title: "AERL Nexus – Modbus TCP Protocol"
revision: "1.0.3"
publisher: AERL (Australian Energy Research Laboratories)
url: https://www.aerl.com.au/docs/nexus-modbus-tcp-protocol
pdf: https://www.aerl.com.au/documents/protocols/AERL_Nexus_Modbus_TCP_Protocol_REV_103.pdf
description: "Modbus TCP register map for reading AERL Nexus and connected-device data from a SCADA system or EMS (Nexus firmware 1.15.1 and later)."
---

# AERL Nexus – Modbus TCP Protocol

*Rev 1.0.3. Markdown copy of the AERL document at https://www.aerl.com.au/docs/nexus-modbus-tcp-protocol; the PDF (https://www.aerl.com.au/documents/protocols/AERL_Nexus_Modbus_TCP_Protocol_REV_103.pdf) is the controlled version.*

Modbus TCP Communications

# AERL Nexus

Modbus TCP Communications Protocol

**Doc · NEXUS-MODBUS-TCP**

Standard Modbus TCP

Port 502

Access Read-only

Function codes 0x03 · 0x04

Unit IDs 1 SP PRO · 2 LiFe²

Data types 16 / 32-bit scaled integers

Word order MSW first

| | |
|---|---|
| Document | NEXUS-MODBUS-TCP |
| Revision | 1.0.3 |
| Effective | 09 / 2026 |
| Product | AERL Nexus |
| Audience | Integrators |
| Firmware | 1.15.1 and later |
| Format | A4 · 13 pages |

## Chapter 01 Connection

The AERL Nexus gateway publishes the data it has acquired from the connected Selectronic SP PRO inverter and AERL LiFe² battery bank over **Modbus TCP**. The interface is read-only. Values are served from the gateway's live cache; a Modbus read never triggers a request to the equipment. Every numeric value is a 16 or 32-bit scaled integer: no floating-point or 64-bit data type is needed in the client.

| Item | Value |
|---|---|
| Transport | Modbus TCP, port **502**, on the gateway's LAN address |
| Function codes | FC03 and FC04 (identical data). All write functions are rejected with exception 01. |
| Registers per request | 1 to 125 |
| Concurrent clients | Up to 16. Further connections are closed immediately. |
| Idle timeout | A connection that has sent no request for 10 s is closed. Poll at least that often, or reconnect for each poll cycle. |
| Register addressing | Zero-based protocol (PDU) addresses. In 1-based "4xxxx" notation add 40001 (FC03) or 30001 (FC04): address 256 is 40257. |
| Data types | INT16, UINT16, INT32, UINT32 and fixed-length ASCII or byte fields |
| Word order | Most-significant word first (ABCD) for all 32-bit values; signed values are two's complement |

### Unit IDs

| Unit ID | Device |
|---|---|
| 1 | SP PRO inverter |
| 2 | Battery bank (LiFe²) |

Each connected device is a separate Modbus **unit ID** with its own register space. A unit that is not assigned answers descriptor reads with an "unassigned" descriptor and returns exception 0B for its values. Unit IDs outside 1 to 32 return exception 0B. Confirm the profile and source identity of each unit at commissioning. Other equipment connected to the same gateway may be published on further unit IDs in a later revision of this document.

## Chapter 02 Device Descriptor

Registers 0 to 127 of every unit. Read this block after every connection and whenever the session value changes. Registers not listed read 0.

| Register | Content |
|---|---|
| 0 | Magic 0xA3E1 |
| 1 | Register map format identifier. Reads 3 for the map described in this document. |
| 2 to 3 | Session identifier, UINT32. Changes on every gateway restart: discard cached values when it changes. |
| 4 to 5 | Server heartbeat in seconds, UINT32. Shows that the Modbus service is running, not that the equipment is answering. |
| 6 to 7 | Update sequence, UINT32, increments on every new reading and wraps |
| 10 | Number of assigned units |
| 11 | Unit capacity (32) |
| 16 | Number of fields for this unit |
| 17 | Number of module slots for this unit (80 for a battery, 0 otherwise) |
| 18 | Layout identifier. Reads 1 for the layout described in this document. |
| 19 | First value register (256) |
| 20 to 21 | First module block (2048) and module block length (128) |
| 22 to 23 | First quality register (1024) and first age register (1280) |
| 64 | 1 if this unit is assigned, 0 if not |
| 65 | Profile: 2 = LiFe², 3 = SP PRO |
| 68 to 69 | Stale threshold in milliseconds, UINT32 |
| 72 to 87 | Label, 32 ASCII bytes |
| 88 to 119 | Source identity, 64 ASCII bytes |

## Chapter 03 Register Layout

Every field *F* of a unit has three fixed locations: its **value**, a **quality** register and an **age**. The field tables list all three addresses for every field.

