AERL technical documentation

AERL Nexus – Modbus TCP Protocol Rev 1.0.3

13 pages

Download PDF Print
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026
Download PDF· Rev 1.0.3
Modbus TCP Communications

AERL Nexus

Modbus TCP Communications Protocol
Doc · NEXUS-MODBUS-TCP
StandardModbus TCP
Port502
AccessRead-only
Function codes0x03 · 0x04
Unit IDs1 SP PRO · 2 LiFe²
Data types16 / 32-bit scaled integers
Word orderMSW first
DocumentNEXUS-MODBUS-TCP
Revision1.0.3
Effective09 / 2026
ProductAERL Nexus
AudienceIntegrators
Firmware1.15.1 and later
FormatA4 · 13 pages

Contents

01ConnectionTransport, function codes, unit IDs02
02Device DescriptorRegisters 0 to 127 of every unit03
03Register LayoutValue, quality and age registers, types, worked examples03
04Freshness and TimingRefresh rates, stale thresholds, sessions05
05Exception CodesModbus exception responses05
06Client ChecklistFive steps to a correct client05
07SP PRO InverterUnit 1, 96 fields and status codes06
08LiFe² Battery BankUnit 2, 55 fields11
09Battery ModulesPer-module blocks from register 204813
10Revision HistoryDocument revision log13
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 1 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026
Chapter 01

Connection

The AERL Nexus gateway publishes the data it has acquired from the connected Selectronic SP PRO inverter and AERL LiFe² battery bank over Modbus TCP. The interface is read-only. Values are served from the gateway's live cache; a Modbus read never triggers a request to the equipment. Every numeric value is a 16 or 32-bit scaled integer: no floating-point or 64-bit data type is needed in the client.

ItemValue
TransportModbus TCP, port 502, on the gateway's LAN address
Function codesFC03 and FC04 (identical data). All write functions are rejected with exception 01.
Registers per request1 to 125
Concurrent clientsUp to 16. Further connections are closed immediately.
Idle timeoutA connection that has sent no request for 10 s is closed. Poll at least that often, or reconnect for each poll cycle.
Register addressingZero-based protocol (PDU) addresses. In 1-based "4xxxx" notation add 40001 (FC03) or 30001 (FC04): address 256 is 40257.
Data typesINT16, UINT16, INT32, UINT32 and fixed-length ASCII or byte fields
Word orderMost-significant word first (ABCD) for all 32-bit values; signed values are two's complement

Unit IDs

Unit IDDevice
1SP PRO inverter
2Battery bank (LiFe²)

Each connected device is a separate Modbus unit ID with its own register space. A unit that is not assigned answers descriptor reads with an "unassigned" descriptor and returns exception 0B for its values. Unit IDs outside 1 to 32 return exception 0B. Confirm the profile and source identity of each unit at commissioning. Other equipment connected to the same gateway may be published on further unit IDs in a later revision of this document.

AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 2 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026
Chapter 02

Device Descriptor

Registers 0 to 127 of every unit. Read this block after every connection and whenever the session value changes. Registers not listed read 0.

RegisterContent
0Magic 0xA3E1
1Register map format identifier. Reads 3 for the map described in this document.
2 to 3Session identifier, UINT32. Changes on every gateway restart: discard cached values when it changes.
4 to 5Server heartbeat in seconds, UINT32. Shows that the Modbus service is running, not that the equipment is answering.
6 to 7Update sequence, UINT32, increments on every new reading and wraps
10Number of assigned units
11Unit capacity (32)
16Number of fields for this unit
17Number of module slots for this unit (80 for a battery, 0 otherwise)
18Layout identifier. Reads 1 for the layout described in this document.
19First value register (256)
20 to 21First module block (2048) and module block length (128)
22 to 23First quality register (1024) and first age register (1280)
641 if this unit is assigned, 0 if not
65Profile: 2 = LiFe², 3 = SP PRO
68 to 69Stale threshold in milliseconds, UINT32
72 to 87Label, 32 ASCII bytes
88 to 119Source identity, 64 ASCII bytes
Chapter 03

Register Layout

Every field F of a unit has three fixed locations: its value, a quality register and an age. The field tables list all three addresses for every field.

