AERL technical documentation

Tanami HV — Installation and Operating Manual Rev 1.0.0

31 pages

Download PDF Print
Download PDF· Rev 1.0.0 Installation and Operating Manual

Tanami HV

Installation and Operating Manual

Tanami HV
Tanami-HV Installation and Operating ManualRev 1.0.0, 16 Nov 2026
aerl.com.au © 2026 AERL Pty Ltd

Contents

Tanami HV · Installation and Operating ManualRev 1.0.0

Document

Revision1.0.0
Effective11 / 2026
AudienceLicensed electrical workers
ChemistryLiFePO4 (LFP)
Module8.06 kWh / 105 Ah, 76.8 V DC
System6–9 modules, 460.8–691.2 V DC nominal
ScalabilityUp to 16 systems in parallel
WarrantyTanami HV Warranty Statement
FormatA4 · 31 pages
Tanami HV · Installation and Operating ManualRev 1.0.0
01

Introduction

The Tanami HV is a high-voltage lithium iron phosphate (LFP) battery for commercial and industrial energy storage. A Tanami system is one power distribution unit (Tanami-PDU) and six to nine 8.06 kWh battery modules (Tanami-M8.06) connected in series, for 48.38–72.58 kWh at 460.8–691.2 V DC nominal. It connects to a high-voltage hybrid or battery inverter, or to an energy management system (EMS), over CAN, RS485, Modbus RTU or Modbus TCP.

The PDU holds the battery management system (BMS), the DC circuit breaker, the ON/OFF button and the status LEDs. It also has control connections for an air-conditioner, an emergency stop and fire suppression, two dry-contact outputs, and a parallel link that connects up to 16 systems.

The system is supplied in one of two enclosures:

The battery charges at temperatures down to −10 °C and discharges down to −20 °C. It can black-start an off-grid inverter.

This manual covers the installation, commissioning, operation and maintenance of the Tanami system in both enclosures. Where a step differs between the indoor rack and the outdoor cabinet, the manual says so.

High voltage

A Tanami system operates at up to 788 V DC. Only licensed electrical workers trained in high-voltage DC battery systems may install, commission, maintain or service it.

Tanami HV · Installation and Operating ManualRev 1.0.0
02

Glossary

TermMeaning
BMSBattery Management System
EMSEnergy Management System
HVACHeating, Ventilation and Air-Conditioning
LFPLithium Iron Phosphate (LiFePO4)
MCBMiniature Circuit Breaker (here: the PDU's DC breaker)
PDUPower Distribution Unit: the Tanami's high-voltage control box, with the BMS
PEProtective Earth
SOCState of Charge
Tanami HV · Installation and Operating ManualRev 1.0.0
03

SafetyWarnings and cautions, transportation, handling

Follow the safety requirements in this manual when installing, commissioning, operating and maintaining the product. Incorrect operation or handling can damage the product and other property, or cause injury or death to the operator or others.

When securing the product with screws or other fasteners, use the correct tools and tighten to the torque given in this manual or on the product label. Incorrect torque can make the product unstable or damage it.

Make sure you know how to use each tool correctly before you start, to prevent injury.

Read this manual first

Read this manual in full before installation, so that the product is installed and used safely and correctly.

3.1Warnings and Cautions

Tanami HV · Installation and Operating ManualRev 1.0.0

3.2Transportation

Ship battery modules in their original packaging, horizontal and firmly fastened to a pallet, with the terminals covered. Batteries are shipped at a reduced SOC to comply with transport regulations.

Move the outdoor cabinet only with a forklift through the forklift pockets in its base, or with a crane on its four lifting eyes. Ship and move the cabinet without modules installed; empty, it weighs about 450 kg.

3.3Handling

3.4Storing the Battery

3.5Leaking Batteries

Stop using a damaged battery immediately, and dispose of it safely or return it to AERL. A damaged battery can leak electrolyte, which may cause breathing difficulties, skin irritation and chemical burns. If you come into contact with electrolyte:

Tanami HV · Installation and Operating ManualRev 1.0.0

3.6Fire

A battery fire may occur if the battery is too close to a flame or the ambient temperature is unusually high. A burning battery may release carbon monoxide, carbon dioxide and other gases, and smoke. The outdoor cabinet has an overpressure relief valve on each side; keep clear of them.