| Item | Address | Content |
|---|---|---|
| Value | From 256 | At the fixed address in the field tables: 1 register for a 16-bit value, 2 for a 32-bit value, more for text |
| Quality | 1024 + F | 1 register, UINT16 (see below) |
| Age | 1280 + 2 × F | 2 registers, UINT32: milliseconds since the gateway received the value. 0xFFFFFFFF when never received. |

### Register Layout, Continued

### Quality

Quality is a bit field: 1 = supported, 2 = received, 4 = valid, 8 = stale, 16 = out of range. Use a value only when its quality register reads **7**.

| Quality | Meaning |
|---|---|
| 0 | Field is not defined for this unit |
| 1 | Field exists, nothing received yet |
| 3 | Received, but no valid value |
| 7 | **Valid and fresh. The only value to act on.** |
| 15 | Last valid value, older than the stale threshold |
| 19 | Received, but outside the range of the register |
| 11, 27 | As 3 and 19, and older than the stale threshold |

### Types

| Type | Encoding |
|---|---|
| INT16 / UINT16 | One register. Engineering value = register × scale. |
| INT32 / UINT32 | Two registers, most-significant word first. Engineering value = raw × scale. Read both registers in one request. |
| ASCII *n* | *n* characters, two per register, first character in the high byte, zero padded. |
| BYTES *n* | *n* raw bytes as sent by the equipment, two per register. Not text. |

Scales are fixed per field and listed in the field tables; there are no offsets. A value register reads 0 whenever its quality is not 7 or 15, so **0 is never evidence of a real zero**: always read the quality register with the value.

### No Data

A read that includes value registers returns **exception 0B** when none of the fields in it has been received since the gateway started, and for every value read of a unit that is not assigned. Treat 0B as a communication failure: keep the last value and mark it bad. A read that includes at least one received field is answered normally; any other field in it that has not been received reads 0 with quality 1. Descriptor, quality and age registers always answer.

> Worked examples
>
> SP PRO battery voltage (unit 1, field 0): INT16 at **256**, scale 0.1. A reading of 0x020E = 526 is 52.6 V. Use it only while register **1024** reads 7; its age is the UINT32 at 1280 to 1281.
>
> Battery bank current (unit 2, field 7): INT16 at **263**, scale 0.1. A reading of 0xFF71 = −143 is −14.3 A. Total energy charged (field 41) is the UINT32 at **318 to 319**: 0x0000 0x30D4 = 12500 is 1250000 Wh.
>
> Reading a whole unit: the SP PRO's 96 values occupy registers 256 to 358 (one read), their quality registers 1024 to 1119 (one read) and their ages 1280 to 1471 (two reads). Each read returns a consistent snapshot; values within one read may have different ages.

## Chapter 04 Freshness and Timing

| Data | Typical refresh | Stale threshold |
|---|---|---|
| SP PRO (all registers) | Every 45 to 60 s. A full sweep of the inverter takes about 30 s. | 80 s |
| Battery bank | 1 to 5 s (limits, voltage, current, SOC, alarms); up to 10 s for names and cell addresses | 150 s |
| Battery modules | Each module about once per minute | 150 s |

Each unit has one stale threshold, reported in registers 68 to 69 of its descriptor; the values above are typical. For fast values such as battery voltage, current and SOC, apply your own tighter limit to the age registers.

Age counts from the moment the gateway received the value. When the equipment stops responding, values keep their last reading, age keeps climbing and the stale bit sets when the threshold is passed.

Any restart of the gateway closes open TCP sessions and starts a new session identifier. Reconnect, re-read the descriptor and treat all previous values as unknown. Values return 0B until each device reports again.

## Chapter 05 Exception Codes

| Code | Name | Returned when |
|---|---|---|
| 01 | Illegal function | Write function, or unsupported function |
| 02 | Illegal data address | Address range not mapped |
| 03 | Illegal data value | Register count 0 or more than 125 |
| 0B | Gateway target failed to respond | Unit ID not in 1 to 32, unit not assigned, or no data yet (see No data) |

## Chapter 06 Client Checklist

1. Connect to port 502 and read registers 0 to 63 and 64 to 127 of each unit you use; confirm magic 0xA3E1 , map format 3, layout 1 and *assigned* = 1.
2. Map each value you need at its fixed address with the type and scale from the field tables, and map its quality register beside it.
3. Use a value only when its quality register reads **7** ; treat 15 as stale and 1 as not yet received. Treat exception 0B as no data, never as 0.
4. Watch registers 2 to 3: a new session means the gateway restarted; re-read the descriptor and clear cached values.
5. Poll at your own rate; polling faster does not refresh the equipment faster. Keep the connection open only if you poll at least every 10 s, otherwise reconnect for each cycle.

Questions about the data, the equipment behind it, or additional points you would like exposed: contact AERL support.