ItemAddressContent
ValueFrom 256At the fixed address in the field tables: 1 register for a 16-bit value, 2 for a 32-bit value, more for text
Quality1024 + F1 register, UINT16 (see below)
Age1280 + 2 × F2 registers, UINT32: milliseconds since the gateway received the value. 0xFFFFFFFF when never received.
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 3 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026

Register Layout, Continued

Quality

Quality is a bit field: 1 = supported, 2 = received, 4 = valid, 8 = stale, 16 = out of range. Use a value only when its quality register reads 7.

QualityMeaning
0Field is not defined for this unit
1Field exists, nothing received yet
3Received, but no valid value
7Valid and fresh. The only value to act on.
15Last valid value, older than the stale threshold
19Received, but outside the range of the register
11, 27As 3 and 19, and older than the stale threshold

Types

TypeEncoding
INT16 / UINT16One register. Engineering value = register × scale.
INT32 / UINT32Two registers, most-significant word first. Engineering value = raw × scale. Read both registers in one request.
ASCII nn characters, two per register, first character in the high byte, zero padded.
BYTES nn raw bytes as sent by the equipment, two per register. Not text.

Scales are fixed per field and listed in the field tables; there are no offsets. A value register reads 0 whenever its quality is not 7 or 15, so 0 is never evidence of a real zero: always read the quality register with the value.

No Data

A read that includes value registers returns exception 0B when none of the fields in it has been received since the gateway started, and for every value read of a unit that is not assigned. Treat 0B as a communication failure: keep the last value and mark it bad. A read that includes at least one received field is answered normally; any other field in it that has not been received reads 0 with quality 1. Descriptor, quality and age registers always answer.

Worked examples

SP PRO battery voltage (unit 1, field 0): INT16 at 256, scale 0.1. A reading of 0x020E = 526 is 52.6 V. Use it only while register 1024 reads 7; its age is the UINT32 at 1280 to 1281.

Battery bank current (unit 2, field 7): INT16 at 263, scale 0.1. A reading of 0xFF71 = −143 is −14.3 A. Total energy charged (field 41) is the UINT32 at 318 to 319: 0x0000 0x30D4 = 12500 is 1250000 Wh.

Reading a whole unit: the SP PRO's 96 values occupy registers 256 to 358 (one read), their quality registers 1024 to 1119 (one read) and their ages 1280 to 1471 (two reads). Each read returns a consistent snapshot; values within one read may have different ages.

AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 4 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026
Chapter 04

Freshness and Timing

DataTypical refreshStale threshold
SP PRO (all registers)Every 45 to 60 s. A full sweep of the inverter takes about 30 s.80 s
Battery bank1 to 5 s (limits, voltage, current, SOC, alarms); up to 10 s for names and cell addresses150 s
Battery modulesEach module about once per minute150 s

Each unit has one stale threshold, reported in registers 68 to 69 of its descriptor; the values above are typical. For fast values such as battery voltage, current and SOC, apply your own tighter limit to the age registers.

Age counts from the moment the gateway received the value. When the equipment stops responding, values keep their last reading, age keeps climbing and the stale bit sets when the threshold is passed.

Any restart of the gateway closes open TCP sessions and starts a new session identifier. Reconnect, re-read the descriptor and treat all previous values as unknown. Values return 0B until each device reports again.

Chapter 05

Exception Codes

CodeNameReturned when
01Illegal functionWrite function, or unsupported function
02Illegal data addressAddress range not mapped
03Illegal data valueRegister count 0 or more than 125
0BGateway target failed to respondUnit ID not in 1 to 32, unit not assigned, or no data yet (see No data)
Chapter 06

Client Checklist

  1. Connect to port 502 and read registers 0 to 63 and 64 to 127 of each unit you use; confirm magic 0xA3E1, map format 3, layout 1 and assigned = 1.
  2. Map each value you need at its fixed address with the type and scale from the field tables, and map its quality register beside it.
  3. Use a value only when its quality register reads 7; treat 15 as stale and 1 as not yet received. Treat exception 0B as no data, never as 0.
  4. Watch registers 2 to 3: a new session means the gateway restarted; re-read the descriptor and clear cached values.
  5. Poll at your own rate; polling faster does not refresh the equipment faster. Keep the connection open only if you poll at least every 10 s, otherwise reconnect for each cycle.

