AERL technical documentation

CoolPro Cathodic Converter — User Manual Rev 2.0.1

21 pages

Download PDF Print
Download PDF· Rev 2.0.1 User Manual

CoolPro

Cathodic Converter™

AERL CoolPro Cathodic Converter — front three-quarter view
CP30 Installation & OperationAER04 Rev 2.0.1, 8 Nov 2026
aerl.com.au CP30 · Max CP current 30 A

Contents

Document

DocumentAER04
Revision2.0.1
ModelCP30
Max CP Current30 A
FormatA4 · 21 pages
CoolPro CP30 User Manual AER04 Rev 2.0.1
01

Important Safety InformationDisclaimer, symbols, manual scope

Disclaimer

AERL Pty Ltd, its affiliates, agents, and employees, and all persons acting on its or their behalf (collectively, “AERL”):

(a) Disclaims any and all liability for any errors, inaccuracies or incompleteness contained in any datasheet or in any other disclosure relating to any product.

(b) Assumes no responsibility or liability for loss or damage whether direct, indirect, consequential or incidental, which might arise out of use of such information. The use of any such information will be entirely at the user’s risk.

(c) Reserves the right to change any AERL product, product specifications and data without notice to improve reliability, function or design or otherwise.

CoolPro CP30 User Manual AER04 Rev 2.0.1

Notice of Copyright

CoolPro Cathodic Converter™ User Manual © 2026 AERL Pty Ltd. All rights reserved. AERL reserves the right to periodically revise this document and to make changes to the content without notice.

This manual contains important safety information and installation instructions for the CoolPro Cathodic Converter™. It uses the following symbols for important operating information and potentially dangerous conditions.

Important

Indicates information that must be followed to ensure proper operation of the CoolPro Cathodic Converter™.

Caution

Indicates a critical procedure for the safe installation of the unit, or provides safety information that is required to be followed.

About This Manual

CoolPro CP30 User Manual AER04 Rev 2.0.1
02

SpecificationsOptions, ratings, electrical characteristics

Model
ModelMax anti-corrosion current
CP3030 A
Options
OptionFunction
Surge BusterLightning surge arrestor
Structure / Ref Cell Potential ControlAccurate corrosion protection for structures where overprotection is harmful

Surge Buster

The Surge Buster lightning protection module uses twenty-six 4.5 kA metal oxide varistors (MOVs) to give common-mode and differential surge protection on the CoolPro’s input, output and local cabinet earth; its rated output capability is 50 kA (8/20 µs). It also protects the interrupt control and reference cell connections. It also contains the optically isolated ON/OFF control and a surge protected opto-coupler for buffered/isolated ON/OFF interrupt control if permanently connecting an interrupt sequencer.

Important

The Surge Buster is required only in lightning-prone applications: pipelines or structures longer than 100 metres or higher than 10 metres. There, install the CoolPro with an AERL Surge Buster (50 kA / 500 Joule) to supplement its on-board surge protection; lightning damage to a CoolPro installed in such an application without one is not covered by the warranty. Elsewhere the Surge Buster is optional.

Surge Buster — electrical characteristicsValue
Output current rating (non-repetitive 8/20 µs rating)50,000 A
Output energy absorption (non-repetitive 8/20 µs rating)500 Joules
Output energy absorption (non-repetitive 10/1000 µs rating)230 Joules
CoolPro CP30 User Manual AER04 Rev 2.0.1

Constant Structure Potential Control Mode

In some situations, overprotection of a structure may be harmful. Examples of such situations include protection of structures with painted coatings, and structures under mechanical stress (such as tanks and pressure vessels). In these circumstances, precise control of corrosion potential can be achieved using a reference cell placed in the ground near the structure to be protected.

