AERL technical documentation

AERL LiFe² 5120S — Installation and Operation Manual Rev 2.0.2

34 pages

Download PDF Print
Download PDF· Rev 2.0.2 Installation and Operation Manual

AERL LiFe² 5120S

5.12 kWh LFP Battery and Battery Cabinets

AERL LiFe² 5120S
LiFe²-5120S · LiFe² battery cabinets Installation and Operation ManualRev 2.0.2, 8 Nov 2026
aerl.com.au © 2026 AERL Pty Ltd

Contents

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

Document

Revision2.0.2
Effective11 / 2026
AudienceSuitably qualified installers
ChemistryLiFePO4 (LFP)
Module5.12 kWh / 100 Ah, 51.2 V DC
ScalabilityUp to 64 modules in parallel
WarrantyLiFe² Warranty Statement
FormatA4 · 34 pages
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
01

Introduction

The LiFe² 5120S is a 5.12 kWh lithium iron phosphate (LFP) battery for off-grid and backup systems. It balances its cells actively and runs in two modes: Managed and Self-Managed. The module is a 19-inch rack-mount unit: install it in a standard 19-inch rack or in an AERL pre-wired battery cabinet.

Up to 64 LiFe² 5120S modules can be connected in parallel, for a system capacity of up to 327.68 kWh. With a supported inverter, the battery is managed over CAN bus (Managed mode) and falls back to Self-Managed mode automatically if communication with the inverter is lost. Without communication, the LiFe² 5120S works in Self-Managed mode with third-party power conversion equipment (PCE): hybrid inverters, battery chargers and MPPT solar charge controllers.

The LiFe² 5120S can be hot-swapped and has an integrated circuit breaker for isolation. The Battery Management System (BMS) monitors the breaker and can trip it electronically, in addition to the breaker's own overcurrent protection.

The battery discharges at temperatures down to −20 °C and charges down to −10 °C.

This manual covers the installation and operation of the LiFe² 5120S battery and the LiFe² battery cabinets.

02

Glossary

TermMeaning
BESSBattery Energy Storage System
BMSBattery Management System
DODDepth of Discharge
LEDLight Emitting Diode
LFPLithium Iron Phosphate (LiFePO4)
PCEPower Conversion Equipment (inverters, chargers and charge controllers)
SOCState of Charge
SOHState of Health
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
03

SafetyWarnings and cautions, transportation, handling, storage

Follow the safety requirements in this manual when installing, commissioning, operating and maintaining the product. Incorrect operation or handling can damage the product and other property, or cause injury or death to the operator or others.

When securing the product with screws or other fasteners, use the correct tools and tighten to the torque given in this manual or on the product label. Incorrect torque can make the product unstable or damage it.

Make sure you know how to use each tool correctly before you start, to prevent injury.

Read this manual first

Read this manual in full before installation, so that the product is installed and used safely and correctly.

3.1Warnings and Cautions

3.2Transportation

Ship LiFe² 5120S batteries with the terminals covered, to prevent contact with metal objects and short circuits. To comply with international transport regulations, the batteries are discharged to a low SOC before shipping.

Wherever possible, ship batteries in the original packaging, horizontal and firmly fastened to a pallet. Do not ship batteries on end, and do not stack more than six.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

3.3Handling

3.4Storage

3.5Long Term Storage Check

Check the voltage of LiFe² 5120S batteries that have been stored for 6 months or more:

  1. If the battery voltage is above 51.6 V, the battery is in good condition and does not need charging. Check it again every 3 months.
  2. If the battery voltage is below 51.6 V, charge the battery to prevent irreversible damage from low SOC: charge at 55 V DC and a constant 10 A for at least 30 minutes.

3.6Leaking Batteries

Stop using a damaged battery immediately, and dispose of it safely or return it to the manufacturer. A damaged battery can leak electrolyte, which may cause breathing difficulties, skin irritation and chemical burns. If you come into contact with electrolyte:

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

3.7Fire

A battery fire may occur if the battery is too close to a flame or the ambient temperature is unusually high. A burning battery may release carbon monoxide, carbon dioxide and other gases, and smoke.