## Chapter 07 SP PRO Inverter (Unit 1)

Profile 3. All read-only registers of the Selectronic SP PRO Modbus map are included. **Source** is the SP PRO's own register number. Power is in W (not kW), and battery power and current carry the SP PRO's native signs: verify against a known charge and discharge before using signs in alarms. Values are for the accessed inverter, not automatically a site total.

| ID | Value | Type | Scale | Unit | Field | Quality | Age | Source | Values |
|---|---|---|---|---|---|---|---|---|---|
| 0 | 256 | INT16 | 0.1 | V | battery_voltage | 1024 | 1280 | 8000 |  |
| 1 | 257 | INT16 | 0.1 | % | battery_soc | 1025 | 1282 | 8001 |  |
| 2 | 258 | INT16 | 10 | W | battery_power | 1026 | 1284 | 8002 |  |
| 3 | 259 | INT16 | 0.1 | A | battery_current | 1027 | 1286 | 8003 |  |
| 4 | 260 | INT16 | 10 | W | ac_load_power | 1028 | 1288 | 8004 |  |
| 5 | 261 | INT16 | 0.1 | V | ac_load_voltage | 1029 | 1290 | 8005 |  |
| 6 | 262 | INT16 | 0.1 | Hz | ac_load_frequency | 1030 | 1292 | 8006 |  |
| 7 | 263 | INT16 | 0.1 | kWh | ac_load_energy | 1031 | 1294 | 8007 |  |
| 8 | 264 | INT16 | 10 | W | ac_source_power | 1032 | 1296 | 8008 |  |
| 9 | 265 | INT16 | 0.1 | V | ac_source_voltage | 1033 | 1298 | 8009 |  |
| 10 | 266 | INT16 | 0.1 | A | ac_source_current | 1034 | 1300 | 8010 |  |
| 11 | 267 | INT16 | 0.1 | Hz | ac_source_frequency | 1035 | 1302 | 8011 |  |
| 12 | 268 | INT16 | 10 | VAr | ac_source_reactive | 1036 | 1304 | 8012 |  |
| 13 | 269 | INT16 | 0.1 | kWh | ac_source_input_energy | 1037 | 1306 | 8013 |  |
| 14 | 270 | INT16 | 0.1 | kWh | ac_source_export_energy | 1038 | 1308 | 8014 |  |
| 15 | 271 | INT16 | 10 | W | ac_inverter_power | 1039 | 1310 | 8015 |  |
| 16 | 272 | INT16 | 0.1 | A | ac_inverter_current | 1040 | 1312 | 8016 |  |
| 17 | 273 | INT16 | 10 | VAr | inverter_reactive | 1041 | 1314 | 8017 |  |
| 18 | 274 | UINT16 | 1 |  | output_status | 1042 | 1316 | 8018 | 0 = Off; 1 = Econo; 2 = On; 3 = Sync |
| 19 | 275 | INT16 | 0.1 | °C | battery_temperature | 1043 | 1318 | 8019 |  |
| 20 | 276 | INT16 | 0.1 | °C | transformer_temperature | 1044 | 1320 | 8020 |  |
| 21 | 277 | INT16 | 0.1 | °C | heatsink_temperature | 1045 | 1322 | 8021 |  |
| 22 | 278 | UINT16 | 1 |  | solar_hybrid_priority_active | 1046 | 1324 | 8022 | 0 = None; other = a priority is active |
| 23 | 279 | INT16 | 10 | W | ac_source_input_limit | 1047 | 1326 | 8023 |  |
| 24 | 280 | INT16 | 10 | W | grid_export_limit | 1048 | 1328 | 8024 |  |
| 25 | 281 | INT16 | 10 | W | charge_limit | 1049 | 1330 | 8025 |  |
| 26 | 282 | INT16 | 10 | W | ac_load_support_limit | 1050 | 1332 | 8026 |  |
| 27 | 283 | UINT16 | 1 |  | battery_charging_status | 1051 | 1334 | 8027 | 0 = Normal charge; 1 = Override charge; 2 = Charger Off; 3 = Renewable charge; 4 = Restricted charge |
| 28 | 284 | UINT16 | 1 |  | inverter_shutdown_status | 1052 | 1336 | 8028 | 0 = Not Active; 1 = Active |
| 29 | 285 | UINT16 | 1 |  | grid_disconnect_status | 1053 | 1338 | 8029 | 0 = Not Active; 1 = Active |