In case of fire
  • Evacuate the area and call emergency services (000 in Australia).
  • Fight the fire only with a full-face self-contained breathing apparatus (SCBA) and full protective gear.
  • Use a dry chemical fire extinguisher to cool and extinguish the battery and stop the fire spreading.

3.7Wet Battery

If the battery has been submerged in water, stop using it immediately and contact AERL. If you must disconnect power, or you are in the same water as the battery, first put on rubber gloves and boots to protect yourself from electric shock.

Tanami HV · Installation and Operating ManualRev 1.0.0
04

Product InformationSystem overview, box contents, battery module interfaces

4.1System Overview

A Tanami system has three parts:

PartPart numberDescription
Battery moduleTanami-M8.068.06 kWh, 76.8 V DC LFP module. Six to nine per system, connected in series.
Power distribution unitTanami-PDUBMS, DC circuit breaker and system connections. One per system.
EnclosureTanami-RACK9 or Tanami-CAB9-OUTDIndoor rack (6–9 modules) or outdoor cabinet (9 modules).
Tanami-CAB9-OUTD outdoor cabinet with nine modules and the PDU, door open.
Figure 4.1 Tanami-CAB9-OUTD outdoor cabinet with nine modules and the PDU, door open.
Tanami HV · Installation and Operating ManualRev 1.0.0

4.2Box Contents

Each battery module is packed with:

ItemQuantity
Tanami-M8.06 battery module1
Communication cable A (module to module)1
Battery cable A (module to module, black to orange)1

Each PDU is packed with:

ItemQuantity
Tanami-PDU1
Battery cable B (module next to the PDU, − to PDU B−)1
Battery cable C (last module in the string, + to PDU B+)1
Communication cable B (PDU to first module)1
Termination resistor, blue (last module COM 1)1
Termination resistor, black (PDU OUT)1
Screws (modules and PDU into the enclosure)40

4.3Battery Module Interfaces

Tanami-M8.06 front panel.
Figure 4.2 Tanami-M8.06 front panel.
Tanami HV · Installation and Operating ManualRev 1.0.0
PositionLabelFunction
A−Battery negative
B+Battery positive
CCOM 1Communication port (to the next module along the chain, or the blue termination resistor)
DCOM 2Communication port (from the PDU or the previous module in the chain)

4.4PDU Interfaces

Tanami-PDU front panel.
Figure 4.3 Tanami-PDU front panel.
PositionLabelFunction
AP−System negative (to the inverter)
BP+System positive (to the inverter)
CCAN/RS485CAN or RS485 to the inverter or EMS
DTCP/IPModbus TCP to the inverter or EMS
EOUTParallel link out
FINParallel link in
GALM / RUNAlarm and run LEDs
HSOCState-of-charge LEDs
IB+Battery positive (from the last module in the string)
JBATTERY COMMCommunication to the battery modules
KMCBDC circuit breaker
LON/OFFStart / stop button
Tanami HV · Installation and Operating ManualRev 1.0.0
PositionLabelFunction
MDigital out / in (10-pin)Air-conditioner RS485; 2 dry-contact outputs; emergency stop and fire-suppression inputs
NFunctional interface (8-pin)12 V / 24 V DC auxiliary output (10 W); run, alarm and lamp outputs
OB−Battery negative (from the module next to the PDU)

Use Cat5e Ethernet cable for every IN, OUT, TCP/IP and CAN/RS485 connection.

CAN/RS485 port pin assignment

Pin12345678
Signal11 V GND12 V11 VCAN_HCAN_L12 V GNDRS485 BRS485 A

Pins are numbered 1–8 from left to right, looking into the socket with the latch slot down.