In case of fire
  • Evacuate the area and call emergency services (000 in Australia).
  • Fight the fire only with a full-face self-contained breathing apparatus (SCBA) and full protective gear.
  • Use a dry chemical fire extinguisher to cool and extinguish the battery and stop the fire spreading.

3.8Wet Battery

If the battery has been submerged in water, stop using it immediately and contact AERL. If you must disconnect power, or you are in the same water as the battery, first put on rubber gloves and boots to protect yourself from electric shock.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
04

Product InformationIntroduction: LiFe² 5120S battery system

4.1Introduction: LiFe² 5120S Battery System

The LiFe² 5120S has an integrated Battery Management System (BMS) that monitors the battery continuously and protects it against harmful conditions.

The BMS provides:

The integrated circuit breaker is electronically controlled, so the BMS can isolate the battery quickly when it detects a fault or unsafe operating condition.

4.2LiFe² 5120S Battery Module & Box Contents

Each LiFe² 5120S battery is supplied with all the cables needed to install it in a LiFe² pre-wired battery cabinet.

#PartQty
1Termination Plug1
2Comms Cable1
3M6 × 16 Bolt4
LiFe² 5120S battery module.
Figure 4.1 LiFe² 5120S battery module.
Box contents: 1 termination plug, 2 comms cable, 3 M6 × 16 bolts.
Figure 4.2 Box contents: 1 termination plug, 2 comms cable, 3 M6 × 16 bolts.
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

4.3LiFe² 5120S Battery Module Interface and Status LEDs

The front-panel LEDs show the battery state (Status, Error and SOC) at a glance.

LiFe² 5120S front panel, interface and status LEDs.
Figure 4.3 LiFe² 5120S front panel, interface and status LEDs.
LetterLabelFunction
ACOMMInverter Comms
BOUTBattery Comms Out
CINBattery Comms In
DN/AError Indication
EN/ABattery Status
FN/ASOC Indicator
GON/OFFOn/Off Switch
HMCBCircuit Breaker
I+DC+ Port
J−DC− Port

4.4LiFe² 5120S Battery Module Specification

ParameterBattery specification
Part NumberLiFe²-5120S
Nominal Voltage51.2 V DC
Operating Voltage Range40.8 V DC to 58.4 V DC
Capacity5.12 kWh / 100 Ah
Depth of DischargeUp to 100%
Maximum Continuous Discharge Rate1C (@ 25 °C)
Maximum Continuous Discharge Current100 A (@ 25 °C)
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
ParameterBattery specification
Maximum Discharge Power5.12 kW
Peak Discharge Current200 A (10.24 kW, 5 s)
Maximum Continuous Charge C-Rate1C (@ 25 °C)
Maximum Continuous Charge Current100 A (@ 25 °C)
Peak Charge Current200 A (@ 25 °C)
Integrated Circuit Breaker2-pole, 125 A, 80 V DC
Lithium ChemistryLiFePO4 / LFP
Cell ConstructionPrismatic
Operating Temperature Range, ManagedCharge: −10 to 55 °C / Discharge: −20 to 55 °C
Operating Temperature Range, Self-ManagedCharge: 0 to 55 °C / Discharge: −5 to 55 °C
Operating HumidityUp to 95% (non-condensing)
BMS Over-Voltage Cell Level Protection3.65 V DC
BMS Under-Voltage Cell Level Protection2.55 V DC
BMS Over-Temperature Cut-Off56 °C
Short Circuit Current2000 A
Arc Flash Incident Energy (IEm at 45 cm)0.341 cal/cm²
Arc Flash Boundary (AFB)23.952 cm
Altitude< 2500 m
DC Connectors125 A Quick Connect
IP RatingIP20
Efficiency> 96%
CoolingNatural Convection
Scalability64 Batteries in Parallel
Series ConnectionNot Permitted
CommunicationsCAN 2.0A / RS485 / No Comms
Weight44 kg
Dimensions (W × H × D)440 × 134 × 480 mm
Warranty5 years; 10 years if registered within 60 days of installation. Conditions apply: see the LiFe² Warranty Statement
Certifications, CellUL 1973, UL 9540A, IEC 62619:2022, UN 38.3
Certifications, PackIEC 62619:2022, IEC 62040-1, UN 38.3, CE
Country of ManufacturePeople's Republic of China
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