### SP PRO Inverter (Unit 1), Continued

| ID | Value | Type | Scale | Unit | Field | Quality | Age | Source | Values |
|---|---|---|---|---|---|---|---|---|---|
| 30 | 286 | INT16 | 10 | W | active_power_override_target | 1054 | 1340 | 8030 |  |
| 31 | 287 | UINT16 | 1 |  | soc_shutdown_recovery_active | 1055 | 1342 | 8031 | 0 = Not Active; 1 = Active |
| 32 | 288 | UINT16 | 1 |  | passcode_status | 1056 | 1344 | 8039 |  |
| 33 | 289 | UINT16 | 1 |  | output_digital_control_1_status | 1057 | 1346 | 8040 | 0 = inactive; 1 = active |
| 34 | 290 | UINT16 | 1 |  | output_digital_control_2_status | 1058 | 1348 | 8041 | 0 = inactive; 1 = active |
| 35 | 291 | UINT16 | 1 |  | output_digital_control_3_status | 1059 | 1350 | 8042 | 0 = inactive; 1 = active |
| 36 | 292 | UINT16 | 1 |  | output_relay_1_status | 1060 | 1352 | 8043 | 0 = inactive; 1 = active |
| 37 | 293 | UINT16 | 1 |  | output_relay_2_status | 1061 | 1354 | 8044 | 0 = inactive; 1 = active |
| 38 | 294 | UINT16 | 1 |  | output_relay_3_status | 1062 | 1356 | 8045 | 0 = inactive; 1 = active |
| 39 | 295 | UINT16 | 1 |  | output_relay_4_status | 1063 | 1358 | 8046 | 0 = inactive; 1 = active |
| 40 | 296 | UINT16 | 1 |  | inputs_digital_control_1_status | 1064 | 1360 | 8047 | 0 = inactive; 1 = active |
| 41 | 297 | UINT16 | 1 |  | inputs_digital_control_2_status | 1065 | 1362 | 8048 | 0 = inactive; 1 = active |
| 42 | 298 | UINT16 | 1 |  | inputs_digital_control_3_status | 1066 | 1364 | 8049 | 0 = inactive; 1 = active |
| 43 | 299 | UINT16 | 1 |  | inputs_digital_control_4_status | 1067 | 1366 | 8050 | 0 = inactive; 1 = active |
| 44 | 300 | UINT16 | 1 |  | ac_source_status | 1068 | 1368 | 8059 | See status codes |
| 45 | 301 | UINT16 | 1 |  | generator_status | 1069 | 1370 | 8060 | See status codes |
| 46 | 302 | UINT16 | 1 |  | generator_start_reason | 1070 | 1372 | 8061 | See status codes |
| 47 | 303 | UINT16 | 1 |  | generator_running_reason | 1071 | 1374 | 8062 | See status codes |
| 48 | 304 | UINT16 | 1 |  | attention_required_0 | 1072 | 1376 | 8063 | 0 = None; other: see status codes |
| 49 | 305 | UINT16 | 1 |  | attention_required_1 | 1073 | 1378 | 8064 | 0 = None; other: see status codes |
| 50 | 306 | UINT16 | 1 |  | attention_required_2 | 1074 | 1380 | 8065 | 0 = None; other: see status codes |
| 51 | 307 | UINT16 | 1 |  | attention_required_3 | 1075 | 1382 | 8066 | 0 = None; other: see status codes |
| 52 | 308 | UINT16 | 1 |  | attention_required_4 | 1076 | 1384 | 8067 | 0 = None; other: see status codes |
| 53 | 309 | UINT16 | 1 |  | attention_required_5 | 1077 | 1386 | 8068 | 0 = None; other: see status codes |
| 54 | 310 | UINT16 | 1 |  | attention_required_6 | 1078 | 1388 | 8069 | 0 = None; other: see status codes |
| 55 | 311 | UINT16 | 1 |  | attention_required_7 | 1079 | 1390 | 8070 | 0 = None; other: see status codes |