Constant structure potential
ParameterValue
Min. controllable structure / ref cell potential−2400 mV
Max. controllable structure / ref cell potential2400 mV
Physical characteristics
ParameterTypical
Weight1.5 kg
Dimensions (L × W × H)240 × 160 × 90 mm
Input / output cable size25 mm²
CP30 — absolute maximum ratings
ParameterMax
Max ambient air temp.65 °C (12/24 V) · 50 °C (36/48 V)
Ibatt — max output current30 A
VMIN — min input voltage11 V
VMAX — max input voltage60 V
CP30 — electrical characteristics
DescriptionValue
VOUT — output voltage (adjustable)0 – VIN
Iq — standby current consumption35 mA
η — efficiency @ 10 V, 30 A, 25 °C97.00%
Output current variation with load< ±0.50%
Output current variation with temp.< ±0.50%
Current interruption fall time1–2 ms (typ)
CoolPro CP30 User Manual AER04 Rev 2.0.1
03

OverviewFeatures & safety information

The AERL CoolPro Cathodic Converter™ is a high-current DC–DC converter and controller for impressed current cathodic protection (ICCP). Units can run in parallel to protect large metallic structures. Its high efficiency suits solar-powered sites and keeps component temperatures and thermal cycling low, which extends its life in hot conditions. Its weatherproof enclosure suits the harsh sites where cathodic protection is often deployed.

Options are automatic reference cell (structure potential) control and the AERL “Surge Buster” lightning protection module. Main features:

Caution — important safety information

The CoolPro Cathodic Converter™ can operate at lethal voltages. Take extreme care whenever you work on it.

Battery packs are extremely destructive in reverse polarity and short circuit situations. The CoolPro on-board fuse is provided only as a last line of defence against continual power dissipation in the product. It is always necessary to connect appropriately sized circuit breakers.

All electronic circuits in the CoolPro product or connected to the product are not isolated from the battery. This means that accidentally shorting the control module or the LCD meter module can cause a destructive failure. Use extreme caution when the product is live.

CoolPro CP30 User Manual AER04 Rev 2.0.1
04

Cathodic Protection BackgroundGround bed, potential, control modes

When a structure corrodes, it is because the environment or another metallic body (a cathode) becomes involved in a series of chemical reactions with the structure (the anode). These reactions steal electrons from the metallic bonds holding the structure together, and corrosion is the result.

Impressed current cathodic protection such as supplied by the AERL CoolPro Cathodic Converter™ injects electrical current into the structure, which provides the structure with a surplus of electrons. This means that electrons can still be provided to the environment to fuel the cathodic reactions – but the anodic reaction does not occur, so metallic bonds in the structure are safe from degradation. The protection current is injected using inert metallic anodes and flows through the ground bed to the structure.

Ground Bed Resistance

Resistance anywhere in the path between the anode and the structure is a cause of wasted corrosion protection power and should be minimised. Multiple anodes are often used to reduce the resistance between the anode and the ground bed. Additionally, mesh anodes with high surface areas can be used, and coke breeze is used as an interface between the anode and the earth.

Corrosion Potential

The corrosion potential of the structure can be thought of as the electrochemical force driving the anodic reactions in the structure to occur. Corrosion potential varies depending on the environmental conditions and the presence of other corrosion-inhibiting factors such as a protective coating. Using impressed current cathodic protection, the aim is to reduce the corrosion potential of the structure so that the anodic reactions are no longer driven to occur.

Determining the correct level of current to provide to the structure is not trivial. Providing too little current can mean that the structure is not completely protected and will corrode. Too much current can lead to other chemical reactions resulting in effects such as hydrogen embrittlement of the structure and breakdown of any protective coatings on the pipe. The corrosion potential of the structure can be determined and accurately corrected for using a reference cell.

Reference Cell Measurement

A reference half-cell is generally used to survey the corrosion potential in a local area around the structure to be protected. This determines the natural electrochemical corrosion potential which must be cancelled out by impressing current from the CoolPro unit. From here on, this manual assumes a copper/copper sulphate (Cu/CuSO₄) half-cell, the most common type. Impressing current into the structure makes it chemically less anodic; this will be reflected in its potential measured with respect to the Cu/CuSO₄ half-cell. The ideal potential to exist between a Cu/CuSO₄ reference cell and a structure is 850 mV (with the reference cell more positive).