4.5LiFe² Cabinet Specification

ParameterLiFe²-CAB6LiFe²-CAB10LiFe²-CAB4-OUTDLiFe²-CAB6-OUTDLiFe²-CAB10-OUTD
Dimensions (W × H × D)620 × 1270 × 600 mm620 × 1890 × 600 mm580 × 1380 × 400 mm680 × 1240 × 700 mm680 × 1800 × 700 mm
Fixing4 × wheels, 4 × feet4 × wheels, 4 × feet4 × bolt points, 4 × lift points4 × bolt points, 4 × lift points4 × bolt points, 4 × lift points
Max. Module Quantity6 (30.72 kWh)10 (51.20 kWh)4 (20.48 kWh)6 (30.72 kWh)10 (51.20 kWh)
Busbar Continuous Current Rating625 A1250 A250 A400 A600 A
Battery InterconnectionPre-wired quick connector, 4 AWG UL cablePre-wired quick connector, 4 AWG UL cablePre-wired quick connector, 4 AWG UL cablePre-wired quick connector, 4 AWG UL cablePre-wired quick connector, 4 AWG UL cable
DC Circuit BreakerNoneNoneNoneNoneNone
IP RatingIP20 (indoor)IP20 (indoor)IP55 (outdoor)IP55 (outdoor)IP55 (outdoor)
Weight91 kg128 kg52 kg135 kg142 kg
Warranty2 years2 years2 years2 years2 years

Cabinet warranty conditions: see the LiFe² Warranty Statement.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
LiFe²-CAB10 and LiFe²-CAB6 pre-wired battery cabinets.
Figure 4.4 LiFe²-CAB10 and LiFe²-CAB6 pre-wired battery cabinets.
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
05

InstallationInstallation location and environment, battery cabinets

This chapter sets out how to install the LiFe² battery and cabinets safely. Correct installation is essential for the system's life, efficiency and safe operation.

5.1Installation Location and Environment

Choose the installation location carefully. If you are not using a LiFe² battery cabinet, install the battery in a 19-inch data rack or another compliant, secure electrical enclosure. The IP20 cabinets (LiFe²-CAB6 and LiFe²-CAB10) are for indoor use only.

The location must be:

5.2Battery Cabinets

The LiFe² batteries fit a 600 mm deep 19-inch equipment rack. AERL's pre-wired cabinets hold 6 or 10 batteries indoors (LiFe²-CAB6, LiFe²-CAB10, IP20) and 4, 6 or 10 batteries outdoors (LiFe²-CAB4-OUTD, LiFe²-CAB6-OUTD, LiFe²-CAB10-OUTD, IP55).

The pre-wired cabinets save installation time and are the recommended solution.

If you design and build your own battery enclosure:

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
Notice

Use pre-assembled cables to connect the batteries to a custom cabinet busbar (or similar). Order them from AERL as part number AERL-BATT-CABLE-2.5.

5.3Battery Connections

The LiFe² 5120S has Exconn (non-keyed) connectors on its positive and negative terminals. To parallel several cabinets you may need additional power cables, combined through a DC busbar assembly or a DC combiner box. Use power cables of the same length throughout, so that every battery sees the same impedance.

5.4Tools

You need the following tools to install the LiFe² 5120S:

Installation tools.
Figure 5.1 Installation tools.