### SP PRO Inverter (Unit 1), Continued

| ID | Value | Type | Scale | Unit | Field | Quality | Age | Source | Values |
|---|---|---|---|---|---|---|---|---|---|
| 56 | 312 | UINT16 | 1 |  | attention_required_8 | 1080 | 1392 | 8071 | 0 = None; other: see status codes |
| 57 | 313 | UINT16 | 1 |  | attention_required_9 | 1081 | 1394 | 8072 | 0 = None; other: see status codes |
| 58 | 314 | UINT16 | 1 |  | attention_required_10 | 1082 | 1396 | 8073 | 0 = None; other: see status codes |
| 59 | 315 | UINT16 | 1 |  | attention_required_11 | 1083 | 1398 | 8074 | 0 = None; other: see status codes |
| 60 | 316 | UINT16 | 1 |  | attention_required_12 | 1084 | 1400 | 8075 | 0 = None; other: see status codes |
| 61 | 317 | UINT16 | 1 |  | attention_required_13 | 1085 | 1402 | 8076 | 0 = None; other: see status codes |
| 62 | 318 | UINT16 | 1 |  | attention_required_14 | 1086 | 1404 | 8077 | 0 = None; other: see status codes |
| 63 | 319 | UINT16 | 1 |  | attention_required_15 | 1087 | 1406 | 8078 | 0 = None; other: see status codes |
| 64 | 320 | UINT16 | 1 |  | attention_required_16 | 1088 | 1408 | 8079 | 0 = None; other: see status codes |
| 65 | 321 | UINT16 | 1 |  | attention_required_17 | 1089 | 1410 | 8080 | 0 = None; other: see status codes |
| 66 | 322 | UINT16 | 1 |  | attention_required_18 | 1090 | 1412 | 8081 | 0 = None; other: see status codes |
| 67 | 323 | UINT16 | 1 |  | attention_required_19 | 1091 | 1414 | 8082 | 0 = None; other: see status codes |
| 68 | 324 | UINT16 | 1 |  | charging_mode | 1092 | 1416 | 8083 | 0 = Initial; 1 = Bulk; 2 = Absorb; 3 = Short Term Float; 4 = Initialise Float; 5 = Equalise; 6 = LongTerm Float |
| 69 | 325 | INT16 | 10 | W | shunt_1_power | 1093 | 1418 | 8084 |  |
| 70 | 326 | INT16 | 10 | W | shunt_2_power | 1094 | 1420 | 8085 |  |
| 71 | 327 | INT16 | 10 | W | 5_minute_battery_load | 1095 | 1422 | 8086 |  |
| 72 | 328 | INT16 | 10 | W | 15_minute_battery_load | 1096 | 1424 | 8087 |  |
| 73 | 329 | UINT16 | 0.1 | % | ac_coupled_solar_target | 1097 | 1426 | 8088 |  |
| 74 | 330 | INT16 | 10 | W | ac_coupled_solar_1_power | 1098 | 1428 | 8089 |  |
| 75 | 331 | INT16 | 10 | W | ac_coupled_solar_2_power | 1099 | 1430 | 8090 |  |
| 76 | 332 | INT16 | 10 | W | ac_coupled_solar_3_power | 1100 | 1432 | 8091 |  |
| 77 | 333 | INT16 | 10 | W | ac_coupled_solar_4_power | 1101 | 1434 | 8092 |  |
| 78 | 334 | INT16 | 10 | W | ac_coupled_solar_5_power | 1102 | 1436 | 8093 |  |
| 79 | 335 | INT16 | 0.1 | A | target_charge_current | 1103 | 1438 | 8094 |  |
| 80 | 336 | INT16 | 0.1 | V | target_charge_voltage | 1104 | 1440 | 8095 |  |
| 81 | 337 | UINT16 | 0.1 | % | fan_speed | 1105 | 1442 | 8096 |  |
| 82 | 338 | UINT16 | 0.1 | kWh | battery_input_energy | 1106 | 1444 | 8097 |  |
| 83 | 339 | UINT16 | 0.1 | kWh | battery_output_energy | 1107 | 1446 | 8098 |  |
| 84 | 340 | UINT16 | 0.1 | kWh | ac_coupled_input_energy | 1108 | 1448 | 8099 |  |
| 85 | 341 | UINT16 | 1 | min | minutes_of_ac_source | 1109 | 1450 | 8100 |  |
| 86 | 342 | UINT16 | 1 | h | sp_pro_total_run_time | 1110 | 1452 | 8101 |  |

### SP PRO Inverter (Unit 1), Continued

| ID | Value | Type | Scale | Unit | Field | Quality | Age | Source | Values |
|---|---|---|---|---|---|---|---|---|---|
| 87 | 343 | UINT16 | 1 |  | unit_serial_number_low | 1111 | 1454 | 8102 |  |
| 88 | 344 | UINT16 | 1 |  | unit_serial_number_high | 1112 | 1456 | 8103 |  |
| 89 | 345 | UINT16 | 1 |  | sp_pro_software_version | 1113 | 1458 | 8104 | Version × 100 (530 = 5.30) |
| 90 | 346 | UINT16 | 1 |  | comms_card_acc_software_version | 1114 | 1460 | 8105 | Version × 100 (530 = 5.30) |
| 91 | 347 | INT16 | 10 | W | ac_inverter_power_worker_1 | 1115 | 1462 | 8107 |  |
| 92 | 348 | INT16 | 10 | W | ac_inverter_power_worker_2 | 1116 | 1464 | 8108 |  |
| 93 | 349 | INT16 | 10 | W | ac_inverter_power_worker_3 | 1117 | 1466 | 8109 |  |
| 94 | 350 | INT16 | 10 | W | ac_inverter_power_phase | 1118 | 1468 | 8110 |  |
| 95 | 351 | ASCII 16 |  |  | serial_number | 1119 | 1470 | 8102 + 8103 |  |

### SP PRO Status Codes

Code lists for the SP PRO status registers whose **Values** cell says "see status codes", as defined in Selectronic document OI0010 Rev 13. The generator start reason (8061) and running reason (8062) share one list.