CoolPro CP30 User Manual AER04 Rev 2.0.1
Plot of structure potential (E) versus impressed current (I) measured against a Cu/CuSO4 reference cell: an unprotected pipe at −300 mV corrodes rapidly, the optimal protection level at −850 mV gives minimal corrosion, and −1000 mV represents overprotection
Figure 1 · The voltage between the structure and the half-cell changes with applied CP current

Instantaneous Potential

It is desirable to measure the potential of the structure while it is being protected to make sure it is close to the optimal −850 mV level. The problem is that while protection current is flowing there is an ohmic error introduced in the reference cell measurement due to the CP current flowing through the resistance of the ground bed. To reduce the severity of this error, care should be taken to place the reference cell much closer to the structure than the anode injection point.

To compensate for this error even further, the CP current is removed and then instantaneously the potential of the structure is measured. Because the corrosion potential of the structure takes some time to decay back to its natural state, it can be accurately measured a few milliseconds after the ohmic error is removed. This is referred to as measuring the “Instantaneous Off Potential” of the structure.

Protection Current Control Modes

There are three control modes in the CoolPro unit, although only one can be active at any time. The control modes are output current control mode, output voltage control mode, and structure / ref cell potential control mode.

CoolPro CP30 User Manual AER04 Rev 2.0.1

Control Mode Relationships

Output current and output voltage are related by Ohm’s law with the ground bed resistance between the anode and the structure. Ground bed resistance changes with many factors but the major one is ground moisture content. However, at any two given times, if the setup and environment are completely unchanged, a given output voltage will produce the same output current. Struct/ref potential is related to output current by the electrochemical relationships governing how much current is needed to prevent corrosion from occurring.

Note

The control mode which is commanding the lowest CP current will always be active.

Using the Control Modes

Each of the control mode setpoints provides upper limits on the CP current that can be produced. The lowest setpoint will always be the active limit on the CP current.

Using Ref Cell control: Struct/ref potential control mode is tuned to give the desired instantaneous off potential (see chapter 08). Current control mode and voltage control mode are used to set the maximum power that can be delivered by the system in the event of a non-typical operating condition. These should be selected paying attention to the estimated ground bed resistance and being careful not to interfere with the normal operation of Struct/Ref potential control mode.

Not using Ref Cell control: Struct/ref potential control mode is disabled by linking the Struct/ref terminals and turning the adjustment dial clockwise all the way. Current control mode is set to be the desired constant CP current. Voltage control mode setpoint is selected to limit the power delivered by the CP system if the ground bed resistance changes due to local or generalised reductions in ground bed moisture. For example, if regulating in current control mode and the ground bed resistance doubles during a dry period, because P = I²R the power output will double if not checked by the voltage control mode setpoint.

CoolPro CP30 User Manual AER04 Rev 2.0.1
05

PCB LayoutTerminals & adjustment

CoolPro internal PCB with numbered callouts: 1 Input/Output Terminals, 2 Reference Cell Inputs, 3 Current Interrupt Terminal, 4 LCD Meter Module Header, 6 Adjustment Dials Header, 7 Low Battery Reset Button, 8 Battery Voltage Selector
Figure 2 · CoolPro internal PCB layout
CoolPro CP30 User Manual AER04 Rev 2.0.1

Terminal & Indicator Functions

The numbers below match the callouts in Figure 2 (previous page); there is no callout 5.

Pos.DescriptionFunction
1Input / output terminalsConnect battery and load with polarity marked on board. Output + to anode. Output − to structure.
2Reference cell inputsConnect to ref cell and to structure being protected.
3Current interrupt terminalShort terminals together to immediately interrupt current.
4LCD meter module headerRibbon cable connection to front panel LCD meter module.
6Adjustment dials headerRibbon cable connection to front panel adjustment dials.
7Low batt reset buttonReset hysteresis on low battery cut out.
8Battery voltage selectorSelect nominal input voltage for low battery cut out. See arrow for “on” position.
CoolPro CP30 User Manual AER04 Rev 2.0.1
06

Circuit Breakers & MountingProtection & location

Circuit Breakers

Note

AERL recommends the use of 6 kVA, 8 kVA or 10 kVA DC-rated circuit breakers with an appropriate voltage rating between the batteries and the CoolPro unit.

