FB 04 | Device 20 (0x14): read 26 inputs, start 0, quantity 26 (0x1A) |
| Response | 14 02 04 40 00 00 00 AA E3 | Byte count = 4 (last byte padded); 0x40 in the first byte = input 6 (Vin Low Fault) set |

0x04 Read Input Registers Min FW 2.0.1

Read one or more input registers containing measurements or device information. Quantity 1–58; start address + quantity must not exceed 58.

Request [Device ID] [0x04] [Start Address High] [Start Address Low] [Quantity High] [Quantity Low] [CRC Low] [CRC High] Response [Device ID] [0x04] [Byte Count] [Data…] [CRC Low] [CRC High]

| Frame | Bytes | Notes |
|---|---|---|
| Request | 14 04 00 08 00 02 F2 CC | Read 2 registers starting at offset 8 (PV Voltage, 30009–30010) |
| Response | 14 04 04 00 06 2E 83 03 45 | Byte count = 4, value = 0x00062E83 = 405 123 mV = 405.123 V |

0x0B Get Comm Event Counter Min FW 2.19.5

Read the count of successful 0x02 / 0x04 responses since power-up. Firmware before 2.19.5 answers 0x0B, but its response leaves out the function-code byte; the standard response below needs 2.19.5.

Request [Device ID] [0x0B] [CRC Low] [CRC High] Response [Device ID] [0x0B] [Status High] [Status Low] [Count High] [Count Low] [CRC Low] [CRC High] Response, before 2.19.5 [Device ID] [Status High] [Status Low] [Count High] [Count Low] [CRC Low] [CRC High]

Status is always 0. The counter is 16-bit and wraps.

All other function codes return an Illegal Function (01) exception. In particular **0x03 Read Holding Registers**, the default in many Modbus tools, is not supported: configure the client for input registers (0x04).

## Chapter 03 Exception Codes

Standard Modbus exception responses:

| Code | Name | Description | Min FW |
|---|---|---|---|
| 0x01 | Illegal Function | Function code other than 0x02, 0x04, 0x0B | 2.0.1 |
| 0x02 | Illegal Data Address | Start address + quantity exceeds 26 inputs (32 from 2.19.5) / 58 registers | 2.0.1 |
| 0x03 | Illegal Data Value | Quantity is 0, or greater than 26 inputs (32 from 2.19.5) / 58 registers | 2.0.1 |

Exception response [Device ID] [Function Code + 0x80] [Exception Code] [CRC Low] [CRC High]

Example: 14 83 01 91 34 answers an unsupported 0x03 request. A request whose CRC fails is discarded without a response.

## Chapter 04 Modbus Register Map

### Addressing

Register **reference numbers** (1xxxx for discrete inputs, 3xxxx for input registers) are a documentation convention only. The value placed on the wire is the zero-based **offset**: input 10001 is addressed as 0x0000 under function 0x02, and register 30001 is addressed as 0x0000 under function 0x04.

### Chapter 04 · continued Input Registers (FC 0x04)

All registers are read-only 16-bit words. Multi-register values are big-endian: the register at the lowest address holds the most significant word.

| Address | Offset | Regs | Description | Type | Unit / notes | Min FW |
|---|---|---|---|---|---|---|
| 30001–30004 | 0–3 | 4 | **Product ID** | UInt64 |  |  |
| 30005–30008 | 4–7 | 4 | **Serial Number** | UInt64 |  |  |
| 30009–30010 | 8–9 | 2 | **PV Voltage** | Int32 |  |  |
| 30011–30012 | 10–11 | 2 | **PV Current** | Int32 |  |  |
| 30013–30014 | 12–13 | 2 | **Output Voltage** | Int32 |  |  |
| 30015–30016 | 14–15 | 2 | **Output Current** | Int32 |  |  |
| 30017–30020 | 16–19 | 4 | **Reserved** | UInt64 |  |  |
| 30021–30022 | 20–21 | 2 | **Power (see below)** | Int32 |  |  |
| 30023–30024 | 22–23 | 2 | **Case Temperature** | Int32 |  |  |
| 30025–30026 | 24–25 | 2 | **Active Event** | Int32 |  |  |
| 30027–30030 | 26–29 | 4 | **Status Flags** | UInt64 |  |  |
| 30031–30034 | 30–33 | 4 | **Reserved** | UInt64 |  |  |
| 30035–30038 | 34–37 | 4 | **Reserved** | UInt64 |  |  |
| 30039–30040 | 38–39 | 2 | **Battery Temperature** | Int32 |  |  |
| 30041–30044 | 40–43 | 4 | **Hardware Version** | 8 × ASCII |  |  |
| 30045–30048 | 44–47 | 4 | **Firmware Version** | 8 × ASCII |  |  |
| 30049–30050 | 48–49 | 2 | **Model Type** | UInt32 |  |  |
| 30051–30054 | 50–53 | 4 | **Product ID (mirror)** | UInt64 |  |  |
| 30055–30058 | 54–57 | 4 | **Serial Number (mirror)** | UInt64 |  |  |