Questions about the data, the equipment behind it, or additional points you would like exposed: contact AERL support.

AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 5 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026
Chapter 07

SP PRO Inverter (Unit 1)

Profile 3. All read-only registers of the Selectronic SP PRO Modbus map are included. Source is the SP PRO's own register number. Power is in W (not kW), and battery power and current carry the SP PRO's native signs: verify against a known charge and discharge before using signs in alarms. Values are for the accessed inverter, not automatically a site total.

IDValueTypeScaleUnitFieldQualityAgeSourceValues
0256INT160.1Vbattery_voltage102412808000
1257INT160.1%battery_soc102512828001
2258INT1610Wbattery_power102612848002
3259INT160.1Abattery_current102712868003
4260INT1610Wac_load_power102812888004
5261INT160.1Vac_load_voltage102912908005
6262INT160.1Hzac_load_frequency103012928006
7263INT160.1kWhac_load_energy103112948007
8264INT1610Wac_source_power103212968008
9265INT160.1Vac_source_voltage103312988009
10266INT160.1Aac_source_current103413008010
11267INT160.1Hzac_source_frequency103513028011
12268INT1610VArac_source_reactive103613048012
13269INT160.1kWhac_source_input_energy103713068013
14270INT160.1kWhac_source_export_energy103813088014
15271INT1610Wac_inverter_power103913108015
16272INT160.1Aac_inverter_current104013128016
17273INT1610VArinverter_reactive104113148017
18274UINT161output_status1042131680180 = Off; 1 = Econo; 2 = On; 3 = Sync
19275INT160.1°Cbattery_temperature104313188019
20276INT160.1°Ctransformer_temperature104413208020
21277INT160.1°Cheatsink_temperature104513228021
22278UINT161solar_hybrid_priority_active1046132480220 = None; other = a priority is active
23279INT1610Wac_source_input_limit104713268023
24280INT1610Wgrid_export_limit104813288024
25281INT1610Wcharge_limit104913308025
26282INT1610Wac_load_support_limit105013328026
27283UINT161battery_charging_status1051133480270 = Normal charge; 1 = Override charge; 2 = Charger Off; 3 = Renewable charge; 4 = Restricted charge
28284UINT161inverter_shutdown_status1052133680280 = Not Active; 1 = Active
29285UINT161grid_disconnect_status1053133880290 = Not Active; 1 = Active
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 6 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026

SP PRO Inverter (Unit 1), Continued

IDValueTypeScaleUnitFieldQualityAgeSourceValues
30286INT1610Wactive_power_override_target105413408030
31287UINT161soc_shutdown_recovery_active1055134280310 = Not Active; 1 = Active
32288UINT161passcode_status105613448039
33289UINT161output_digital_control_1_status1057134680400 = inactive; 1 = active
34290UINT161output_digital_control_2_status1058134880410 = inactive; 1 = active
35291UINT161output_digital_control_3_status1059135080420 = inactive; 1 = active
36292UINT161output_relay_1_status1060135280430 = inactive; 1 = active
37293UINT161output_relay_2_status1061135480440 = inactive; 1 = active
38294UINT161output_relay_3_status1062135680450 = inactive; 1 = active
39295UINT161output_relay_4_status1063135880460 = inactive; 1 = active
40296UINT161inputs_digital_control_1_status1064136080470 = inactive; 1 = active
41297UINT161inputs_digital_control_2_status1065136280480 = inactive; 1 = active
42298UINT161inputs_digital_control_3_status1066136480490 = inactive; 1 = active
43299UINT161inputs_digital_control_4_status1067136680500 = inactive; 1 = active
44300UINT161ac_source_status106813688059See status codes
45301UINT161generator_status106913708060See status codes
46302UINT161generator_start_reason107013728061See status codes
47303UINT161generator_running_reason107113748062See status codes
48304UINT161attention_required_01072137680630 = None; other: see status codes
49305UINT161attention_required_11073137880640 = None; other: see status codes
50306UINT161attention_required_21074138080650 = None; other: see status codes
51307UINT161attention_required_31075138280660 = None; other: see status codes
52308UINT161attention_required_41076138480670 = None; other: see status codes
53309UINT161attention_required_51077138680680 = None; other: see status codes
54310UINT161attention_required_61078138880690 = None; other: see status codes
55311UINT161attention_required_71079139080700 = None; other: see status codes
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 7 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026