Supply pins

Pins 1, 2, 3 and 6 carry 11–12 V DC. Do not use a straight-through cable to the inverter. Make up the inverter cable with only CAN_H and CAN_L (pins 4 and 5), or RS485 A and B (pins 7 and 8), wired to the inverter's pin order, and leave pins 1, 2, 3 and 6 unconnected unless AERL's setting guide for the inverter says otherwise.

4.5LED Status

The three LED groups on the PDU (ALM, RUN and SOC) show the system status.

LEDStateMeaning
ALMRedFault
ALMOffNo fault
RUNGreen, steadyRunning, communicating with the inverter
RUNGreen, slow flashRunning, no communication
RUNOffSystem off
SOC4 green75% < SOC ≤ 100%
SOC3 green50% < SOC ≤ 75%
SOC2 green25% < SOC ≤ 50%
SOC1 green0% < SOC ≤ 25%
SOCFirst LED fast flash (0.5 s on, 0.5 s off)SOC below 5%
SOCLast lit LED flashes (1 s on, 1 s off)Discharging
SOCLast lit LED slow flash (2 s on, 2 s off)Charging
Tanami HV · Installation and Operating ManualRev 1.0.0

4.6Battery Module Specification

ParameterTanami-M8.06
Nominal energy8.06 kWh (8064 Wh)
Capacity105 Ah
Nominal voltage76.8 V DC
Operating voltage range60–87.6 V DC
Max. continuous current105 A (1C)
Peak current150 A (5 s)
ChemistryLiFePO4 (LFP), prismatic cells
Dimensions (W × H × D)490 × 135 × 786 mm
Weight65 kg
IP ratingIP20
Operating temperatureCharge: −10 to 55 °C / Discharge: −20 to 55 °C
Round-trip efficiency≥ 95%
Country of manufacturePeople's Republic of China

4.7PDU Specification

ParameterTanami-PDU
Operating voltage200–1000 V DC
Max. current150 A
CommunicationsCAN / RS485 / Modbus RTU / Modbus TCP
Parallel systemsUp to 16
Dry contacts2 outputs, 2 inputs
Auxiliary output12 V / 24 V DC, 10 W
Dimensions (W × H × D)490 × 200 × 545 mm
Weight15 kg
Tanami HV · Installation and Operating ManualRev 1.0.0

4.8System Configurations

Modules6789
Nominal energy (kWh)48.3856.4564.5172.58
Nominal voltage (V)460.8537.6614.4691.2
Operating voltage (V)360–526420–613480–701540–788
EnclosureRACK9RACK9RACK9RACK9 or CAB9-OUTD
Weight with modules (kg)495560625690 (rack), 1050 (cabinet)

All systems: max. continuous current 105 A, peak 150 A (5 s), round-trip efficiency ≥ 95%. Check that the system's operating voltage range lies within the inverter's battery voltage range before choosing the module count.

Compatible inverters: Solinteg, Solis and Deye high-voltage hybrid and battery inverters. Contact AERL to confirm the model and for its battery settings.

Prospective short-circuit current (for the AS/NZS 5139 arc-flash calculation): contact AERL.

4.9Enclosure Specification

ParameterTanami-RACK9Tanami-CAB9-OUTD
Modules6–99
InstallationIndoorOutdoor
Dimensions (W × H × D)564 × 1773 × 783 mm780 × 1980 × 1300 mm
IP ratingIP20IP55
CoolingNatural convectionAir-conditioning (HVAC)
Auxiliary supplyNone230 V AC, 50 Hz
Fire suppressionNone (site system)Aerosol unit
FixingAdjustable feet; anchored to the floor4 × M6 × 80 expansion bolts
Altitude≤ 3000 m≤ 3000 m
HumidityUp to 95% (non-condensing)Up to 95% (non-condensing)

Certifications (system): IEC 62619, UN 38.3, CE, VDE-AR-E 2510-50, IEC 62040-1; outdoor cabinet also EN ISO 13849-1.