Using an output circuit breaker or fuse is not recommended as large currents can be shunted by the onboard surge protection circuitry and the “Surge Buster” during surges. This will cause the output breaker to trip unnecessarily.

Mounting

Line drawing of the CoolPro enclosure showing the three front-panel adjustment dials on the top face and the four cable glands along the lower edge
Figure 3 · CoolPro enclosure — adjustment dials and cable glands

Location

Caution

Mount the CoolPro where splashing water and direct sunlight cannot reach it.

The “Surge Buster” is a bare PCB: if you use one, protect it from all moisture and vermin.

Cables should always be routed downwards away from the CoolPro and Surge Buster products so that any moisture which may condense on the cables does not run back into the product.

The aluminium cold plate on the back of the enclosure is the source of heat dissipation for the CoolPro controller. The CoolPro unit will run more efficiently and last longer if the product can be spaced out such that air is allowed to flow past the aluminium plate.

CoolPro CP30 User Manual AER04 Rev 2.0.1
07

InstallationWiring, connections, setup

Wiring Diagram

Figure 4 shows the CoolPro connected to the field equipment through a Surge Buster. A dashed line divides the safe side from the surge side. The reference cell and structure sense connect to the Ref Struct terminals; the output feeds the anode and structure, and the input comes from the battery bank. A remote current interrupt switch connects to the Link On/Off (current interrupt) terminals through the Surge Buster’s protected ON/OFF path.

CoolPro CP wiring diagram: the AERL CoolPro connects through a Surge Buster buffer to the reference cell, protected structure, anode, battery bank and remote current interrupt; a dashed boundary divides the safe side from the surge side
Figure 4 · CoolPro wiring diagram
CoolPro CP30 User Manual AER04 Rev 2.0.1

Connections

Caution

Open the breakers so the CoolPro is isolated from every source before you make any connection.

Connect the battery + and − to the terminals marked Input + and −.

Connect the anodes to Output + and the protected structure to Output −.

Use suitably rated cable for every connection. Check the input polarity with a multimeter before you close any breaker.

Setup

Important

Set the battery voltage selector (item 8 in Figure 2) to the nominal battery voltage: 12, 24, 36 or 48 V.

Configuration

There are three control modes in the CoolPro controller: output current control mode, output voltage control mode, and structure / ref cell potential control mode.

Note

Only one control mode can be active at any time. The control mode with the lowest setpoint will always be active.

Set each setpoint with its dial on the front panel while the CoolPro is running: clockwise raises it, anti-clockwise lowers it.

CoolPro CP30 User Manual AER04 Rev 2.0.1

Setting the Current Control Mode Setpoint

  1. Turn all three dials on the front panel fully anti-clockwise. Every setpoint is now zero.
  2. Close the input breakers. The “Input Alive” LED lights at once; the “Output Alive” LED stays off.
  3. Turn the “Voltage” dial (and the “Ref Cell” dial, if you use reference cell control) a few turns clockwise. No current flows and the Output Alive LED stays off, because the current setpoint is still zero.
  4. The current setpoint is now the lowest, so it limits the output. Slowly turn the “Current” dial clockwise while you measure the output current. If the current stops rising, another control mode has taken over: raise that mode’s dial until the current control mode is limiting again.

Power Down Procedure

Shut the CoolPro down in this order to avoid voltage and current transients on the protected structure.

  1. Turn all three dials fully anti-clockwise. Every setpoint is now zero.
  2. Check that the LCD shows zero output for at least two full display cycles (10 seconds). The “Output Alive” LED turns off.
  3. Open the input breakers. The “Input Alive” LED turns off.
CoolPro CP30 User Manual AER04 Rev 2.0.1
08

Operating GuidelinesLow battery, interruption, modes

Low Battery Cutout

The CoolPro has an automatic low-battery cut-out to protect lead-acid batteries from over-discharge. It stops output when the battery voltage falls below the cut-out voltage, and resumes when the battery has recharged to the cut-in voltage.

Note

To force the CoolPro to cut back in at any voltage above the cut-out voltage, press the Low Batt Reset button (item 7 in Figure 2).

