# Surge Buster

Lightning Protection Module for the CoolPro

**50kA** Rating, 8/20 µs

**500J** Energy absorption

**26MOVs** 4.5 kA each

**85V** Max working voltage

## Specifications

Surge Buster · SURGE-BUSTER

The Surge Buster is a lightning protection module for the AERL CoolPro cathodic converter. Its twenty-six 4.5 kA metal oxide varistors (MOVs) give common-mode and differential surge protection on the CoolPro’s input, output and local cabinet earth, with a rated output capability of 50 kA (8/20 µs). It also protects the interrupt control and reference cell connections.

**When it is required** The Surge Buster is required only in lightning-prone applications: pipelines or structures longer than 100 metres or higher than 10 metres. There, install the CoolPro with an AERL Surge Buster to supplement its on-board surge protection; lightning damage to a CoolPro installed in such an application without one is not covered by the warranty. Elsewhere the Surge Buster is optional.

![Surge Buster board, illustrative top view](https://www.aerl.com.au/docs/_assets/assets/images/coolpro/aerl-surge-buster-drawing-plain.svg)

*Illustrative top view, not to scale. Safe side at the top, surge side at the bottom.*

### Surge ratings

Current and energy ratings are non-repetitive.

### Ordering

### Connections

### Mechanical

### Installation

- Wire as the CoolPro manual’s wiring diagram
- Connect the earth terminal to the cabinet chassis
- Protect the bare board from moisture and vermin
- Route cables downwards, away from the board
- Output circuit breaker or fuse not recommended
- Interrupt sequencer: 8–30 Vdc input

AERL reserves the right to change any product, product specifications and data without notice to improve reliability, function, or design or otherwise.

#### Manufactured by

**Australian Energy Research Laboratories** 1/75 Bluestone Circuit, Seventeen Mile Rocks QLD 4073

#### Origin and warranty

Australian made 2-year warranty

#### Contact