AERL LiFe² 5120S — System Sizing Guide Rev 1.0.0

15 pages

Download PDF Print
Download PDF· Rev 1.0.0 System Sizing Guide

AERL LiFe² 5120S

Battery Modules, Cabinets and Inverters

AERL LiFe² 5120S
LiFe²-5120S · LiFe² battery cabinets System Sizing GuideRev 1.0.0, 8 Nov 2026
aerl.com.au © 2026 AERL Pty Ltd

Contents

Document

Revision1.0.0
Effective11 / 2026
AudienceSystem designers and installers
BatteryAERL LiFe² 5120S, 5.12 kWh / 100 Ah
CabinetsCAB6 · CAB10 · CAB4-OUTD · CAB6-OUTD · CAB10-OUTD
FormatA4 · 15 pages
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0

About This Guide

This guide shows how to size a LiFe² 5120S battery bank: how many modules, which cabinet, and the checks on current, temperature and cabling. It brings together values from the LiFe² 5120S datasheet, the Installation and Operation Manual, the PCE Integration Guide and the Managed Battery Integration Guide. Where they set a rule, this guide restates it; for installation, wiring and settings, use those documents.

The system design is the designer's responsibility. Check every design against the inverter manufacturer's requirements and the local standards, including AS/NZS 5139 and AS/NZS 3000.

01

Building BlocksThe LiFe² 5120S module, usable energy, battery cabinets

1.1The LiFe² 5120S Module

ParameterValue
Nominal voltage51.2 V DC
Operational voltage range40.8 V DC to 58.4 V DC
Capacity5.12 kWh / 100 Ah
Depth of dischargeUp to 100%
Maximum continuous discharge current100 A (1C at 25 °C)
Peak discharge current200 A (10.24 kW, 5 s)
Maximum continuous charge current100 A (1C at 25 °C)
Peak charge current200 A (at 25 °C)
Integrated circuit breaker2-pole, 125 A, 80 V DC
Short-circuit current2000 A
ScalabilityUp to 64 modules in parallel (327.68 kWh)
Series connectionNot permitted
Operating temperature, ManagedCharge −10 to 55 °C, discharge −20 to 55 °C
Operating temperature, Self-ManagedCharge 0 to 55 °C, discharge −5 to 55 °C
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0

1.2Usable Energy

Size the bank on usable energy: the module's 5.12 kWh multiplied by the depth of discharge (DoD) the inverter is set to.

ModeDefault depth of dischargeUsable energy per module
Managed (CAN bus)80% (20% SOC low cut-off)4.096 kWh
Self-Managed (no comms)90% (recommended setting)4.608 kWh

The battery can discharge to 100%; a shallower depth of discharge gives a longer cycle life (LiFe² 5120S Installation and Operation Manual, chapter 11).

1.3Battery Cabinets

CabinetModulesEnergyBusbar ratingUse
LiFe²-CAB6Up to 630.72 kWh625 AIndoor, IP20
LiFe²-CAB10Up to 1051.20 kWh1250 AIndoor, IP20
LiFe²-CAB4-OUTDUp to 420.48 kWh250 AOutdoor, IP55
LiFe²-CAB6-OUTDUp to 630.72 kWh400 AOutdoor, IP55
LiFe²-CAB10-OUTDUp to 1051.20 kWh600 AOutdoor, IP55

The cabinets are pre-wired (quick connectors, 4 AWG UL cable) and have no DC circuit breaker: fit the DC isolation and protection between the cabinet and the inverter.

Cabinet current

A cabinet's continuous current is the lower of 100 A per installed module and its busbar rating. In the indoor cabinets the busbar carries every module at full current. In the outdoor cabinets the busbar rating is lower than the modules together (for example 250 A for four modules in the LiFe²-CAB4-OUTD), so the busbar sets the limit.

AERL LiFe² 5120S · System Sizing GuideRev 1.0.0
02

Sizing MethodStep 1: energy, step 2: minimum modules for the inverter

2.1Step 1: Energy

  1. Work out the energy the battery must supply between charges, in kWh: the daily load from the battery, multiplied by the days of autonomy the site needs.
  2. Divide by the usable energy per module (4.096 kWh Managed, 4.608 kWh Self-Managed).
  3. Round up to a whole number of modules.