Tanami HV · Installation and Operating ManualRev 1.0.0
Tanami-CAB9-OUTD outdoor cabinet, door closed.
Figure 4.4 Tanami-CAB9-OUTD outdoor cabinet, door closed.
Tanami HV · Installation and Operating ManualRev 1.0.0
Tanami-RACK9 indoor rack with nine modules and the PDU.
Figure 4.5 Tanami-RACK9 indoor rack with nine modules and the PDU.
Tanami HV · Installation and Operating ManualRev 1.0.0
05

InstallationInstallation location and environment, tools

Install the Tanami system in accordance with this manual, AS/NZS 3000, AS/NZS 5139 and the inverter manufacturer's instructions.

5.1Installation Location and Environment

5.2Tools

5.3Clearances and Fixing

Keep at least these clearances around each enclosure:

Fix the outdoor cabinet to the plinth through its four fixing holes with M6 × 80 expansion bolts. Level the indoor rack on its adjustable feet, then anchor it to the floor through its base with fixings suited to the floor, so it cannot tip.

Tanami HV · Installation and Operating ManualRev 1.0.0
Minimum clearances between systems and walls (top view), with and without an inverter.
Figure 5.1 Minimum clearances between systems and walls (top view), with and without an inverter.
Outdoor cabinet base and fixing-hole layout.
Figure 5.2 Outdoor cabinet base and fixing-hole layout.
Tanami HV · Installation and Operating ManualRev 1.0.0

5.4Outdoor Cabinet Cable Entries

The outdoor cabinet has glands on both sides, near the base:

Both sides also have an overpressure relief valve and forklift pockets (230 mm apart, 700 mm across). The inverter can be mounted on the bracket on the right side of the cabinet.

Cable entries on the right side of the outdoor cabinet: AC supply, COM (communication), INV, and the two DC glands P− (left) and P+ (right).
Figure 5.3 Cable entries on the right side of the outdoor cabinet: AC supply, COM (communication), INV, and the two DC glands P− (left) and P+ (right).

5.5Step 1: Install the Modules and PDU

  1. Outdoor cabinet: install the PDU on the bottom shelf first, then the nine modules above it, from the bottom up.
  2. Indoor rack: install the PDU in the top position, then the modules in the shelves directly below it, working down, so that every module is next to the one before and the cables reach. With 6 or 7 modules the lowest shelves stay empty.
  3. Fasten each module and the PDU to the enclosure with the screws supplied, torqued to 8 N·m.
Modules are always live

Make sure the PDU breaker (MCB) is OFF before you connect any cable. The modules have no switch: each module's terminals carry 76.8 V DC nominal, and the series string reaches the full system voltage (up to 788 V DC) as you connect it.

Tanami HV · Installation and Operating ManualRev 1.0.0

5.6Step 2: Connect the Protective Earth

Connect the enclosure's PE point to the site earth with a conductor sized to AS/NZS 3000 and AS/NZS 5139, before you connect any DC cable. In the outdoor cabinet the PE point is inside, at the bottom of the door opening.

5.7Step 3: Connect the Battery Negative

Connect battery cable B from the negative (−) connector of the module next to the PDU to B− on the PDU: the bottom module in the outdoor cabinet (PDU at the bottom), or the top module in the indoor rack (PDU at the top).

5.8Step 4: Connect the Modules in Series

  1. Connect the modules to each other in series with battery cable A: the positive (+) of one module to the negative (−) of the next.
  2. Connect the positive (+) of the last module in the string (the module furthest from the PDU) to B+ on the PDU with battery cable C.
Notice

Always plug the black connector into a negative (−) socket and the orange connector into a positive (+) socket.

Before connecting cable C, measure the string voltage with a multimeter rated for 1000 V DC, between the free positive (+) connector of the last module and the negative (−) connector of the module next to the PDU. Expect 60–87.6 V per module (about 77–80 V per module as delivered).