SP PRO Inverter (Unit 1), Continued

IDValueTypeScaleUnitFieldQualityAgeSourceValues
56312UINT161attention_required_81080139280710 = None; other: see status codes
57313UINT161attention_required_91081139480720 = None; other: see status codes
58314UINT161attention_required_101082139680730 = None; other: see status codes
59315UINT161attention_required_111083139880740 = None; other: see status codes
60316UINT161attention_required_121084140080750 = None; other: see status codes
61317UINT161attention_required_131085140280760 = None; other: see status codes
62318UINT161attention_required_141086140480770 = None; other: see status codes
63319UINT161attention_required_151087140680780 = None; other: see status codes
64320UINT161attention_required_161088140880790 = None; other: see status codes
65321UINT161attention_required_171089141080800 = None; other: see status codes
66322UINT161attention_required_181090141280810 = None; other: see status codes
67323UINT161attention_required_191091141480820 = None; other: see status codes
68324UINT161charging_mode1092141680830 = Initial; 1 = Bulk; 2 = Absorb; 3 = Short Term Float; 4 = Initialise Float; 5 = Equalise; 6 = LongTerm Float
69325INT1610Wshunt_1_power109314188084
70326INT1610Wshunt_2_power109414208085
71327INT1610W5_minute_battery_load109514228086
72328INT1610W15_minute_battery_load109614248087
73329UINT160.1%ac_coupled_solar_target109714268088
74330INT1610Wac_coupled_solar_1_power109814288089
75331INT1610Wac_coupled_solar_2_power109914308090
76332INT1610Wac_coupled_solar_3_power110014328091
77333INT1610Wac_coupled_solar_4_power110114348092
78334INT1610Wac_coupled_solar_5_power110214368093
79335INT160.1Atarget_charge_current110314388094
80336INT160.1Vtarget_charge_voltage110414408095
81337UINT160.1%fan_speed110514428096
82338UINT160.1kWhbattery_input_energy110614448097
83339UINT160.1kWhbattery_output_energy110714468098
84340UINT160.1kWhac_coupled_input_energy110814488099
85341UINT161minminutes_of_ac_source110914508100
86342UINT161hsp_pro_total_run_time111014528101
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 8 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026

SP PRO Inverter (Unit 1), Continued

IDValueTypeScaleUnitFieldQualityAgeSourceValues
87343UINT161unit_serial_number_low111114548102
88344UINT161unit_serial_number_high111214568103
89345UINT161sp_pro_software_version111314588104Version × 100 (530 = 5.30)
90346UINT161comms_card_acc_software_version111414608105Version × 100 (530 = 5.30)
91347INT1610Wac_inverter_power_worker_1111514628107
92348INT1610Wac_inverter_power_worker_2111614648108
93349INT1610Wac_inverter_power_worker_3111714668109
94350INT1610Wac_inverter_power_phase111814688110
95351ASCII 16serial_number111914708102 + 8103

SP PRO Status Codes

Code lists for the SP PRO status registers whose Values cell says "see status codes", as defined in Selectronic document OI0010 Rev 13. The generator start reason (8061) and running reason (8062) share one list.