5.5Extra Accessories

  1. Inverter DC Cabling
  2. Cabinet PE Cable
  3. Communication Cable
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
Extra accessories.
Figure 5.2 Extra accessories.
Note

Check the local requirements for battery installations. They differ between countries and jurisdictions, and many require DC isolation between the battery cabinets and the inverter.

5.6Positioning the Cabinet

When the cabinet arrives, inspect it inside and out for damage. If you find any, contact your supplier.

Sections 5.6 and 5.7 describe the indoor cabinets (LiFe²-CAB6, LiFe²-CAB10), which have caster wheels and support feet. The outdoor cabinets have no wheels or feet: lift them by their four lift points and fix them through their four bolt points.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

5.6.1 Minimum cabinet clearances

Minimum clearances:

Minimum cabinet clearances (top view).
Figure 5.3 Minimum cabinet clearances (top view).

Indoors, leave at least 25 mm between the top of the cabinet and the ceiling.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

5.7Connecting Power Cables and Deploying the Support Feet

When the cabinet is in its final position, lower the load-bearing feet fully before you insert any batteries, so that the feet carry the weight and the wheels are off the floor.

The main DC busbar is behind the removable panel on the right side of the cabinet. Remove the internal securing screw and lift the panel off to reach the busbar. Torque all connections, then refit the panel.

Power Lug Torque: 15 N·m

Support feet and the DC power cables on the right side of the cabinet.
Figure 5.4 Support feet and the DC power cables on the right side of the cabinet.
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

5.8Inserting and Fastening Battery Modules

Starting at the bottom of the cabinet, slide the battery modules in one at a time until the cabinet is full or you have installed the number required. Secure each module with the supplied screws.

Module Bolt Torque: 3 N·m

Inserting and fastening the battery modules.
Figure 5.5 Inserting and fastening the battery modules.

5.9Cable Connection

5.9.1 Connecting the communications and protective earth

The first battery module in the chain is the master battery.

Insert the termination plug into the OUT port of the last battery in the chain.

Connect the PE to each battery module.

PE Torque: 3 N·m

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
Communications daisy chain, termination plug and protective earth.
Figure 5.6 Communications daisy chain, termination plug and protective earth.

5.10Connecting to Inverter

Important note

The LiFe² 5120S has a built-in 2-pole 125 A / 80 V DC breaker.

To comply with AS/NZS 5139, all live battery conductors must also pass through 2-pole MCCBs installed between the battery modules and the inverter or DC bus.

Connect the main DC cables to the inverter's positive and negative terminals as the inverter manufacturer instructs.

Cable legend:

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
Connecting a cabinet to the inverter.
Figure 5.7 Connecting a cabinet to the inverter.
Important note

The comms cable must be Cat 5 or higher.

Master Comms Port Pin-Out

PIN No.Definition
1NC
2NC
3NC
4CAN_H
5CAN_L
6NC
7RS485B
8RS485A
RJ45 pin numbering.
Figure 5.8 RJ45 pin numbering.
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

5.11Self-Managed Mode (No Comms)

In Self-Managed (No Comms) mode, the LiFe² 5120S runs without communication, with third-party charging sources whose charge settings can be configured. In this mode the LiFe² can replace a lead-acid battery.

The LiFe² 5120S starts in Managed (communication) mode by default.

Use Self-Managed mode when the inverter has no communication link to the battery (a no-comms or Self-Managed PCE). To switch to Self-Managed (No Comms) mode: with the battery on, double-press the ON/OFF button on the master battery. The SOC LEDs flash 3 times to confirm. The battery remembers the mode after a restart, so you set it once.

The battery switches back to Managed mode automatically when the communication cable between the inverter and the master battery is connected.

5.12Connecting Multiple Cabinets

If one cabinet does not provide enough storage, connect several cabinets in parallel.

5.12.1 Connecting communication cables between multiple cabinets

The diagram below shows how to connect the communication chain across several cabinets.