The four telemetry values (PV and output voltage and current) are positive in normal operation; a small negative reading can appear at zero current or voltage from sensor offset.

- **Power (30021)** before 2.19.6 holds the MPPT tracker’s last power sample, which with the default sensor configuration is **output** power (output voltage × output current). The value is held, stale, while the converter is stopped: read it together with the Status Flags. From 2.8.4 (SRX-R) / 2.9.4 (SRX) it is 0 or above. From 2.19.6 it is PV power, PV voltage × PV current, calculated live.
- **Case Temperature** comes from the power-stage sensor.
- **Battery Temperature** comes from a CAN Remote Temperature message or an external sensor. It reads 0 until the first value arrives, then holds the last value received. Values outside −10 to 100 °C are ignored.

## Chapter 05 Data Mappings

### Discrete Inputs and Status Flags

The 32 discrete inputs (FC 0x02, 10001–10032) and bits 0–31 of the Status Flags (30027–30030) are the same fault flags; bits 32–63 are always 0, and the numbering matches the CAN Active Flags broadcast. A flag reads 1 when its condition is active. On 2.17.9 and earlier the Status Flags are a latched snapshot, updated when a fault is raised or cleared, not a live view of each condition. Min FW is the first firmware with the flag.

| Bit | Input | Flag | Description | Min FW |
|---|---|---|---|---|
| 0 | 10001 | Hardware Fault (Generic) | Generic hardware fault; also a battery BMS alarm | 2.0.1 |
| 1 | 10002 | No Config Data | No configuration data set | 2.0.1 |
| 2 | 10003 | Config Data Out of Range | Configuration out of range; from 2.19.5, also a charge target outside the BMS limits | 2.0.1 |
| 3 | 10004 | Battery Sense Lost | Battery Sense no longer responding | 2.0.1 |
| 4 | 10005 | CAN Master Lost | CAN master lost | 2.0.1 |
| 5 | 10006 | Internal Over Temp | Internal temperature fault | 2.0.1 |
| 6 | 10007 | Vin Low Fault | Input voltage too low | 2.0.1 |
| 7 | 10008 | Vout Low Fault | Output voltage too low | 2.0.1 |
| 8 | 10009 | Vout High Fault | Output voltage too high | 2.0.1 |
| 9 | 10010 | Vin High Fault | Input voltage too high | 2.0.1 |
| 10 | 10011 | High PV Current | PV input current too high | 2.0.1 |
| 11 | 10012 | Over Temp Fault | Device temperature exceeds maximum | 2.0.1 |
| 12 | 10013 | Low Battery Temp | Low battery temperature (separate from cut-off) | 2.0.1 |
| 13 | 10014 | Earth Fault Positive | Earth fault on the positive conductor | 2.0.1 |
| 14 | 10015 | Earth Fault Negative | Earth fault on the negative conductor | 2.0.1 |
| 15 | 10016 | Active Cooling Fault | Fan fault | 2.0.1 |
| 16 | 10017 | Output Over-Current | Output current too high; on bit 24 from 2.19.5 | 2.0.1 |
| 17 | 10018 | Iin High Fault | Input current too high | 2.0.1 |
| 18 | 10019 | Cross Check Fault | Cross-check failed | 2.0.1 |
| 19 | 10020 | Temp Sensor Timeout | Temperature sensor unresponsive | 2.0.1 |
| 20 | 10021 | Earth Fault | Low isolation resistance; clears after about 30 min from 2.6.6, held until reset from 2.19.6 | 2.0.1 |
| 21 | 10022 | No Output Fault | No output detected | 2.0.1 |
| 22 | 10023 | Low Bat Temp Cut-off | Low battery temperature cut-off active | 2.0.1 |
| 23 | 10024 | High Bat Temp Cut-off | High battery temperature cut-off active | 2.0.1 |
| 24 | 10025 | Current Flow Disrupted | Charging interrupted (incl. output over-current) | 2.0.1 |
| 25 | 10026 | Pre-charge Failure | Pre-charge failure | 2.0.1 |
| 26 | 10027 | PV Pre-charge Failure | PV input pre-charge failure | 2.8.4 (SRX-R) / 2.9.4 (SRX) |
| 27 | 10028 | PWM Regulation Failure | Current flowing while PWM disabled | 2.19.5 |
| 28 | 10029 | PWM Corruption | PWM state corruption detected | 2.19.5 |
| 29 | 10030 | Stack Overflow | Internal stack overflow detected | 2.19.5 |
| 30 | 10031 | Clock Failure | Clock failure (CSS / drift) detected | 2.19.5 |
| 31 | 10032 | Brownout | Brown-out detected | 2.19.5 |