2.2Step 2: Minimum Modules for the Inverter

Look up the inverter in chapter 03 and use at least that number of modules. The minimum makes sure the battery can support the inverter's full output. In Managed mode the inverter stays within the battery's limits; in Self-Managed mode, fewer modules than the minimum may operate the battery outside its warranty conditions.

For an inverter that is not listed, check the discharge current: the inverter's maximum DC current must not exceed 100 A per module. Work out the DC current from the inverter's rated AC power, its efficiency and the lowest battery voltage it runs at:

Idc = Pac ÷ (η × Vdc)

Check the inverter's surge rating against the module's peak discharge of 200 A for 5 seconds.

2.3Step 3: Charge Current

Add up the charge current of every source that can charge at the same time: the inverter's charger (from the grid or a generator) and any CoolMax SRX or other DC charge controllers.

2.4Step 4: Temperature

The battery allows its full 1C charge and discharge rates only between about 20 and 45 °C; outside that range the rates fall (LiFe² 5120S Installation and Operation Manual, chapter 12). Below 0 °C a managed battery charges at no more than 0.1C, and it does not charge below −10 °C. For a site that is cold in winter, size the bank so that it can accept the winter charge current at the reduced rate, or keep the battery warm.

AERL LiFe² 5120S · System Sizing GuideRev 1.0.0

2.5Step 5: Cabinets

Choose cabinets for the module count and the site: indoor (IP20) or outdoor (IP55). Check that each cabinet's continuous current (the lower of 100 A per module and the busbar rating) covers its share of the inverter's DC current. Connect parallel cabinets through a DC bus or DC combiner box, with DC cables of the same length for every cabinet.

2.6Step 6: Round Up and Check

03

Minimum Modules by InverterAERL controllers, Selectronic, Victron, Deye, Noark, Solis, SMA

The minimum number of LiFe² 5120S modules for each AERL charge controller and each Selectronic, Victron, Deye, Noark, Solis and SMA inverter, from the LiFe² PCE Integration Guide and the LiFe² Managed Battery Integration Guide.

3.1AERL Controllers

ChargerBattery modules
SRX 600/70-481
SRX-R 600/60-481

3.2Selectronic

InverterSingle phaseThree phase
SPMC48026
SPMC48126
SPMC48239
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0

3.3Victron

Per inverter, from Victron's and ZYC's published tables.

InverterSingle-phase on-gridSingle-phase off-gridThree-phase on-gridThree-phase off-grid
MultiPlus 48/500/61111
MultiPlus 48/800/91111
MultiPlus 48/1200/131111
MultiPlus 48/1600/201112
MultiPlus 48/2000/251112
MultiPlus 48/3000/351123
MultiPlus 48/5000/701224
MultiPlus-II (GX) 48/3000/35-321113
MultiPlus-II (GX) 48/5000/70-501224
MultiPlus-II 48/3000/35-321113
MultiPlus-II 48/5000/70-501224
MultiPlus-II 48/8000/110-1001337
MultiPlus-II 48/10000/140-1002338
MultiPlus-II 48/15000/200-10024412
Quattro 48/5000/70-100/1001224
Quattro 48/8000/110-100/1001327
Quattro 48/10000/140-100/1002348
Quattro 48/15000/200-100/10024412
Quattro II 48/5000/70-501224
RS Smart Solar 48/60001224
Multi RS Solar 48/60001224
Multi RS Solar 48/6000 Dual Tracker1224
EasySolar-II 48/3000/35-32 MPPT 250/70 GX1123
EasySolar-II 48/5000/70-50 MPPT 250/100 GX1224
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0