#### AC source status (8059)

| Code | Meaning | Code | Meaning |
|---|---|---|---|
| 0 | Nothing | 5 | Charger Locked Out |
| 1 | Earth Neutral Fault | 6 | Ac Source is present |
| 2 | Ac Input Locked Out | 7 | Ac Source is in tolerance |
| 3 | Inverter Locked Out | 8 | Ac Source is too high for frequency |
| 4 | Grid Capacity Active | 9 | Disconnected DRM |

#### Generator status (8060)

| Code | Meaning | Code | Meaning |
|---|---|---|---|
| 0 | Not running | 6 | Generator starting |
| 1 | Is running | 7 | Retry pause |
| 2 | Low fuel | 8 | Generator is stopping |
| 3 | No fuel | 9 | Disabled |
| 4 | Fault active | 10 | AC present |
| 5 | Not available |  |  |

### SP PRO Status Codes, Continued

#### Generator start reason (8061) and running reason (8062)

| Code | Meaning | Code | Meaning |
|---|---|---|---|
| 0 | Not running | 15 | Gen Min Run Time Expired |
| 1 | Front panel Gen Request | 16 | Gen LockOut Active |
| 2 | Remote Gen Request | 17 | Gen Float HoldOn Active |
| 3 | Time Schedule Gen Request | 18 | Gen is Cooling Down |
| 4 | Temperature Gen Request | 19 | Gen Confirmed Start |
| 5 | Impending shutdown Gen Request | 20 | Gen Manual Start |
| 6 | Sync fault | 21 | Gen ACVolts Present |
| 7 | SoC Gen Request | 22 | Gen is Disabled |
| 8 | Battery volts Gen Request | 23 | Gen Start Open Sync |
| 9 | Battery mid point Gen Request | 24 | Gen Equalise HoldOn Active |
| 10 | Equalise Gen Request | 25 | Gen Start Battery Power |
| 11 | AcLoad Gen Request | 26 | Gen Grid Failed So Gen is Available |
| 12 | Exercise Gen Request | 27 | Gen Grid Returned Stop Gen |
| 13 | Gen is available | 28 | Gen ReEvaluate Gen Available |
| 14 | Gen Fault Stop | 29 | Gen is Warming Up |

- **Attention required (8063 to 8082).** A packed list, not a bit map: active service codes fill the slots from 0 upward, and when a code clears the later entries move up. If a slot reads 0 every later slot is also 0, so read until the first 0. The service codes are defined and published by Selectronic, not by AERL; contact Selectronic for the code list.
- **Software versions (8104, 8105).** Major version × 100 + minor version: 530 is version 5.30.
- **Worker and phase power (8107 to 8110).** Reported only by inverters with comms card software 5.20 or later. On an older card these four fields keep quality 1, and a read of only these fields returns exception 0B.

## Chapter 08 LiFe² Battery Bank (Unit 2)

Profile 2. Field names follow the battery's CAN messages; **Source** is the CAN message the value comes from. Cell addresses are BYTES and name or serial parts are ASCII; *serial_number* and *battery_name* are assembled from their parts. Alarm and warning fields are 0 or 1. The three "alarm battery" fields are only refreshed while a module is in alarm: before the first alarm they read "not yet received" (a read of only these fields returns exception 0B), and after an alarm clears they keep the last report and go stale, so apply the quality rule before acting on them.

