# AERL LiFe² → AERL Cloud — Integration Guide

*Rev 1.0.1. Markdown copy of the AERL document at https://www.aerl.com.au/docs/life2-cloud-integration; the PDF (https://www.aerl.com.au/documents/guides/AERL_Nexus_LiFe2_Cloud_Integration_REV_101.pdf) is the controlled version.*

Integration Guide

# AERL LiFe² → AERL Cloud

Via an AERL Nexus Gateway, Over CAN Bus

**AERL Nexus · Rev 1.0.1**

![AERL Nexus gateway](https://www.aerl.com.au/docs/_assets/assets/images/nexus/aerl-nexus-lite.png)

| | |
|---|---|
| Revision | 1.0.1 |
| Effective | 11 / 2026 |
| Audience | Installers |
| Gateway | AERL Nexus |
| Transport | CAN bus |
| Applies to | Any approved CAN device |
| Cloud setup | docs.aerl.cloud |
| Format | A4 · 3 pages |

## In This Guide

## Chapter 01 Connecting the Nexus to the CAN Bus

These instructions apply to **any AERL-approved CAN bus product** (battery, inverter, MPPT). Once the Nexus is on the CAN bus, it finds the approved devices and handles their communications automatically: there is nothing to configure on the battery or inverter for monitoring.

The Nexus has two CAN ports that are **internally linked**, so it can sit directly on the existing CAN bus between your AERL-approved products. Connect it one of two ways:

### Option 1 — Inline Pass-Through (Preferred)

Insert the Nexus inline on the CAN bus. Because CAN 1 and CAN 2 are internally linked, existing communications keep flowing through the Nexus:

- **Battery → Nexus CAN 1**
- **Nexus CAN 2 → approved inverter / MPPT**

See Figure 1 for this arrangement.

### Option 2 — Endpoint with Termination Plug

The Nexus has no built-in termination. If it sits at an end of the CAN bus, connect one CAN socket to the bus and fit a **120 Ω RJ45 termination plug** in the other.

![AERL LiFe² 48 V battery connected by CAN bus to the Nexus CAN 1 socket, with the internally linked Nexus CAN 2 socket connected on to an approved inverter or MPPT.](https://www.aerl.com.au/docs/_assets/assets/images/nexus/nexus-canbus-wiring.svg)

**Figure 1** — Inline pass-through: the LiFe² battery connects to Nexus CAN 1, and the internally linked CAN 2 connects on to the approved inverter or MPPT.

## Chapter 02 Getting Online

Once the Nexus is on the CAN bus, it handles the rest. Plug in **Ethernet**, power it on, and claim it in AERL Cloud. For detailed AERL Cloud setup instructions, see [docs.aerl.cloud](https://docs.aerl.cloud).

## Chapter 03 Quick Checklist

1. Connect the Nexus to the CAN bus either inline (CAN 1 from the battery, CAN 2 to the inverter/MPPT), or at the end of the bus with a termination plug.
2. Get the Nexus online and claim it in AERL Cloud — see [docs.aerl.cloud](https://docs.aerl.cloud) .
3. Confirm the LiFe² data appears in AERL Cloud.