5.9Step 5: Connect the Internal Communication

  1. Connect communication cable B from BATTERY COMM on the PDU to COM 2 on the first module (the module next to the PDU).
  2. Connect the remaining modules in a chain with communication cable A: COM 1 of each module to COM 2 of the next.
  3. Plug the blue termination resistor into COM 1 of the last module in the chain.
Tanami HV · Installation and Operating ManualRev 1.0.0

5.10Step 6: Connect the Inverter

  1. Run the inverter DC cables and a Cat5e communication cable into the enclosure (outdoor cabinet: through the glands on the right side).
  2. Connect the communication cable from CAN/RS485 on the PDU to the inverter's battery communication port. Wire the inverter end to suit the inverter, with the supply pins left unconnected (section 4.4).
  3. Connect P− and P+ on the PDU to the inverter's battery terminals with double-insulated cables rated for at least 1000 V DC and 150 A (35 mm² copper is typical; size the cable to AS/NZS 3008 for the route and length), terminated in P+ (orange) and P− (black) quick-connect plugs that mate with the PDU (available from AERL). Fit a DC isolator rated for the system voltage between the battery and the inverter, as AS/NZS 5139 requires.
  4. Plug the black termination resistor into OUT on the PDU. (In a parallel system, only the last PDU gets it: section 5.13.)

Set up the inverter's battery settings for the Tanami HV and the number of modules. Contact AERL for the settings for your inverter.

5.11Step 7: Connect the AC Supply (Outdoor Cabinet)

The outdoor cabinet needs a 230 V, 50 Hz AC supply for its air-conditioner and controls.

  1. Run the supply cable through the AC gland on the right side of the cabinet. Use copper conductors of at least 4 mm².
  2. Connect active and neutral to the supply terminals in the cabinet, and earth to the PE terminal.
  3. Protect the supply with a dedicated 16 A circuit breaker at the switchboard, with RCD protection where AS/NZS 3000 requires it.

5.12Step 8: Dry Contacts and Safety Inputs

The PDU has two plug-in terminal blocks: the 8-pin functional interface (N in section 4.4) and the 10-pin digital out / in block (M). In the outdoor cabinet they come pre-wired to the cabinet's indicator lamps, air-conditioner, emergency stop and fire suppression.

BlockTerminalFunction
8-pin24V, GND24 V DC auxiliary output
8-pin12V, GND12 V DC auxiliary output
8-pinLED RUNRun lamp (green wire)
8-pinLED ALMAlarm lamp (red wire)
Tanami HV · Installation and Operating ManualRev 1.0.0
BlockTerminalFunction
8-pinLED+, GNDLamp supply (brown wire)
10-pin485AHVAC RS485+
10-pin485BHVAC RS485−
10-pinCOM2, NO2 / COM1, NO1Dry-contact outputs 2 and 1 (normally open): alarm and run signals for external equipment, such as a site alarm or generator start
10-pinDI1, GNDEmergency stop input (GND is the 8th terminal from the left)
10-pinDI2, GNDFire suppression (aerosol) input (GND is the 7th terminal from the left)
PDU terminal blocks: terminal numbers and functions.
Figure 5.4 PDU terminal blocks: terminal numbers and functions.
Tanami HV · Installation and Operating ManualRev 1.0.0

5.13Connecting Systems in Parallel

Up to 16 Tanami systems can run in parallel on one inverter DC bus. All systems in parallel must have the same number of modules.

  1. Connect each system's P+ and P− to a common DC bus or combiner, with a DC isolator for each system.
  2. Link the PDUs in a chain with Cat5e cable: OUT of the first PDU to IN of the next, and so on.
  3. Connect the inverter's communication cable to CAN/RS485 on the first PDU only.
  4. Plug the black termination resistor into OUT of the last PDU.

The PDU that the inverter is connected to acts as the master, and the BMS addresses the other PDUs in the chain automatically when the systems start. Start the other systems first and the master last (section 6.2).

Before closing the DC isolators between systems, check that their voltages are within 10 V of each other (charge or discharge a system first if they are not), to limit the current that flows between them. Use DC cables of the same size and length from each system to the common bus, so that the systems share current evenly.

Tanami HV · Installation and Operating ManualRev 1.0.0
06

Commissioning and OperationBefore start-up, start-up, shut-down, black start

6.1Before Start-Up

Before starting the system, check that:

6.2Start-Up

  1. Outdoor cabinet: switch on the AC supply breaker for the cabinet.
  2. Switch the PDU's MCB to ON.
  3. Press the ON/OFF button on the PDU.