Nominal battery voltage (V)Cut-outCut-in
1211 V13 V
2422 V26 V
3633 V39 V
4844 V52 V

High Speed Current Interruption

To measure the instantaneous off potential, the output can be switched to zero within 1–2 ms. Link the current interrupt terminals (item 3 in Figure 2; Link On/Off in Figure 4): linked, the output is off.

Ref Cell Control Mode

With the reference cell option fitted, calibrate the CoolPro for the required structure / ref cell potential: turn the “Ref Cell” dial while you measure the structure / ref cell voltage with a multimeter (or with high-speed current interruption and an oscilloscope) until it reaches the required value.

Note

The reference cell can be controlled over a range of +2400 mV to −2400 mV.

Constant Current Output Mode

The CoolPro is usually run in constant current output mode. Set the output current with the “Current” dial on the front panel.

Constant Voltage Output Mode

When the ground bed resistance rises in dry periods, the voltage limit overrides the current control mode. This limits the power drawn from the batteries and protects them from heavy cycling. Set the voltage limit with the “Voltage” dial on the front panel.

CoolPro CP30 User Manual AER04 Rev 2.0.1
09

Meter Board Sub-assemblyLCD, RS485 / Modbus telemetry

Overview

The Meter Board is a microcontroller-driven sub-PCB mounted alongside the CoolPro power stage. It provides:

Important

The Meter Board is a monitoring path only. RS485 / Modbus traffic does not change output current, voltage limit, or reference-cell setpoint. Those remain manual front-panel adjustments per chapter 07.

The unit is calibrated and tested at the AERL factory. Re-calibration is a workshop operation; contact AERL if a unit’s measurements drift.

LCD Display Operation

During normal operation, the LCD alternates between input and output measurements every 5 seconds. Each screen shows the corresponding voltage, current, and the board temperature.

CoolPro CP30 User Manual AER04 Rev 2.0.1

RS485 / Modbus Telemetry

Default communication parameters: 9600 baud, 8-N-1, station 40.

To use a different station address or baud rate, change it in the field over Modbus: write the new address to holding register 40001 (or the baud rate index to 40002); the change takes effect after a reset (see the CoolPro Modbus RTU Communications Protocol). Alternatively, ask AERL to pre-program a different address or baud rate when ordering. The settings are kept in non-volatile memory and survive power cycles.

RS485 connector pinout (RJ45)

The Meter Board exposes RS485 on a standard 8P8C RJ45 connector.

PinSignal
1NC
2NC
3RS485 A
4NC
PinSignal
5NC
6RS485 B
7NC
8GND
Note

Pins 1, 2, 4, 5, and 7 are not connected. Use only pins 3 (A), 6 (B), and 8 (GND).

The register map (live measurements, status flags, device information and configuration registers) is in the CoolPro Modbus RTU Communications Protocol (CP-MODBUS-RTU), available from aerl.com.au.

Contact AERL

Address

Australian Energy Research Laboratories

1/75 Bluestone Circuit
Seventeen Mile Rocks QLD 4073
Australia

Phone & web

Phone: 1800 950 865

Email: [email protected]

Web: aerl.com.au

CoolPro CP30 User Manual AER04 Rev 2.0.1
10

Revision HistoryDocument change log

DateVersionDescription
Earlier revisions: see previous editions.
11/05/2026AER04 Rev 2.0.0First issue for the CP30, under document number AER04
08/11/2026AER04 Rev 2.0.1Re-issued in the new AERL document design; the Surge Buster is required only in lightning-prone applications; the Modbus address and baud rate can be changed in the field; ambient temperature for 36/48 V inputs is −20 to 50 °C
CoolPro CP30 User Manual AER04 Rev 2.0.1

Notes

CoolPro CP30 User Manual AER04 Rev 2.0.1

Notes

CoolPro CP30 User Manual AER04 Rev 2.0.1

Notes

CoolPro CP30 User Manual AER04 Rev 2.0.1

Australian Energy Research Laboratories

Address

1/75 Bluestone Circuit
Seventeen Mile Rocks QLD 4073
Australia

Contact

[email protected]
[email protected]

aerl.com.au Phone1800 950 865