AC source status (8059)

CodeMeaningCodeMeaning
0Nothing5Charger Locked Out
1Earth Neutral Fault6Ac Source is present
2Ac Input Locked Out7Ac Source is in tolerance
3Inverter Locked Out8Ac Source is too high for frequency
4Grid Capacity Active9Disconnected DRM

Generator status (8060)

CodeMeaningCodeMeaning
0Not running6Generator starting
1Is running7Retry pause
2Low fuel8Generator is stopping
3No fuel9Disabled
4Fault active10AC present
5Not available
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 9 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026

SP PRO Status Codes, Continued

Generator start reason (8061) and running reason (8062)

CodeMeaningCodeMeaning
0Not running15Gen Min Run Time Expired
1Front panel Gen Request16Gen LockOut Active
2Remote Gen Request17Gen Float HoldOn Active
3Time Schedule Gen Request18Gen is Cooling Down
4Temperature Gen Request19Gen Confirmed Start
5Impending shutdown Gen Request20Gen Manual Start
6Sync fault21Gen ACVolts Present
7SoC Gen Request22Gen is Disabled
8Battery volts Gen Request23Gen Start Open Sync
9Battery mid point Gen Request24Gen Equalise HoldOn Active
10Equalise Gen Request25Gen Start Battery Power
11AcLoad Gen Request26Gen Grid Failed So Gen is Available
12Exercise Gen Request27Gen Grid Returned Stop Gen
13Gen is available28Gen ReEvaluate Gen Available
14Gen Fault Stop29Gen is Warming Up
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 10 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026
Chapter 08

LiFe² Battery Bank (Unit 2)

Profile 2. Field names follow the battery's CAN messages; Source is the CAN message the value comes from. Cell addresses are BYTES and name or serial parts are ASCII; serial_number and battery_name are assembled from their parts. Alarm and warning fields are 0 or 1. The three "alarm battery" fields are only refreshed while a module is in alarm: before the first alarm they read "not yet received" (a read of only these fields returns exception 0B), and after an alarm clears they keep the last report and go stale, so apply the quality rule before acting on them.

IDValueTypeScaleUnitFieldQualityAgeSource
0256UINT160.1Vlimits.charge_voltage_limit10241280CAN 0x351
1257UINT160.1Alimits.charge_current_limit10251282CAN 0x351
2258UINT160.1Alimits.discharge_current_limit10261284CAN 0x351
3259UINT160.1Vlimits.discharge_voltage_limit10271286CAN 0x351
4260UINT161%soc_soh.soc10281288CAN 0x355
5261UINT161%soc_soh.soh10291290CAN 0x355
6262UINT160.01Vactual_values.voltage10301292CAN 0x356
7263INT160.1Aactual_values.current10311294CAN 0x356
8264INT160.1°Cactual_values.temperature10321296CAN 0x356
9265UINT161alarm_warning.cell_high_voltage_alarm10331298CAN 0x359
10266UINT161alarm_warning.cell_low_voltage_alarm10341300CAN 0x359
11267UINT161alarm_warning.high_temperature_alarm10351302CAN 0x359
12268UINT161alarm_warning.low_temperature_alarm10361304CAN 0x359
13269UINT161alarm_warning.high_discharge_current_alarm10371306CAN 0x359
14270UINT161alarm_warning.high_charge_current_alarm10381308CAN 0x359
15271UINT161alarm_warning.bms_internal_alarm10391310CAN 0x359
16272UINT161alarm_warning.cell_imbalance_alarm10401312CAN 0x359
17273UINT161alarm_warning.high_voltage_warning10411314CAN 0x359
18274UINT161alarm_warning.low_voltage_warning10421316CAN 0x359
19275UINT161alarm_warning.high_temperature_warning10431318CAN 0x359
20276UINT161alarm_warning.low_temperature_warning10441320CAN 0x359
21277UINT161alarm_warning.high_discharge_current_warning10451322CAN 0x359
22278UINT161alarm_warning.high_charge_current_warning10461324CAN 0x359
23279UINT161alarm_warning.bms_internal_warning10471326CAN 0x359
24280UINT161alarm_warning.cell_imbalance_warning10481328CAN 0x359
25281UINT161charge_control.force_charge_flag10491330CAN 0x35C
26282ASCII 8manufacturer_id.manufacturer_name10501332CAN 0x35E
27286ASCII 8name_1.battery_name_part110511334CAN 0x701
28290ASCII 8name_2.battery_name_part210521336CAN 0x702
29294UINT161counts.batteries_working10531338CAN 0x703
30295UINT161counts.batteries_charge_open10541340CAN 0x703
31296UINT161counts.batteries_discharge_open10551342CAN 0x703
32297UINT161counts.batteries_offline10561344CAN 0x703
33298UINT161mVcell_extremes.min_cell_voltage10571346CAN 0x704
34299UINT161mVcell_extremes.max_cell_voltage10581348CAN 0x704
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 11 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026