The RUN and SOC LEDs light when the system has started. Then close the DC isolators and start the inverter as its manufacturer instructs.

In a parallel system, start each system in turn with steps 1–3, the master (the PDU the inverter is connected to) last, then close the DC isolators.

6.3Shut-Down

  1. Stop the inverter and open the DC isolators.
  2. Press and hold the ON/OFF button on the PDU for 3 seconds.
  3. The PDU's MCB trips automatically. Move it fully to OFF before the next start-up.
  4. Outdoor cabinet: switch off the AC supply breaker. The system is now off.
Tanami HV · Installation and Operating ManualRev 1.0.0

6.4Black Start

The Tanami can black-start an off-grid inverter: it energises the DC bus from the battery so the inverter can start without a grid or generator.

  1. Start the system (section 6.2, steps 1–3) and close the DC isolator between the battery and the inverter.
  2. Press the ON/OFF button three times to activate black start.
  3. Start the inverter. Once it is running, it takes over and the battery charges and discharges normally.
Dangerous voltage

After black start is activated, P+ and P− carry the full system voltage (up to 788 V DC). Take extreme care.

6.5Monitoring and Firmware

The Tanami is monitored through AERL Cloud. An AERL Nexus Gateway on the site network reads the PDU over Modbus TCP and sends the battery's data to AERL Cloud, where the owner and installer can see the state of charge, voltages, currents, temperatures and alarms, and AERL can update the battery firmware remotely.

  1. Connect the PDU's TCP/IP port to the site network switch, or directly to the Nexus Gateway, with a Cat5e cable. In a parallel system, connect the master PDU.
  2. Install and connect the Nexus Gateway as described in the Nexus user manual.
  3. Register the site in AERL Cloud, or contact AERL to have the system added to your account.
Tanami HV · Installation and Operating ManualRev 1.0.0
07

Maintenance

The battery modules need no routine maintenance. Check the system at least every 6 months:

Do not unplug any cable while the system is running. Shut the system down (section 6.3) before any work inside the enclosure. The module string stays live after shut-down (section 3.1).

Tanami HV · Installation and Operating ManualRev 1.0.0
08

Adding Modules or Systems

Modules can be added to a system, or systems added in parallel, at any time during the product's life. All modules must be Tanami-M8.06, and every module count must stay within the enclosure's range and the inverter's voltage range:

Shut the system down (section 6.3) before adding modules. When it restarts, the BMS detects and addresses the new modules automatically. Then update the inverter's battery settings for the new module count.

Tanami HV · Installation and Operating ManualRev 1.0.0
09

Battery End of Life and Recycling

When a Tanami battery reaches the end of its life:

  1. Return the battery to AERL for assessment.
  2. Batteries that can be refurbished are tested and refurbished for charitable, community or educational use.
  3. Batteries that cannot be refurbished are recycled, to recover as much material as possible.
Tanami HV · Installation and Operating ManualRev 1.0.0
10

Warranty

The Tanami HV is covered by AERL's warranty: 10 years for the battery modules (70% state of health) and the PDU, 2 years for the indoor rack and the outdoor cabinet, and 1 year for the cabinet's aerosol fire-suppression unit. Conditions apply: see the Tanami HV Warranty Statement, at aerl.com.au. Register the system at aerl.com.au/warranty-registration.

Tanami HV · Installation and Operating ManualRev 1.0.0

Thank You for Choosing AERL

If you have any questions or need support, contact AERL.

Sincerely,

The AERL Team

AERL Pty Ltd · 1/75 Bluestone Circuit, Seventeen Mile Rocks QLD 4073 · 1800 950 865 · [email protected] · aerl.com.au

Tanami HV · Installation and Operating ManualRev 1.0.0

Notes

Tanami HV · Installation and Operating ManualRev 1.0.0

Australian Energy Research Laboratories

Address

1/75 Bluestone Circuit
Seventeen Mile Rocks QLD 4073
Australia

Contact

[email protected]
[email protected]

aerl.com.au Phone1800 950 865