3.4Deye

InverterBattery modules
SUN-3.6K-SG01LP1-EU2
SUN-5K-SG01LP1-EU2
SUN-7.6K-SG01LP1-EU3
SUN-8K-SG01LP1-EU3
SUN-12K-SG01LP1-EU4
SUN-14K-SG01LP1-EU4
SUN-16K-SG01LP1-EU5
SUN-3.6K-SG03LP1-EU2
SUN-4.6K-SG03LP1-EU2
SUN-5K-SG03LP1-EU2
SUN-5.5K-SG03LP1-EU2
SUN-6K-SG03LP1-EU2
SUN-5K-SG04LP3-EU2
SUN-6K-SG04LP3-EU2
SUN-8K-SG04LP3-EU3
SUN-10K-SG04LP3-EU3
SUN-12K-SG04LP3-EU4
SUN-3K-SG04LP1-EU1
SUN-3.6K-SG04LP1-EU2
SUN-5K-SG04LP1-EU2
SUN-6K-SG04LP1-EU2
SUN-3.6K-SG05LP1-EU2
SUN-5K-SG05LP1-EU2
SUN-6K-SG05LP1-EU2
SUN-7K-SG05LP1-EU2
SUN-7.6K-SG05LP1-EU3
SUN-8K-SG05LP1-EU3
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0

3.5Noark

InverterBattery modules
Ex9N-DH-3KS-AU1
Ex9N-DH-3.6KS-AU1
Ex9N-DH-5KS-AU2
Ex9N-DH-6KS-AU2
Ex9N-DH-7.6KS-AU3
Ex9N-DH-8KS-AU3
Ex9N-DH-5KT-AU2
Ex9N-DH-6KT-AU2
Ex9N-DH-8KT-AU3
Ex9N-DH-10KT-AU3
Ex9N-DH-12KT-AU4

3.6Solis

InverterSingle phaseThree phase
RHI-3K-48ES-5G1—
RHI-3.6-48ES-5G1—
RHI-4.6K-48ES-5G2—
RHI-5K-48ES-5G2—
RHI-6K-48ES-5G2—
RAI-3K-48ES-5G1—
S5-EH1P3K-L1—
S5-EH1P3.6K-L1—
S5-EH1P4.6K-L2—
S5-EH1P5K-L2—
S5-EH1P6K-L2—
S5-EO1P4K-482—
S5-EO1P4K-48-P2—
S5-EO1P5K-482—
S5-EO1P5K-48-P2—
S6-EO1P4K-4824
S6-EO1P5K-4825
S6-EH1P3K-L-EU13
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0
InverterSingle phaseThree phase
S6-EH1P3.6K-L-EU24
S6-EH1P4.6K-L-EU24
S6-EH1P5K-L-EU25
S6-EH1P6K-L-EU26
S6-EH1P3K-L-PRO13
S6-EH1P3.6K-L-PRO24
S6-EH1P5K-L-PRO25
S6-EH1P6K-L-PRO26
S6-EH1P8K-L-PRO37

3.7SMA

Sunny IslandSingle phaseThree phase
SI 4.4M26
SI 6.0H26
SI 8.0H39
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0
04

Cabling and Protection

These are pointers to the rules in the LiFe² 5120S Installation and Operation Manual. Size every cable and protective device to AS/NZS 3008.1.1 and AS/NZS 5139 for the installed current, route length and conditions.

ItemRule
DC cables to the inverterSize for the current of the connected inverter or load. Keep the voltage drop small (AERL's example systems use 2% or less).
Cable terminalsLiFe²-CAB6: SCxxx-10. LiFe²-CAB10: SCxxx-12. Outdoor cabinets: contact AERL.
Parallel cabinetsThrough a DC bus or DC combiner box. DC cables of the same length and size for every cabinet, so every module sees the same impedance.
Custom enclosuresConnect modules to the busbar with AERL pre-assembled cables (AERL-BATT-CABLE-2.5), all the same length and size. Fuses, cables and connections are the designer's to select.
DC isolation and protectionA 2-pole DC breaker or MCCB between the battery and the inverter, on both conductors. Rate it for the bank's prospective short-circuit current (2000 A per module). The cabinets have no DC breaker.
Protective earthCross-section at least 25 mm², with an SC35-6 terminal.
CommunicationsShielded Cat 5 or better, no longer than 5 m (Managed mode).
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0
05

Worked ExamplesExample 1: off-grid home, Selectronic SP PRO, Managed

The loads in these examples are illustrative. Use the site's own load data and the current inverter documentation.

5.1Example 1: Off-Grid Home, Selectronic SP PRO, Managed

A single-phase off-grid home uses 15 kWh a day from the battery and needs 1.5 days of autonomy. The inverter is a Selectronic SP PRO SPMC482 (7500 W), running the LiFe² 5120S in Managed mode.