### Chapter 05 · continued Active Event (Registers 30025–30026)

A single **signed Int32** event code, not a bit field. 0 = no event (cleared once all flags clear and the converter re-enables). **Negative** values are fault codes, for example −1100 = temperature exceeds maximum; **positive** values are informational events, for example 101 = fault recovered. The register holds the most recent code raised. A battery BMS alarm shows here as −1305. Decode as two’s complement. The SRX user manual’s troubleshooting chapter lists the codes an installer sees; the full list is available from AERL on request.

## Chapter 06 Data Encoding

- **16-bit registers** : big-endian (MSB first). Value 0x2E83 is transmitted as [0x2E, 0x83] .
- **32-bit and 64-bit values** : split across 2 or 4 consecutive registers, most significant register at the lowest address. PV Voltage 405.123 V = 405 123 mV = 0x00062E83 is read from 30009 = 0x0006 and 30010 = 0x2E83 .
- **Signed values** : two’s complement over the full 32-bit width. −1100 = 0xFFFFFBB4 .
- **Milliunit scaling** : mV, mA, mW and m°C; divide by 1000 for V, A, W and °C.
- **Character fields** : 8 ASCII bytes packed two per register in string order, no terminator.

All values are transmitted as integers; no floating-point encoding is used.

### CRC-16

Every frame ends with a 16-bit CRC computed over all preceding bytes using polynomial 0xA001 (0x8005 reflected) with an initial value of 0xFFFF, and transmitted **low byte first**.

| Frame (without CRC) | CRC-16 | On the wire (CRC appended, low byte first) |
|---|---|---|
| 14 04 00 08 00 02 | 0xCCF2 | 14 04 00 08 00 02 F2 CC |
| 14 04 04 00 06 2E 83 | 0x4503 | 14 04 04 00 06 2E 83 03 45 (response) |

## Chapter 07 Revision History

| Rev. | Date | Change |
|---|---|---|
| – | – | Earlier revisions: see previous editions. |
| 2.0.2 | 10/09/26 | Reorganised for integrators. |
| 2.0.3 | 08/11/26 | Updated for firmware 2.19.6: register 30021 is PV power; inter-frame gap per baud rate; flag notes; MODBUS sockets have their own pin-out; bus termination clarified. |
| 2.0.4 | 09/11/26 | Minimum firmware marked on items that need firmware later than 2.17.9. |
| 2.0.5 | 16/11/26 | Minimum firmware for every register, function and flag, from 2.0.1; corrections for firmware 2.17.9 and earlier. |