  1. From the OUT port of the last (bottom) battery in the first cabinet, run the communication cable through the pre-drilled hole to the IN port of the bottom battery in the second cabinet.
  2. From the second cabinet to the third, connect the top battery of the second cabinet to the top battery of the third.
  3. Continue the same alternating pattern (bottom to bottom, then top to top) for each further cabinet.

Insert the termination plug into the OUT port of the last module.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
Communication cables between multiple cabinets.
Figure 5.9 Communication cables between multiple cabinets.

5.12.2 Connecting parallel cabinets to the inverter

  1. Connect the PE cable.
  2. Connect the power cables of the paralleled cabinets to the DC combiner box or DC bus, and from there to the inverter.
  3. Connect the communication cable between the master battery and the inverter.

Cable legend:

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
Parallel cabinets connected to the inverter through a DC bus.
Figure 5.10 Parallel cabinets connected to the inverter through a DC bus.
Note
  1. Up to 64 LiFe² 5120S modules can be connected in parallel.
  2. Connect parallel cabinets through a DC bus or DC combiner box.
  3. Use DC power cables of the same length for all cabinets.
  4. The communication cable must be no longer than 5 m, and shielded Cat 5 or higher.
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
06

CommissioningLED Status, circuit breaker protection

6.1LED Status

The LiFe² 5120S LEDs show the status of the battery.

LEDStatusDescription
ErrorRed ONAn error has occurred.
ErrorOffThere are no active errors.
StatusGreen ONThe battery is active and can be charged and discharged.
StatusOffThe battery is not active.
SOC4 LEDs ON75–100% SOC
SOC3 LEDs ON50–75% SOC
SOC2 LEDs ON25–50% SOC
SOC1 LED ON0–25% SOC

6.2Circuit Breaker Protection

The integrated circuit breaker of the LiFe² 5120S:

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

6.3System Start-Up and Shut-Down Procedure

Before you power up the system, check the installation:

Start up the battery system as recommended by the PCE manufacturer and this manual, and in line with local and government safety requirements.

The ON/OFF button on the master battery.
Figure 6.1 The ON/OFF button on the master battery.
System start upSystem shutdown
1: Turn ON the DC breakers between the battery cabinet(s) and the inverter.1: Turn OFF the system AC isolators (if any).
2: Turn ON the battery module breakers.2: Turn OFF the system PV isolators (if any) and shut down the inverter.
3: Press the ON/OFF button on the master battery for 1 second to power up the system.3: Turn OFF the DC breakers between the battery cabinet(s) and the inverter.
4: Turn ON the system PV isolators (if any).4: Press and hold the ON/OFF button on the master battery for 3 seconds to power down the system.
5: Turn ON the system AC isolators (if any) and start the inverter.5: Check that the LEDs on all batteries are off, then turn OFF the battery module breakers.

6.4Charging and Discharging

The LiFe² 5120S discharges down to −20 °C and charges down to −10 °C.

The battery delivers 100 A continuously and 200 A peak for up to 5 seconds. Do not charge at more than 100 A.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

Charge to 100% SOC regularly, to keep the SOC accurate:

Important
  • If the battery shuts down automatically after a long period without charging, recharge it within 10 days to restore the SOC.
  • For an extended shutdown with no charging source, switch the battery off with its ON/OFF button and turn its circuit breaker off.

6.4.1 Initial system charging

LiFe² 5120S batteries are shipped at a low SOC, as international shipping regulations require.

When you first power up the system, charge it to 100% SOC to calibrate the SOC. This matters most in self-managed applications, where the connected PCE must learn the battery's SOC.

6.4.2 Maintaining accurate SOC in self-managed application

SOC drift is the error that builds up in the SOC calculation over time, from tolerances in the voltage and current measurements and in the capacity algorithm. Most systems reset this error when the battery reaches 100% SOC or enters float.

To limit SOC drift, the battery should reach float or 100% SOC regularly, ideally every 1 to 3 days:

  1. Size the solar array to charge the batteries to float or 100% even at the winter solstice.
  2. Install a backup charging source (grid or generator) for long periods of bad weather or high load.
  3. Check with the PCE manufacturer how accurate its SOC calculation is.
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

6.5Setting up Remote Monitoring

Remote monitoring is available through AERL Cloud with a Nexus Gateway, or through third-party inverter platforms.