StepWorking
1. Energy15 kWh × 1.5 days = 22.5 kWh. 22.5 ÷ 4.096 kWh (80% DoD) = 5.5, so 6 modules.
2. Minimum for the inverterSPMC482, single phase: 3 modules. 6 is more than 3.
3. Charge currentThe SP PRO charges within the battery's limits: up to 600 A for 6 modules at 25 °C.
4. TemperatureAssumed between 20 and 45 °C, so the full rates apply. For a colder site, see step 4.
5. CabinetOne LiFe²-CAB6: 6 modules, 30.72 kWh, 625 A busbar. The inverter's DC current at 7500 W and 48 V is about 160 A, well within it.
6. Result6 × LiFe² 5120S in one LiFe²-CAB6: 24.6 kWh usable at 80% DoD.
AERL LiFe² 5120S · System Sizing GuideRev 1.0.0

5.2Example 2: Outdoor Cabinet, Victron MultiPlus-II, Managed

A single-phase off-grid cabin uses 10 kWh a day and needs one day of autonomy. The inverter is a Victron MultiPlus-II 48/5000/70-50 with a GX device. The battery must be outdoors.

StepWorking
1. Energy10 kWh ÷ 4.096 kWh = 2.4, so 3 modules.
2. Minimum for the inverterMultiPlus-II 48/5000/70-50, single-phase off-grid: 2 modules. 3 is more than 2.
3. Charge currentThe MultiPlus-II charger (70 A) charges within the battery's limits.
4. TemperatureAssumed between 20 and 45 °C, so the full rates apply. For a colder site, see step 4.
5. CabinetOne LiFe²-CAB4-OUTD: up to 4 modules, 250 A busbar. With 3 modules the busbar, not the modules (300 A), sets the cabinet's continuous current: 250 A. The inverter's DC current is about 100 A, within it.
6. Result3 × LiFe² 5120S in one LiFe²-CAB4-OUTD: 12.3 kWh usable, with room for a fourth module.

5.3Example 3: DC-Coupled Solar, Self-Managed

An off-grid site with an SMA Sunny Island SI 8.0H (single phase) uses 25 kWh a day, with one day of autonomy. Three CoolMax SRX 600/70-48 charge controllers (70 A each) charge the battery from PV. The battery runs Self-Managed.

StepWorking
1. Energy25 kWh ÷ 4.608 kWh (90% DoD) = 5.4, so 6 modules.
2. Minimum for the inverterSI 8.0H, single phase: 3 modules.
3. Charge currentThe three SRX controllers can deliver 210 A together. At 70 A per module this needs at least 3 modules. With 6 modules the limit for all charge sources together is 6 × 70 A = 420 A, so limit the Sunny Island's own charge current (from a generator) to 420 − 210 = 210 A.
4. TemperatureAssumed between 20 and 45 °C, so the full rates apply. For a colder site, see step 4.
5. CabinetOne LiFe²-CAB6 (625 A busbar).
6. Result6 × LiFe² 5120S in one LiFe²-CAB6: 27.6 kWh usable at 90% DoD.

For the PV array and the SRX settings, see the CoolMax SRX DC-Coupling Design Guide.

AERL LiFe² 5120S · System Sizing GuideRev 1.0.0
06

SupportRegister the warranty, design support, change log

6.1Register the Warranty

The LiFe² 5120S warranty is 5 years. Register the battery within 60 days of installation to extend it to 10 years: register at aerl.com.au/warranty-registration. LiFe² cabinets carry a 2-year warranty. Conditions apply: see the LiFe² Warranty Statement, at aerl.com.au.

6.2Design Support

For a design this guide does not cover, such as an unlisted inverter or a multi-cabinet bank, contact AERL support on 1800 950 865 or [email protected] with the inverter models, the load profile and the site conditions.

6.3Change Log

RevisionDateChange
1.0.011 / 2026First issue.

Thank You for Choosing AERL

If you have any questions or need support, contact AERL.

Sincerely,

The AERL Team

AERL Pty Ltd · 1/75 Bluestone Circuit, Seventeen Mile Rocks QLD 4073 · 1800 950 865 · [email protected] · aerl.com.au