| ID | Value | Type | Scale | Unit | Field | Quality | Age | Source |
|---|---|---|---|---|---|---|---|---|
| 0 | 256 | UINT16 | 0.1 | V | limits.charge_voltage_limit | 1024 | 1280 | CAN 0x351 |
| 1 | 257 | UINT16 | 0.1 | A | limits.charge_current_limit | 1025 | 1282 | CAN 0x351 |
| 2 | 258 | UINT16 | 0.1 | A | limits.discharge_current_limit | 1026 | 1284 | CAN 0x351 |
| 3 | 259 | UINT16 | 0.1 | V | limits.discharge_voltage_limit | 1027 | 1286 | CAN 0x351 |
| 4 | 260 | UINT16 | 1 | % | soc_soh.soc | 1028 | 1288 | CAN 0x355 |
| 5 | 261 | UINT16 | 1 | % | soc_soh.soh | 1029 | 1290 | CAN 0x355 |
| 6 | 262 | UINT16 | 0.01 | V | actual_values.voltage | 1030 | 1292 | CAN 0x356 |
| 7 | 263 | INT16 | 0.1 | A | actual_values.current | 1031 | 1294 | CAN 0x356 |
| 8 | 264 | INT16 | 0.1 | °C | actual_values.temperature | 1032 | 1296 | CAN 0x356 |
| 9 | 265 | UINT16 | 1 |  | alarm_warning.cell_high_voltage_alarm | 1033 | 1298 | CAN 0x359 |
| 10 | 266 | UINT16 | 1 |  | alarm_warning.cell_low_voltage_alarm | 1034 | 1300 | CAN 0x359 |
| 11 | 267 | UINT16 | 1 |  | alarm_warning.high_temperature_alarm | 1035 | 1302 | CAN 0x359 |
| 12 | 268 | UINT16 | 1 |  | alarm_warning.low_temperature_alarm | 1036 | 1304 | CAN 0x359 |
| 13 | 269 | UINT16 | 1 |  | alarm_warning.high_discharge_current_alarm | 1037 | 1306 | CAN 0x359 |
| 14 | 270 | UINT16 | 1 |  | alarm_warning.high_charge_current_alarm | 1038 | 1308 | CAN 0x359 |
| 15 | 271 | UINT16 | 1 |  | alarm_warning.bms_internal_alarm | 1039 | 1310 | CAN 0x359 |
| 16 | 272 | UINT16 | 1 |  | alarm_warning.cell_imbalance_alarm | 1040 | 1312 | CAN 0x359 |
| 17 | 273 | UINT16 | 1 |  | alarm_warning.high_voltage_warning | 1041 | 1314 | CAN 0x359 |
| 18 | 274 | UINT16 | 1 |  | alarm_warning.low_voltage_warning | 1042 | 1316 | CAN 0x359 |
| 19 | 275 | UINT16 | 1 |  | alarm_warning.high_temperature_warning | 1043 | 1318 | CAN 0x359 |
| 20 | 276 | UINT16 | 1 |  | alarm_warning.low_temperature_warning | 1044 | 1320 | CAN 0x359 |
| 21 | 277 | UINT16 | 1 |  | alarm_warning.high_discharge_current_warning | 1045 | 1322 | CAN 0x359 |
| 22 | 278 | UINT16 | 1 |  | alarm_warning.high_charge_current_warning | 1046 | 1324 | CAN 0x359 |
| 23 | 279 | UINT16 | 1 |  | alarm_warning.bms_internal_warning | 1047 | 1326 | CAN 0x359 |
| 24 | 280 | UINT16 | 1 |  | alarm_warning.cell_imbalance_warning | 1048 | 1328 | CAN 0x359 |
| 25 | 281 | UINT16 | 1 |  | charge_control.force_charge_flag | 1049 | 1330 | CAN 0x35C |
| 26 | 282 | ASCII 8 |  |  | manufacturer_id.manufacturer_name | 1050 | 1332 | CAN 0x35E |
| 27 | 286 | ASCII 8 |  |  | name_1.battery_name_part1 | 1051 | 1334 | CAN 0x701 |
| 28 | 290 | ASCII 8 |  |  | name_2.battery_name_part2 | 1052 | 1336 | CAN 0x702 |
| 29 | 294 | UINT16 | 1 |  | counts.batteries_working | 1053 | 1338 | CAN 0x703 |
| 30 | 295 | UINT16 | 1 |  | counts.batteries_charge_open | 1054 | 1340 | CAN 0x703 |
| 31 | 296 | UINT16 | 1 |  | counts.batteries_discharge_open | 1055 | 1342 | CAN 0x703 |
| 32 | 297 | UINT16 | 1 |  | counts.batteries_offline | 1056 | 1344 | CAN 0x703 |
| 33 | 298 | UINT16 | 1 | mV | cell_extremes.min_cell_voltage | 1057 | 1346 | CAN 0x704 |
| 34 | 299 | UINT16 | 1 | mV | cell_extremes.max_cell_voltage | 1058 | 1348 | CAN 0x704 |