LiFe² Battery Bank (Unit 2), Continued

IDValueTypeScaleUnitFieldQualityAgeSource
35300INT161°Ccell_extremes.min_cell_temperature10591350CAN 0x704
36301INT161°Ccell_extremes.max_cell_temperature10601352CAN 0x704
37302BYTES 8min_voltage_address.min_voltage_address10611354CAN 0x705
38306BYTES 8max_voltage_address.max_voltage_address10621356CAN 0x706
39310BYTES 8min_temperature_address.min_temperature_address10631358CAN 0x707
40314BYTES 8max_temperature_address.max_temperature_address10641360CAN 0x708
41318UINT32100Whenergy.total_energy_charged10651362CAN 0x709
42320UINT32100Whenergy.total_energy_discharged10661364CAN 0x709
43322UINT161Ahinstalled_capacity.installed_capacity10671366CAN 0x70A
44323BYTES 8alarm_battery_1.alarm_state_battery_110681368CAN 0x70B
45327BYTES 8alarm_battery_1_address.alarm_battery_1_address10691370CAN 0x70C
46331BYTES 8alarm_battery_2.alarm_state_battery_210701372CAN 0x70D
47335BYTES 8alarm_battery_2_address.alarm_battery_2_address10711374CAN 0x70E
48339BYTES 8alarm_battery_3.alarm_state_battery_310721376CAN 0x70F
49343BYTES 8alarm_battery_3_address.alarm_battery_3_address10731378CAN 0x710
50347ASCII 8serial_number_1.serial_number_part110741380CAN 0x711
51351ASCII 8serial_number_2.serial_number_part210751382CAN 0x712
52355ASCII 8serial_number_3.serial_number_part310761384CAN 0x713
53359ASCII 24serial_number10771386assembled
54371ASCII 16battery_name10781388assembled
AERL Nexus · Modbus TCP Protocol · Rev 1.0.3 Page 12 / 13 © 2026 AERL Pty Ltd
AERL Nexus
Modbus TCP Protocol Rev 1.0.3 24 Sep 2026
Chapter 09

Battery Modules

Module M (1 to 80) has its own block of 128 registers starting at 2048 + 128 × (M − 1). Register 0 of the block is the module number and register 1 the number of fields (13). The Value, Quality and Age columns below are offsets from the start of the block. Modules beyond the installed count read quality 1, and reads of their values return exception 0B. A module's values refresh together.

IDValueTypeScaleUnitFieldQualityAgeSource
016INT161°Cmax_cell_temp6488module response
117INT161°Cmin_cell_temp6590module response
218INT161°Cavg_temp6692module response
319UINT161max_temp_sensor_index6794module response
420UINT161min_temp_sensor_index6896module response
521UINT160.1Vtotal_voltage6998module response
622INT160.1Acurrent70100module response
723UINT161state71102module response
824UINT160.001Vmax_cell_voltage72104module response
925UINT160.001Vmin_cell_voltage73106module response
1026UINT160.1Vpack_voltage74108module response
1127UINT161max_voltage_cell_index75110module response
1228UINT161min_voltage_cell_index76112module response
Chapter 10

Revision History

Rev.DateChange
1.0.017/09/2026Initial release: SP PRO inverter and LiFe² battery bank
1.0.118/09/2026Register map changed to fixed 16 and 32-bit scaled values with separate quality and age registers. Replaces the Rev 1.0.0 register map.
1.0.222/09/2026Added SP PRO status code lists and notes (OI0010 Rev 13). No register changes.
1.0.324/09/2026Reads of values with no data return exception 0B instead of 0 (see No data). Requires Nexus firmware 1.15.1 or later; earlier firmware reads 0 with quality 1. No address changes.