Scan the QR code to learn how to connect your battery system.

QR code: Remote monitoring Connecting your battery system
Remote monitoring
Connecting your battery system
07

Maintenance

The battery itself needs no maintenance. Check the system regularly:

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
08

Adding Batteries to an Existing System

Additional LiFe² 5120S batteries can be added to an existing installation at any time during the warranty period. All batteries must be of the same type and part number. If you are unsure, contact AERL after-sales support.

New batteries can be added at any SOC or voltage. The system balances itself, bringing the new battery to the SOC and voltage of the existing bank.

In Self-Managed mode, update the battery capacity in all PCE settings.

Note

Different battery types or capacities cannot be mixed in a rack. All batteries in a rack must have the same type, part number and specification, unless AERL advises otherwise.

09

Recovering a Flat Battery

If a battery module reaches 0% SOC and its voltage falls below 40 V (over-discharge), recharge it in one of these ways:

  1. If the inverter still operates, charge the battery from the inverter.
  2. Connect a module at a higher voltage in parallel: it balances and charges the flat module automatically.
  3. If inverter charging is not possible, use a 48 V adjustable constant-current charger set to 54 V and no more than 10 A. Charge for at least 30 minutes.
Note

If a battery has shut down automatically after a long period without charging, recharge it within 10 days to restore a healthy SOC.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
10

Battery End of Life and Recycling

When a LiFe² 5120S battery reaches the end of its life:

  1. Return the battery to AERL for assessment.
  2. Batteries that can be refurbished are tested and refurbished for charitable, community or educational use.
  3. Batteries that cannot be refurbished are recycled, to recover as much material as possible.
AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
11

Battery Cycle Performance Characteristics

80% DOD cycling curve at different temperatures.
Figure 11.1 80% DOD cycling curve at different temperatures.

Capacity retention (%) against cycle count at 25 °C, 35 °C and 45 °C, 80% DOD. All curves start at 100% retention and trend down toward 70% retention: 25 °C at ~7000 cycles; 35 °C at ~5500 cycles; 45 °C at ~4500 cycles.

90% DOD cycling curve at different temperatures.
Figure 11.2 90% DOD cycling curve at different temperatures.

At 90% DOD, the 25 °C curve reaches ~70% retention at approximately 6000 cycles; 35 °C at ~5000 cycles; 45 °C at ~4000 cycles.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
100% DOD cycling curve at different temperatures.
Figure 11.3 100% DOD cycling curve at different temperatures.

At 100% DOD, the 25 °C curve reaches ~70% retention at approximately 5500 cycles; 35 °C at ~4500 cycles; 45 °C at ~3500 cycles.

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
12

Managed Battery Performance, Charge and Discharge

Charge limited C-rate map: temperature (°C) against SOC (%).
Figure 12.1 Charge limited C-rate map: temperature (°C) against SOC (%).

Permitted charge C-rate bands by temperature:

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2
Discharge limited C-rate map: temperature (°C) against SOC (%).
Figure 12.2 Discharge limited C-rate map: temperature (°C) against SOC (%).

Permitted discharge C-rate bands by temperature:

Thank You for Choosing AERL

If you have any questions or need support, contact AERL.

Sincerely,

The AERL Team

AERL Pty Ltd · 1/75 Bluestone Circuit, Seventeen Mile Rocks QLD 4073 · 1800 950 865 · [email protected] · aerl.com.au

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

Notes

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

Notes

AERL LiFe² 5120S · Installation and Operation ManualRev 2.0.2

Australian Energy Research Laboratories

Address

1/75 Bluestone Circuit
Seventeen Mile Rocks QLD 4073
Australia

Contact

[email protected]
[email protected]

aerl.com.au Phone1800 950 865