### LiFe² Battery Bank (Unit 2), Continued

| ID | Value | Type | Scale | Unit | Field | Quality | Age | Source |
|---|---|---|---|---|---|---|---|---|
| 35 | 300 | INT16 | 1 | °C | cell_extremes.min_cell_temperature | 1059 | 1350 | CAN 0x704 |
| 36 | 301 | INT16 | 1 | °C | cell_extremes.max_cell_temperature | 1060 | 1352 | CAN 0x704 |
| 37 | 302 | BYTES 8 |  |  | min_voltage_address.min_voltage_address | 1061 | 1354 | CAN 0x705 |
| 38 | 306 | BYTES 8 |  |  | max_voltage_address.max_voltage_address | 1062 | 1356 | CAN 0x706 |
| 39 | 310 | BYTES 8 |  |  | min_temperature_address.min_temperature_address | 1063 | 1358 | CAN 0x707 |
| 40 | 314 | BYTES 8 |  |  | max_temperature_address.max_temperature_address | 1064 | 1360 | CAN 0x708 |
| 41 | 318 | UINT32 | 100 | Wh | energy.total_energy_charged | 1065 | 1362 | CAN 0x709 |
| 42 | 320 | UINT32 | 100 | Wh | energy.total_energy_discharged | 1066 | 1364 | CAN 0x709 |
| 43 | 322 | UINT16 | 1 | Ah | installed_capacity.installed_capacity | 1067 | 1366 | CAN 0x70A |
| 44 | 323 | BYTES 8 |  |  | alarm_battery_1.alarm_state_battery_1 | 1068 | 1368 | CAN 0x70B |
| 45 | 327 | BYTES 8 |  |  | alarm_battery_1_address.alarm_battery_1_address | 1069 | 1370 | CAN 0x70C |
| 46 | 331 | BYTES 8 |  |  | alarm_battery_2.alarm_state_battery_2 | 1070 | 1372 | CAN 0x70D |
| 47 | 335 | BYTES 8 |  |  | alarm_battery_2_address.alarm_battery_2_address | 1071 | 1374 | CAN 0x70E |
| 48 | 339 | BYTES 8 |  |  | alarm_battery_3.alarm_state_battery_3 | 1072 | 1376 | CAN 0x70F |
| 49 | 343 | BYTES 8 |  |  | alarm_battery_3_address.alarm_battery_3_address | 1073 | 1378 | CAN 0x710 |
| 50 | 347 | ASCII 8 |  |  | serial_number_1.serial_number_part1 | 1074 | 1380 | CAN 0x711 |
| 51 | 351 | ASCII 8 |  |  | serial_number_2.serial_number_part2 | 1075 | 1382 | CAN 0x712 |
| 52 | 355 | ASCII 8 |  |  | serial_number_3.serial_number_part3 | 1076 | 1384 | CAN 0x713 |
| 53 | 359 | ASCII 24 |  |  | serial_number | 1077 | 1386 | assembled |
| 54 | 371 | ASCII 16 |  |  | battery_name | 1078 | 1388 | assembled |

## Chapter 09 Battery Modules

Module *M* (1 to 80) has its own block of 128 registers starting at **2048 + 128 × (M − 1)**. Register 0 of the block is the module number and register 1 the number of fields (13). The **Value**, **Quality** and **Age** columns below are offsets from the start of the block. Modules beyond the installed count read quality 1, and reads of their values return exception 0B. A module's values refresh together.

| ID | Value | Type | Scale | Unit | Field | Quality | Age | Source |
|---|---|---|---|---|---|---|---|---|
| 0 | 16 | INT16 | 1 | °C | max_cell_temp | 64 | 88 | module response |
| 1 | 17 | INT16 | 1 | °C | min_cell_temp | 65 | 90 | module response |
| 2 | 18 | INT16 | 1 | °C | avg_temp | 66 | 92 | module response |
| 3 | 19 | UINT16 | 1 |  | max_temp_sensor_index | 67 | 94 | module response |
| 4 | 20 | UINT16 | 1 |  | min_temp_sensor_index | 68 | 96 | module response |
| 5 | 21 | UINT16 | 0.1 | V | total_voltage | 69 | 98 | module response |
| 6 | 22 | INT16 | 0.1 | A | current | 70 | 100 | module response |
| 7 | 23 | UINT16 | 1 |  | state | 71 | 102 | module response |
| 8 | 24 | UINT16 | 0.001 | V | max_cell_voltage | 72 | 104 | module response |
| 9 | 25 | UINT16 | 0.001 | V | min_cell_voltage | 73 | 106 | module response |
| 10 | 26 | UINT16 | 0.1 | V | pack_voltage | 74 | 108 | module response |
| 11 | 27 | UINT16 | 1 |  | max_voltage_cell_index | 75 | 110 | module response |
| 12 | 28 | UINT16 | 1 |  | min_voltage_cell_index | 76 | 112 | module response |

- **Example.** Module 3 starts at 2048 + 128 × 2 = 2304. Its *current* (field 6) is the INT16 at **2326** , scale 0.1, with quality at **2374** and age at **2404** .
- **State.** The module's operating state word as reported by the BMS (2 = normal operation). Cell indexes are zero-based within the module.
- **Not in this map.** Per-module serial numbers, per-module state of health and a per-module alarm bit field are not provided by the battery's module protocol. Use the bank-level serial, SOH and alarm fields, the three "alarm battery" fields (which name the alarming module's address) and each module's *state* .

## Chapter 10 Revision History

| Rev. | Date | Change |
|---|---|---|
| 1.0.0 | 17/09/2026 | Initial release: SP PRO inverter and LiFe² battery bank |
| 1.0.1 | 18/09/2026 | Register map changed to fixed 16 and 32-bit scaled values with separate quality and age registers. Replaces the Rev 1.0.0 register map. |
| 1.0.2 | 22/09/2026 | Added SP PRO status code lists and notes (OI0010 Rev 13). No register changes. |
| 1.0.3 | 24/09/2026 | Reads of values with no data return exception 0B instead of 0 (see No data). Requires Nexus firmware 1.15.1 or later; earlier firmware reads 0 with quality 1. No address changes. |